Friedrich 9315342935-01 Скачать руководство пользователя страница 2

1

2

3

4

1

2

3

L1

L2

G

G

LO

HI

OUTDOOR UNIT

  1. Check if the piping connections are secure.

  2. Check that the stems of 2-way valve and 3-way valve are closed 

fully.

  3. Connect the gauge manifold charge hose to the charging port 

of the 3-way valve (side with the projection for pushing in the 
valve core).

  4. Open the low pressure side valve of the gauge manifold fully.

  5. Operate the vacuum pump and start pump down.

  6. Slowly loosen the fl are nut of the 3-way valve and check if air 

enters, then retighten the fl are nut.

    (When the fl are nut is loosened the operating sound of the 

vacuum pump changes and the reading of the compound 
pressure gauge goes from minus to zero.)

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in 
the outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and 
do not operate it during the following work.

  Set the unit on a strong stand, such as one made of concrete blocks to 

minimize shock and vibration.

  Do not set the unit directly on the ground because it will cause trouble.

Connector cover removal

  Remove the tapping screws.

Installing the connector cover

(1)  After inserting the two front hooks, then insert the rear hook.
(2)  Tighten the tapping screws.

  7.  Pump down the system for at least 15 minutes, then check if the 

compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

  8. At the end of pump down, close the low pressure side gauge 

of the gauge manifold fully and stop the vacuum pump.

  9. Slowly loosen the valve stem of the 3-way valve. When the 

compound pressure gauge reading reaches 0.1-0.2 MPa, 
retighten the valve stem and disconnect the charge hose from 
the 3-way valve charging port.

    (If the stem of the 3-way valve is opened fully before the 

charge hose is disconnected, it may be diffi cult to disconnect 
the charge hose.)

 10. Fully open the valve stems of the 2-way valve and 3-way valve 

using a hexagon wrench. (After the valve stem begins to turn, 
turn it with a torque of less than 2.14 ft•lbs (30 kgf•cm) until it 
stops turning.)

 11.  Firmly tighten the 2-way valve and 3-way valve blank cap and 

the charging port cap.

ELECTRICAL WIRING (OUTDOOR UNIT)

1. Remove the screws, then remove the control box cover.
2. Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut.
3. Connect inter-unit wire harness and power supply to the terminal.

 Refer to the wiring diagram 

4. Use the screws to install the control box cover.

FINISHING

(1)  Insulate between pipes.

  For rear, right, and bottom piping, overlap the connection pipe heat insu-

lation and indoor unit pipe heat insulation and bind them with vinyl tape 
so that there is no gap.

  For left and left rear piping, butt the connection pipe heat insulation and 

indoor unit pipe heat insulation together and bind them with and vinyl 
tape so that there is no gap.

  For left and left rear piping, wrap the area which accommodates the rear 

piping housing section with cloth tape.

  For left and left rear piping, bind the connection cord to the top of the pipe 

with vinyl tape.

  For left and left rear piping, bundle the piping and drain hose together by 

wrapping them with cloth tape over the range within which they fi t into 
the rear piping housing section.

(2)  Temporarily fasten the connection cord along the connection pipe with vinyl 

tape. (Wrap to about 1/3 the width of the tape from the bottom of the pipe so 
that water does not enter.)

(3)  Fasten the connection pipe to the outside wall with saddles, etc.
(4)  Fill the gap between the outside wall pipe hole and the pipe with sealer 

so that rain water and wind cannot blow in.

(5)  Fasten the drain hose to the outside wall, etc.

FRONT PANEL REMOVAL AND INSTALLATION

THE INTAKE GRILLE REMOVAL

(1)  Open the intake grille.
(2)  Pull down the knob.
(3)  Lift the intake grille upward, until the axle at the top of the 

intake grille is removed.

THE INTAKE GRILLE INSTALLATION

(1) The fi xing axle of the intake grille is installed on the Panel.
(2)  Lay down the intake grille.

THE FRONT PANEL REMOVAL

(1)  Remove intake grille (Reference the intake grille removal.)
(2)  Remove six screws.
(3)  The thumb is hung on the lower part as shown in the fi gure, 

and it pulls to the front, pushing [-] mark , and bottom hooks 
(two position) is removed from wall hook bracket.

(4) The front panel is pulled to the front, raising the upper surface, 

and a front panel is removed.

THE FRONT PANEL INSTALLATION

(1) Firstly, fi t the lower part of the front panel, and insert top and 

bottom hooks. (Three top sides)

(2)  Six screws is attached.
(3)  The intake grille is attached.

POWER

Transmitter section

Test run button

TEST RUNNING

  Perform test operation and check items 1 and 2 below.

  For the test operation method, refer to the operating manual.

  The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit 

while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test 
run button with the tip of a ball-point pen, etc.)

  To end test operation, press the remote control unit START/STOP button.

 

(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultane-
ously fl ash slowly.)

1. INDOOR 

UNIT

(1)  Is operation of each button on the remote control unit normal?
(2)  Does each lamp light normally?
(3)  Do the air fl ow-direction louver operate normally?
(4)  Is the drain normal?

2. OUTDOOR 

UNIT

(1)  Is there any abnormal noise and vibration during operation?
(2)  Will noise, wind, or drain water from the unit disturb the neighbors?
(3)  Is there any gas leakage?

REMOTE CONTROL UNIT INSTALLATION

1.  REMOTE CONTROL UNIT HOLDER INSTALLATION

 

Install the remote control unit with a distance of 23 ft
(7 m) between the remote control unit and the photo-
cell as the criteria. However, when installing the remote 
control unit, check that it operates positively.

 

Install the remote control unit holder to a wall, pillar, 
etc. with the tapping screw.

  

Tightening 

torque

Blank cap (2-way valve)  14.75 to 18.44 ft•lbs (200 to 250 kgf•cm)

Blank cap (3-way valve)  22.12 to 25.81 ft•lbs (300 to 350 kgf•cm)

Charging port cap 

7.37 to 8.85 ft•lbs (100 to 120 kgf•cm)

Flare nut

3-way valve

-0.1 MPa
(-76 cmHg 
-1 bar)

High 
pressure  
side valve 
(closed)

Low pressure 
side valve

Blank cap

Charge 
hose

Vacuum pump

2-way valve

Valve stem

Charge hose

Charging port cap

Charging port

Gauge manifold

Compound pressure gauge

Pressure gauge

 

CAUTION

  (1)  Refrigerant must not be discharged into atmos-

phere.

  (2)  After connecting the piping , check the joints for 

gas leakage with gas leak detector. 

Tapping screw

Hooks

Connector cover

Hook

 

WARNING

  (1)  Install the unit where it will not be tilted by more 

than 5°.

 (2)  When installing the outdoor unit where it may 

exposed to strong wind, fasten it securely.

 WARNING

Be sure to comply with local codes while running 
the wire from the indoor unit to the outdoor unit 
(size of wire and wiring method, etc. ).

Every wire must be connected fi rmly.

No wire should be allowed to touch refrigerant 
tubing, the compressor or any moving part.

Loose wiring may cause the terminal to overheat 
or result in unit malfunction. A fi re hazard may 
also exist. Therefore, be sure all wiring is tightly 
connected.

Connect wires to the matching numbers of 
terminals.

NOTE:

 

Connector trade size for this unit is 1/2” (12.7 mm). The connector 
can be bought at a hardware store. Refer to 

How to connect wiring 

to the terminals

 for instructions on connecting depending on the 

wire type you are using.

 

The fuse located in the outdoor unit provides power supply protec-
tion and may blow when power is applied if the system has been 
incorrectly wired.

Indoor unit

Terminal

Grounding line

Control line

(Inter Unit)
Power line

DISCONNECT
SWITCH 
(FIELD SUPPLY)

Outdoor unit

Terminal

PO

WER SUPPL

Y

Single-phase, 208/230V 

Earth screw

Indoor unit
terminal block

Outdoor unit
terminal block

Disconnect switch

Earth screw

Power supply line

Overlap the insulation

Bind the pipes together so 
that there is no gap.

Connection pipe 
(heat insulation)

Vinyl tape

Indoor unit pipe
(heat insullation)

Check the following:

GOOD

Lifted up

Saddle

Wave

End in water

BAD

BAD

BAD

Drain hose

For connection from the left rear

Connection cord

Wall pipe

Connection pipe

Drain hose

Left piping

Connection cord

Pipe

Drain hose

Pipe

Drain hose

Cloth tape

Wrap with 
cloth tape

Pipe

(Saddle)

(Outside wall cap)

(Sealer putty)

(Outdoors)

Wall

 WARNING

  (1)  The rated voltage of this product is 208/230 V AC 

60 Hz.

  (2)  Before turning on the power, check if the voltage 

is within the 208 V 

-

10% to 230 V +10% range.

 (3)  Always use a special branch circuit and install a 

special receptacle to supply power to the room air 
conditioner.

 (4)  Use a circuit breaker and receptacle matched to 

the capacity of the air conditioner.

  (5)  Do not extend the power cord.

 (6)  Perform wiring work in accordance with standards 

so that the air conditioner can be operated safely 
and positively.

 (7)  Install a leakage circuit breaker in accordance 

with the related laws and regulations and electric 
company standards.

 CAUTION

 (1)  The power source capacity must be the sum of 

the air conditioner current and the current of other 
electrical appliances. When the current contracted 
capacity is insuffi cient, change the contracted 
capacity.

  (2)  When the voltage is low and the air conditioner is 

diffi cult to start, contact the power company the 
voltage raised.

CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operat-
ing manual:
(1)  Starting and stopping method, operation switching, temperature 

adjustment, timer, air fl ow switching, and other remote control unit 
operations.

(2)  Air fi lter removal and cleaning, and how to use the air louvers.
(3)  Give the operating and installation manuals to the customer.

 CAUTION

  (1)  Check that the indoor unit correctly receives the 

signal from the remote control unit, then install 
the remote control unit holder.

 (2)  Select the remote control unit holder selection 

site by paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat 
from a stove, etc.

Remote control unit 
holder fi xing

Remote control 
unit holder

Tapping 
screw 
(small)

Remote control 
unit mounting

Remote con-
trol unit

2

 

Push

1

 

Set

Front panel

Bearing

Mounting shaft

Intake grille

Intake grille

Knob

Top hooks
(two sides)

Top holes (two sides)

Top hole (center)

Top hook (center)

Front panel

Indoor unit

 

CAUTION

Install the front panel and INTAKE GRILLE securely. If installation is imperfect, the front panel or INTAKE GRILLE 
may fall off and cause injury.

Wall hook bracket

Front panel

Push

[-] mark

Screws (6 position)

Push

Front panel

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or forced cooling 
operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced cooling operation.)

(1)  Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening 

the low-pressure valve slightly.

(2)  Close the valve stem of 2 way valve completely.
(3)  Start the cooling operation or following forced cooling operation.
 

When using the remote control unit

 

Press the TEST RUN button after starting the cooling operation by the remote control unit.

 

The operation indicator lamp and timer indicator lamp will begin to fl ash simultaneously during test run.

 

When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)

 

Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. 

 

(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4)  Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5)  Stop the operation.
 

• Press the START/STOP button of the remote control unit to stop the operation.

 

• Press the MANUAL AUTO button when stopping the operation from indoor unit side.

 

  (It is not necessary to press on keeping for more than 10 seconds.)

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above  248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insula-
tion around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the 
expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specifi ed, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 68 °F).

 

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal pres-
sure in the refrigeration cycle that leads to breakage and even injury.

Lock nut

Control box cover

Inter-unit wire 
harness

Power supply

Inter-unit wire 
hamess

9315342935_IM_EN.indd   2

9315342935_IM_EN.indd   2

9/27/2010   9:59:21 AM

9/27/2010   9:59:21 AM

Отзывы: