background image

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

FINISHING

(1)  Insulate between pipes.

  For rear, right, and bottom piping, overlap the connection pipe heat in-

sulation and indoor unit pipe heat insulation and bind them with vinyl 
tape so that there is no gap.

  For left and left rear piping, butt the connection pipe heat insulation and 

indoor unit pipe heat insulation together and bind them with and vinyl 
tape so that there is no gap.

  For left and left rear piping, wrap the area which accommodates the rear 

piping housing section with cloth tape.

  For left and left rear piping, bind the connection cord to the top of the 

pipe with vinyl tape.

  For left and left rear piping, bundle the piping and drain hose together 

by wrapping them with cloth tape over the range within which they fi t 
into the rear piping housing section.

(2)  Temporarily fasten the connection cord along the connection pipe with 

vinyl tape. (Wrap to about 1/3 the width of the tape from the bottom of the 
pipe so that water does not enter.)

(3)  Fasten the connection pipe to the outside wall with saddles, etc.
(4)  Fill the gap between the outside wall pipe hole and the pipe with sealer 

so that rain water and wind cannot blow in.

(5)  Fasten the drain hose to the outside wall, etc.

FRONT PANEL REMOVAL AND INSTALLATION

THE INTAKE GRILLE REMOVAL

(1)  Open the intake grille.
(2)  Pull down the knob.
(3)  Lift the intake grille upward, until the axle at the top of the 

intake grille is removed.

THE INTAKE GRILLE INSTALLATION

(1) The fi xing axle of the intake grille is installed on the Panel.
(2)  Lay down the intake grille.

THE FRONT PANEL REMOVAL

(1)  Remove intake grille (Reference the intake grille removal.)
(2)  Remove six screws.
(3)  The thumb is hung on the lower part as shown in the fi gure, 

and it pulls to the front, pushing [-] mark , and bottom hooks 
(two position) is removed from wall hook bracket.

(4)  The front panel is pulled to the front, raising the upper sur-

face, and a front panel is removed.

THE FRONT PANEL INSTALLATION

(1) Firstly, fi t the lower part of the front panel, and insert top 

and bottom hooks. (Three top sides)

(2)  Six screws is attached.
(3)  The intake grille is attached.

TEST RUNNING

 WARNING

  (1)  Install the unit where it will not be tilted by more than 3°. However, do not install the unit with it tilted 

towards the side containing the compressor.

  (2)  When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

Check the following:

GOOD

Lifted up

Saddle

Wave

End in water

BAD

BAD

BAD

Drain hose

For connection from the left rear

Connection cord

Wall pipe

Connection pipe

Drain hose

Left piping

Connection cord

Pipe

Drain hose

Pipe

Drain hose

Cloth tape

Wrap with 
cloth tape

Pipe

(Saddle)

(Outside wall cap)

(Sealer putty)

(Outdoors)

Wall

Front panel

Bearing

Mounting shaft

Intake grille

Intake grille

Knob

Top holes (two sides)

Top hole (center)

Top hook (center)

Front panel

Indoor unit

 CAUTION

Install the front panel and INTAKE GRILLE securely. If installation is imperfect, the front panel or INTAKE GRILLE may fall 
off and cause injury.

Wall hook bracket

Front panel

Push

[-] mark

Screws (6 position)

Push

Front panel

AIR PURGE

Lo

Hi

Gauge manifold

Service hose 

Vacuum pump

Connecting pipe

Blank cap

Hexagon wrench

3-way valve

Charging port

Cap

Service hose 
with valve core

Outdoor unit

Use a 4 mm hexa-
gon wrench.

(1)  Remove the cap, and connect the gauge manifold and the vacu-

um pump to the charging valve by the service hoses.

(2)  Vacuum the indoor unit and the connecting pipes until the pres-

sure gauge indicates –0.1 MPa (–76 cmHg).

(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum 

pump for at least 60 minutes.

(4)  Disconnect the service hoses and fit the cap to the charging 

valve to the specifi ed torque.

(5)  Remove the blank caps, and fully open the spindles of the 

3-way valves with a hexagon wrench [Torque: 6~7 N·m (60 to 70 
kgf·cm)].

(6) Tighten the blank caps of the 3-way valve to the specified 

torque.

 CAUTION

Use a clean gauge mani-
fold and charging hose for 
R410A exclusively.

ELECTRICAL WIRING (OUTDOOR UNIT)

(1)  Service cover removal

•  Remove the two mounting screws.
•  Remove the service cover by pushing downwards.

(2)  Fasten the power supply cord and the connection cord to the 

conduit holder using the lock nut. 

 

(open the knock out holes if necessary)

(3)  Connect the power supply cord and the connection cord to ter-

minal.

(4)  Fasten the power supply cord and connection cord with cord 

clamp.

Hook
(3 places)

30 mm (1

-3/1

6")

Keep the earth wire longer than the other wires.

 CAUTION

Be sure to comply with local codes while running the 
wire from the indoor unit to the outdoor unit (size of 
wire and wiring method, etc. ).

Every wire must be connected fi rmly.

No wire should be allowed to touch refrigerant tubing, 
the compressor or any moving part.

Loose wiring may cause the terminal to overheat or 
result in unit malfunction. A fi re hazard may also exist. 
Therefore, be sure all wiring is tightly connected.

Connect wires to the matching numbers of terminals.

1

2

3

1

2

3

G

G

L1

L2

INDOOR

INDOOR UNIT

OUTDOOR UNIT

TERMINAL

DISCON-
NECT 
SWITCH
(FIELD 
SUPPLY)

Grounding
line

14AWG
(Inter-unit)
Power lines

230/208 V

230/208 V

230/208 V

TERMINAL

P

ower supply line

Single-phase, 230/208 

V

G

G

Control box

Terminal

Power supply cord

Connection cord 
(indoor unit and 
outdoor unit 
connection cord)

Cord clamp

CAUTION

When connecting the power supply cord, make sure that 
the phase of the power supply matches with the phase of 
the terminal board. If the phases do not match, the 
compressor will rotate in reverse and will not be able to 
compress.

 WARNING

Disconnect switch  for over current protection given in 
the table below is to be installed between the indoor 
unit and the outdoor unit.

Disconnect switch

20A

Lock 
nut

Inter-unit line

Power supply

 CAUTION

1

  Do not purge the air with refrigerants, but use a 

vacuum pump to vacuum the installation! There is no 
extra refrigerant in the outdoor unit for air purging!

2

  Use a vacuum pump and gauge manifold and charg-

ing hose for R410A exclusively. Using the same vacu-
um for different refrigerants may damage the vacuum 
pump or the unit.

3

 After connecting the piping, check the all joints for 

gas leakage with gas leak detector.

4

  When inspecting gas leakage, always use the vacuum 

pump for pressure. Do not use nitrogen gas.   

 WARNING

Do not turn on the power until all installation work is complete .

CAUTION

When restarting after a long period of disuse in the winter, turn 
the power switch on at least 12 hours before starting the unit.

POWER

 WARNING

  (1)  The rated voltage of this product is 208/230 V AC 

60 Hz.

  (2)  Before turning on the power, check if the voltage 

is within the 208 V -10 % to 230 V +10% range.

  (3)  Always use a special branch circuit and install a 

special receptacle to supply power to the room 
air conditioner.

  (4)  Use a circuit breaker and receptacle matched to 

the capacity of the air conditioner.

  (5)  Do not extend the power cord.
  (6)  Perform wiring work in accordance with stan-

dards so that the air conditioner can be operated 
safely and positively.

  (7)  Install a leakage circuit breaker in accordance 

with the related laws and regulations and electric 
company standards.

CAUTION

  (1)  The power source capacity must be the sum of 

the air conditioner current and the current of 
other electrical appliances. When the current 
contracted capacity is insuffi cient, change the 
contracted capacity.

  (2)  When the voltage is low and the air conditioner is 

diffi cult to start, contact the power company the 
voltage raised.

CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the oper-
ating manual:
(1)  Starting and stopping method, operation switching, temperature 

adjustment, timer, air fl ow switching, and other remote controller 
operations.

(2)  Air fi lter removal and cleaning, and how to use the air louvers.
(3)  Give the operating and installation manuals to the customer.

Transmitter section

Test run button

  Perform test operation and check items 1 and 2 below.

  For the test operation method, refer to the operating manual.

  The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote controller 

while the air conditioner is running, (Point the transmitter section of the remote controller toward the air conditioner and press the test 
run button with the tip of a ball-point pen, etc.)

  To end test operation, press the remote controller START/STOP button.

 

(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultane-
ously fl ash slowly.)

1. INDOOR 

UNIT

(1)  Is operation of each button on the remote controller normal?
(2)  Does each lamp light normally?
(3)  Do the air fl ow-direction louver operate normally?
(4)  Is the drain normal?

2. OUTDOOR 

UNIT

(1)  Is there any abnormal noise and vibration during operation?
(2)  Will noise, wind, or drain water from the unit disturb the neighbors?
(3)  Is there any gas leakage?

(1)  Outdoor unit to be fasten with bolts at the four places 

indicated by the arrows without fail.

(2) F i x s e c u r e l y  w i t h 

b o l t s   o n   a   s o l i d 
block. (Use 4 sets of 
commercially avail-
able M10 bolt, nut 
and washer.)

(3)  Since the drain water fl ows out of the outdoor unit during heat-

ing operation, install the drain pipe and connect it to a commer-
cial 16 mm (5/8") hose. (Reverse cycle model only)

(4)  When installing the drain pipe, plug all the holes other than the 

drain pipe mounting hole in the bottom of the outdoor unit with 
putty so there is no water leakage. (Reverse cycle model only)

 CAUTION

When the outdoor temperature is 32 °F or less, do not use the ac-
cessory drain pipe and drain cap. If the drain pipe and drain cap 
are used, the drain water in the pipe may freeze in extremely cold 
weather. (Reverse cycle model only)

Bolt

Nut 

Block

REMOTE CONTROLLER INSTALLATION

1.  REMOTE CONTROLLER HOLDER INSTALLA-

TION

• 

Install the remote controller with a distance of 23 ft (7 
m) between the remote controller and the photocell 
as the criteria. However, when installing the remote 
controller, check that it operates positively.

• 

Install the remote controller holder to a wall, pillar, 
etc. with the tapping screw.

CAUTION

  (1) Check that the indoor unit correctly receives the   

signal from the remote controller, then install the 
remote controller holder.

  (2)  Select the remote controller holder selection site 

by paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the 
heat from a stove, etc.

Remote controller 
holder fi xing

Remote controller 
holder

Tapping 
screw 
(small)

Remote controller 
mounting

Remote controller

Push

Set

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation 
or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the 
forced cooling operation.)

(1)  Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve (large) and 

opening the low-pressure valve slightly.

(2)  Close the valve stem of 3 way valve (small) completely.
(3)  Start the cooling operation or following forced cooling operation.
 

When using the remote controller

 

Press the TEST RUN button after starting the cooling operation by the remote controller.

 

The operation indicator lamp and timer indicator lamp will begin to fl ash simultaneously during test run.

 

When using the MANUAL AUTO button of the indoor unit (The remote controller is lost, and so on.)

 

Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. 

 

(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4)  Close the valve stem of 3 way valve (large) when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5)  Stop the operation.
 

• Press the START/STOP button of the remote controller to stop the operation.

 

• Press the MANUAL AUTO button when stopping the operation from indoor unit side.

 

  (It is not necessary to press on keeping for more than 10 seconds.)

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above  248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insu-
lation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if 
the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specifi ed, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 68 °F).

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation 3 way valve open. This may cause abnormal pres-
sure in the refrigeration cycle that leads to breakage and even injury.

This air conditioner can be connected with the following optional kits.

Wired remote controller

• 

External input/output kit

• 

BEFORE INSTALL WIRED REMOTE CONTROLLER 

When you use wired remote controller, some functions may not be used.

• 

Please use the recommended wired remote controller.

• 

CAUTION

(1)  Before installing, be sure to disconnect all power supply.

(2)  Don’t touch the heat exchanger.

(3)  During installing or removing operation, be sure not to have wire caught by parts or draw it hard. Or it may result troubles 

to the air-conditioner.

(4)  Avoid place in direct sunlight.

(5)  Select place that will not be affected by the heat from a stove, etc.

(6)  Before setting up the optional kit, please confi rm whether air-conditioner can receive the signal.

(7)  Do not connect the wired remote control to the terminal for power supply.

(8)  When connecting the wired remote controller with the indoor unit, please use the connecting cord packaged up with the 

wired remote controller.

(9)  Recommended cord length of wired remote controller is 10m. Make sure to do insulate of connecting part when extended 

the cord.

1. REMOTE CONTROLLER CORD MODIFICATION 

(1)  Use a tool to cut off the terminal on the end of the remote 

controller cord,and then remove the insulation from 

the cut end of the cord.

(2)  Connect the remote controller cord and connecting cord.

      (supplied with wired remote controller)

Important:

 Be sure to insulate the connection between the cords.

2. FRONT PANEL, CONTROL BOX COVER AND DISPLAY CASE REMOVEL

(1) Refer to “FRONT PANEL REMOVAL AND INSTALLATION“to remove the front panel.
(2) Remove the screw then remove the control box cover.
(3) Remove the display case and connector.

Connecting cord

White

Red

White

Red

Black

Black

Insulated
connection

Remote
controller cord

Remote
controller cord

20 mm

1

3/1

6”

screw

control box

cover

connector

display case

3. CONNECTING CORD TO CONTROL BOARD CONNECTOR

(1) Pass the cord from the hole in the back of indoor unit.
(2) Connect the cord to the control board connector.
(3) Hook the cord to the rib.

                                                                                                          

Option type

Connector No

Wired remote controller

CN6

External input

CN14

External output

CN16

(4) Use cord clamper and screw to fasten the cord of wired remote controller.

(5) Fix the binder clamp with the screw and bind the wire of external kit with the binder.

4. FRONT PANEL, CONTROL BOX COVER AND DISPLAY CASE INSTALLATION

Install front panel, control box cover and display case by the reverse procedures as stated in “2.FRONT PANEL,
CONTROL BOX COVER AND DISPLAY CASE REMOVAL”.

cord clamper

screw

conduit holder

cord clamper

cord of 

wired 

remote 

controller

original wire of 

control unit

screw

INDOOR UNIT

PCB

TERMINAL

connect the

cord

rib

hole

conduit holder

screw

binder clamp

original wire of 

control box

binder clamp

screw

binder

external connect wire

Direction of the service 
panel removal

Service cover

Power supply 
cord or connec-
tion cord

 Earth wire

40 mm (1

-9/1

6") 

or more

Overlap the insulation

Bind the pipes together so 
that there is no gap.

Connection pipe 
(heat insulation)

Vinyl tape

Indoor unit pipe
(heat insulation)

Tightening torque

Charging port cap

Blank cap

20 to 25 N•m (200 to 250 kgf•cm)
30 to 35 N•m (300 to 350 kgf•cm)

10 to 12 N•m (100 to 120 kgf•cm)

9.52 mm (3/8 in.)

15.88 mm (5/8 in.)

OPTIONAL KIT INSTALLATION(OPTION)

Drain pipe mounting hole

Drain pipe

Power supply line

G

1

2

3

4

1

2

3

L1 L2

G

G

Earth screw

Earth screw

Earth screw

Disconnect switch

Indoor unit
terminal block

Outdoor unit
terminal block

Base

 WARNING

If refrigerant leaks while work is being carried out, ven-
tilate the area. If the refrigerant comes in contact with a 
fl ame, it produces a toxic gas.

Bottom side

Drain cap mount-
ing place

Drain pipe 
mounting place

650 mm

(25-19/32")

4-ø 12 hole

370 mm 

(1

4-9/1

6")

Top hooks
(two sides)

NOTE:

Factory installed protective inline fuses for indoor units’ conductors 
are installed on the Power Supply PCB.

9315342720-02_IM_EN.indd   2

9315342720-02_IM_EN.indd   2

3/25/2010   11:42:52 AM

3/25/2010   11:42:52 AM

Отзывы: