![FRIEDHELM LOH Rittal 3273 Series Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/friedhelm-loh/rittal-3273-series/rittal-3273-series_assembly-and-operating-instructions-manual_2332655019.webp)
Rittal enclosure cooling unit
19
6 Operation
EN
A06
PSA
H
pressure switch
Ambient temperature too high
Lower the ambient temperature;
reset the e-Comfort controller
Condenser soiled
Clean the condenser;
reset the e-Comfort controller
Filter mat soiled
Clean or replace;
reset the e-Comfort controller
Condenser fan defective
Replace;
reset the e-Comfort controller
E-valve defective
Repair by refrigeration engineer;
reset the e-Comfort controller
PSA
H
pressure switch defective
Refrigeration engineer to exchange
reset the e-Comfort controller
A07
Evaporator coil
Lack of refrigerant;
Sensor in front of or behind condenser
defective
Repair by refrigeration engineer;
reset the e-Comfort controller
A08
Condensate warning
Condensate discharge kinked or
blocked
Check condensate drainage; correct any
kinks or blockages in the hose
Only for units with optional conden-
sate evaporation
Check the evaporation unit, replace if neces-
sary
A09
Condenser fan
Blocked or defective
Clear the blockage; replace if necessary
A10
Evaporator fan
Blocked or defective
Clear the blockage; replace if necessary
A11
Compressor
Compressor overloaded
(internal winding protection)
No action required;
Unit switches on again independently
Defective
(check by measuring the winding re-
sistance)
Replace by a refrigeration engineer
A12
Condenser tempera-
ture sensor
Open or short-circuit
Replace
A13
Ambient temperature
sensor
Open or short-circuit
Replace
A14
Icing temperature sen-
sor
Open or short-circuit
Replace
A15
Condensate warning
temperature sensor
Open or short-circuit
Replace
A16
Internal temperature
sensor
Open or short-circuit
Replace
A17
Phase monitoring
For three-phase devices only: Incor-
rect rotary field/phase absent
Swap two phases
A18
EPROM error
New board installed incorrectly
Software update needed (only following
board installation with more recent software):
Enter the programming level with Code 22;
press button 1 and confirm with "Set" until
"Acc" appears. Next, disconnect the unit
from the mains and reconnect.
A19
LAN/Master-Slave
Master and slave not connected
Check setting and/or cable
Display
screen
System message
Possible cause
Measures to rectify the fault
Tab. 5:
Troubleshooting with the e-Comfort controller