Rittal roof-mounted fan
9
5 Performing the electrical installation
EN
Fig. 2:
Connection diagrams
Select the conductor cross-section according to the
pre-fuse (0.5–4 mm² single-wire, 0.5–2.5 mm² fine-
wire).
A smaller pilot wire may be selected (min. 0.34 mm²).
Fig. 3:
Connector and strain relief
Key
1
Strain relief
Connect the connector to the roof-mounted fan from
below.
5.2
Installing the pilot wire
To control the EC roof-mounted fans via an external
control unit (e.g. 3235.440), types 3140.5xx have addi-
tional connections for the pilot wire.
Release and remove the jumper between the "+10 V"
and "0 – 10 V/PWM" (terminals 1 and 2) connections.
Use a screwdriver with a 3.5 x 0.5 mm blade.
Open the terminal with the screwdriver and insert the
connection cable as shown in the connection dia-
gram.
Remove the screwdriver.
Connection
Pin
Function/assignment
L
Power supply
N
Neutral conductor
PE PE
conductor
+10 V
1
Voltage output 10 V max. 1.1 A,
galvanically isolated, not short
circuit-protected
0…10 V/PWM
2
Control input 0…10 V or PWM,
galvanically isolated, impedance
100 kΩ
GND
3
GND connection of the control
interface
Speed
4
Speed output Open Collector, 1
pulse per revolution, galvanically
isolated
Tab. 3:
Connection designations
Note:
In accordance with NFPA 70 (NEC), only
copper conductors must be used to connect
the supply cable to the mains connector.
Note:
To operate without a pilot wire, the jumper
should be left in the connection terminal. The
unit will then be operated at maximum
speed.