5 Performing the electrical installation

EN

Fig. 2:

Connection diagrams

Select the conductor cross-section according to the 
pre-fuse (0.5–4 mm² single-wire, 0.5–2.5 mm² fine-
wire).
A smaller pilot wire may be selected (min. 0.34 mm²).

Fig. 3:

Connector and strain relief

Key

1

Strain relief

Connect the connector to the roof-mounted fan from 
below.

5.2

Installing the pilot wire

To control the EC roof-mounted fans via an external 
control unit (e.g. 3235.440), types 3140.5xx have addi-
tional connections for the pilot wire.

Release and remove the jumper between the "+10 V" 
and "0 – 10 V/PWM" (terminals 1 and 2) connections.

Use a screwdriver with a 3.5 x 0.5 mm blade.

Open the terminal with the screwdriver and insert the 
connection cable as shown in the connection dia-
gram.

Remove the screwdriver.

Connection

Pin

Function/assignment

L

Power supply

N

Neutral conductor

PE PE 

conductor

+10 V

1

Voltage output 10 V max. 1.1 A, 
galvanically isolated, not short 
circuit-protected

0…10 V/PWM

2

Control input 0…10 V or PWM, 
galvanically isolated, impedance 
100 kΩ

GND

3

GND connection of the control 
interface

Speed

4

Speed output Open Collector, 1 
pulse per revolution, galvanically 
isolated

Tab. 3:

Connection designations

Note:
In accordance with NFPA 70 (NEC), only 
copper conductors must be used to connect 
the supply cable to the mains connector.

Note:
To operate without a pilot wire, the jumper 
should be left in the connection terminal. The 
unit will then be operated at maximum 
speed.

Содержание Rittal 3138.000

Страница 1: ...nungsanleitung Assembly and operating instructions Notice d emploi d installation et de montage Montage installatie en bedieningshandleiding Montage installations och bruksanvisning Instrucciones de m...

Страница 2: ...d installation et de mon tage peut tre t l charg e depuis le site www rittal fr Opmerking De montage installatie en gebruikshandlei ding is ook te downloaden via www rittal nl Obs Montage installatio...

Страница 3: ...cope of supply 6 4 Installation 6 4 1 Choosing the installation site 6 4 2 Notes on installation 6 4 2 1 General 6 4 2 2 Layout of the electronic components in the enclosure 6 4 3 Installing the roof...

Страница 4: ...and servicing may only be per formed by properly trained specialists Do not obstruct the air inlet and air outlet of the roof mounted fan inside and outside the enclosure see also section 4 2 2 Layout...

Страница 5: ...our class G3 filter mats installed The filter must be checked regularly de pending on the level of dust exposure and replaced as necessary 3 3 Proper use Rittal roof mounted fans were developed and de...

Страница 6: ...all sides IP 54 If the enclosure has a leak unfiltered contaminated air may enter the enclosure The fan motor is a rotating component that may trans fer vibrations and oscillations Appropriate measure...

Страница 7: ...Rittal roof mounted fan 7 4 Installation EN 4 3 Installing the roof mounted fan...

Страница 8: ...r manufacturer or operator to ensure effec tive protection against lightning and overvoltage The limits specified in standard UL IEC EN 60335 2 40 must be observed The units are classified as overvolt...

Страница 9: ...driver with a 3 5 x 0 5 mm blade Open the terminal with the screwdriver and insert the connection cable as shown in the connection dia gram Remove the screwdriver Connection Pin Function assignment L...

Страница 10: ...perature monitor The life expectancy is at least 50 000 operating hours L10 40 C The roof mounted fan is therefore largely maintenance free From time to time the components may need to be cleaned usin...

Страница 11: ...eded air flow with filter mats m h 417 446 446 725 759 759 700 749 841 841 Air throughput with fil ter mats and inlet filter 1 x 3243 200 m h 370 391 391 590 610 610 580 610 690 690 Fan Radial capacit...

Страница 12: ...egory IP 55 IP 55 without filter mat and installation in accordance with section 4 3 Installing the roof mounted fan Installation for protection category IP 55 Accessories Packs of Spare filter mats f...

Страница 13: ......

Страница 14: ...ution Climate Control IT Infrastructure Software Services You can find the contact details of all Rittal companies throughout the world here www rittal com contact 3nd edition 05 2019 ID no 335 522 Dr...

Отзывы: