Thermozone AC 400
Type
AC401
AC402
AC412
AC418
Power
[kW]
0,6
1,0
12
18
Voltage, motor / manouvre
[V]
230~
230~
230~
230~
Voltage, heat output
[V]
-
-
400V3~
400V3~
Voltage, motor / manouvre
[A]
2,6
4,3
2,5
4,3
Amperage heat output
[A]
-
-
17,3
26,0
Air flow
[m
3
/h]
1350 / 2700 2250 / 4500
1350 / 2700 2250 / 4500
Temperature rise of passing
air at full output
[°C]
-
-
27 / 13
27 / 13
Sound level
[dB(A)]
44 / 62
45 / 63
44 / 62
45 / 63
Weight
[kg]
44
71
54
86
Length
[mm]
1000
1670
1000
1670
Protection class
IP 24
IP 24
IP 24
IP 24
Accessories
Type
Measures (BxLxD)
Air flow selector (4-step)*
1
ACR 304
80x100x90 mm
Air flow selector high/low *
1
ACR 3042
150x200x105 mm
Air flow regulator (stepless), AC 401-402 *
2
2221AG
85x170x63 mm
Output selector (0 –
1
/
2
–
1
/
1)
EV 300
80x100x90 mm
Position limit switch
AGB 304
2-step thermostat
KRT 2800
60x165x60 mm
Mounting plate for vertical mounting
AVMP 300
Adaption set for ceiling mounted sliding doors
AXT401
Adaption set for ceiling mounted sliding doors
AXT402
False ceiling grille (1192 x 192)
22003
False ceiling grille (1515 x 192)
22004
*
1
Regulation for a max of 3 units
*
2
Regulation for a max of 1 units (2xAC401)
23
GB
Complete technical documentation is
available.
EC Declaration of Conformity
Defined by the EC Electromagnetic
Compatibility Directive 89/336/EC och
92/31/EC.
The following harmonised standards are in
use:
SS-EN 50 082-1: 1992
SS-EN 60 555-2/3: 1991
Complete technical documentation is
available.
Partille, 19 januari 1998