temperatures below zero should be equipped 
with external frost protection to ensure that 
the heating coil is not damaged by frost.

Electrical installation

The electrical installation should be carried 
out by a qualified electrician in conformity 
with prevailing regulations. The appliance 
should be preceded by an triple-pole switch 
with at least 3 mm breaking gap.
Fan heater SWT is intended for fixed 
installation and is connected by knock-outs 
on the heaters back side.

The motor has a built-in thermal safety 

cut-out to protect against overheating. This 
will reset automatically once the motor has 
cooled.

Cable glands used must guarantee the 

protection class requirements.

After the electrical installation of the motor, 

check the rotation of the fan. Seen from the 
inlet side, the impellers should be rotating 
anti-clockwise.

See wiring diagrams.

Uppstart

OBS! Vid första användningstillfället eller 
vid uppstart efter ett längre uppehåll, kan 
en mindre rök- och luktutveckling tillfälligt 
förekomma, vilket är helt normalt.

Maintenance 

To ensure performance and reliabilty of 
the unit, inspection and cleaning should be 
carried out reguarly. Inspection should be 
carried out at least twice a year. Clean the 
unit when needed. During inspection the 
power supply must always be disconnected.

Cleaning the fan 

Cleaning intervals of the fan is due to filter 

(if any) and air quality.

To ensure performance and reliabilty of 

the unit, inspection and cleaning should be 
carried out reguarly. Inspection should be 
carried out at least twice a year. Clean the 
unit when needed. During inspection the 
power supply must always be disconnected.

If the impellers are not cleanded properly, 

vibrations/noise can occur and severly 

damage the bearings. If the vibrations/noise 
remain after cleaning, please contact a 
certified technician.

Lossen the clamps on the fan plate and let 

it hang down. Use compressed air from the 
inside out to clean the watercoil. Use a soft 
brush tp clean the impellers. If water or steam 
is used for cleaning, ensure that the motor is 
protected from water.

Residual current circuit breaker 
(applies to units with electric heater) 

When the installation is protected by means 
of a residual current circuit breaker, which 
trips when the appliance is connected, 
this may be due to moisture in the heating 
element. When an appliance containing a 
heater element has not been used for a long 
period or stored in a damp environment, 
moisture can enter the element. 
This should not be seen as a fault, but is 
simply rectified by connecting the appliance 
to the mains supply via a socket without a 
safety cut-out, so that the moisture can be 
eliminated from the element. The drying 
time can vary from a few hours to a few days. 
As a preventive measure, the unit should 
occasionally be run for a short time when it is 
not being used for extended periods of time.

Safety

•  For all installations of electrically heated 

products should a residual current circuit 
breaker 300 mA for fire protection be used.

• 

Ensure that the area around the intake is  
kept free from material which could   
prevent the air flow through the  

 

appliance! 

•  The appliances have hot surfaces during  

operation!

•  This product is not designed to be used by 

children or persons with reduced physical 
or mental ability or a lack of experience 
and knowledge, unless instruction 
regarding the product's use has been 
given by a person with responsibility for 
their safety or that this person supervises 
operation. Children must be kept under 
supervision to ensure they do not play with 
the product.

• Lifting aids should be used to lift the 

appliance.

www.frico-ltd.ru  [email protected]  +7 (495) 215-02-37
Москва. Каширский проезд д. 17 стр. 5

Содержание SWT Series

Страница 1: ...SWT 11 SE 13 GB Art no 172553 02 www frico ltd ru info frico ltd ru 7 495 215 02 37 17 5...

Страница 2: ...12 675 760 420 790 825 115 195 355 160 355 22 SWT22 710 1070 480 1100 1135 110 300 415 115 430 28 1 Fan heater SWT 2 Filter SWTCF 3 Air director SWTCL 4 Extension sleeve SWTCE 1 2 3 4 30 L C F B D E A...

Страница 3: ...8 0 low 5 0 SWT22 high 12 0 low 7 0 Type A mm B mm SWT02 280 640 SWT12 420 760 SWT22 480 1070 To open K The air throw is defined as the distance in a straight angle from the fan heater to the point w...

Страница 4: ...ch for air flow max 3A 200x105x105 RE7 5 step change over switch for air flow max 7A 247x147x145 SD20 Type RSK SD20 672 70 37 TVV20 672 70 35 TVV25 672 70 36 Water regulation Type Description SWTCE02...

Страница 5: ...hermostat only 1 2 M 3 4 5 6 7 8 SWT N Blue Black Brown 1 2 3 L N 230 V SD20 TVV20 25 KRT 1 2 M 3 4 5 6 7 8 SWT N Blue Black Brown L N 230 V SD20 TVV20 25 A B 2 4 4 t C 6 2 7 T10 TK10 Wiring diagrams...

Страница 6: ...flow only 1 2 M 3 4 5 6 7 8 SWT N Blue Black Brown L N 230 V 2 4 5 1 3 CB20 7 5 step control of airflow only 1 2 M 3 4 5 6 7 8 SWT N Blue Black Brown N RE1 5 7 N L N 230 V www frico ltd ru info frico...

Страница 7: ...ack Brown L N 230 V SD20 TVV20 25 2 4 5 1 3 CB20 7 A B 2 4 4 t C 6 2 7 T10 TK10 Thermostat and 5 step control 1 2 M 3 4 5 6 7 8 SWT N Blue Black Brown L N 230 V 1 2 3 SD20 TVV20 25 KRT N RE1 5 7 N 1 2...

Страница 8: ...A Sound 3 level 4 dB A LxWxH 8 mm Weight 9 kg RSK SE NRF NO SWT02 230V 0 4 37 53 705x535x330 19 672 67 03 850 23 11 SWT12 230V 0 6 44 57 825x625x355 26 672 67 04 850 23 12 SWT22 230V 1 0 48 60 1135x71...

Страница 9: ...Air temp out C Water flow l s Pres sure drop kPa SWT02 max 0 31 7 5 30 0 09 4 9 6 4 40 0 08 3 8 5 3 34 0 06 2 7 min 0 19 5 4 33 0 06 2 8 4 6 34 0 06 2 1 3 8 36 0 05 1 5 SWT12 max 0 56 13 0 29 0 16 8...

Страница 10: ...e pressure drop is calculated for an average temperature of 70 C PVV 80 60 For other water temperatures the pressure drop is multiplied with the factor K Pressure drop kPa Tryckfall bar Pressure drop...

Страница 11: ...ill l mplig niv Borrmall och minavst nd till v gg se fig 2 och fig 3 Om takkonstruktionen r svag m ste den f rst rkas s att en s ker installation uppn s F r vikter p varje storlek se tabell sid 8 Mont...

Страница 12: ...vilken milj som fl kten arbetar i och om filter varit monterat eller inte Residual current circuit breaker applies to units with electric heater When the installation is protected by means of a residu...

Страница 13: ...ceiling with four screws thruogh the brackets Drop rods are used when mounting at a distance from ceiling For drilling template see fig 2 and fig 3 If the ceiling structure is weak it must be reinfor...

Страница 14: ...bearings If the vibrations noise remain after cleaning please contact a certified technician Lossen the clamps on the fan plate and let it hang down Use compressed air from the inside out to clean th...

Страница 15: ...www frico ltd ru info frico ltd ru 7 495 215 02 37 17 5...

Страница 16: ...l 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se www frico ltd...

Отзывы: