SWT
5
GB
temperatures below zero should be equipped
with external frost protection to ensure that
the heating coil is not damaged by frost.
Electrical installation
The electrical installation should be carried
out by a qualified electrician in conformity
with prevailing regulations. The appliance
should be preceded by an triple-pole switch
with at least 3 mm breaking gap.
Fan heater SWT is intended for fixed
installation and is connected by knock-outs
on the heaters back side.
The motor has a built-in thermal safety
cut-out to protect against overheating. This
will reset automatically once the motor has
cooled.
Cable glands used must guarantee the
protection class requirements.
After the electrical installation of the motor,
check the rotation of the fan. Seen from the
inlet side, the impellers should be rotating
anti-clockwise.
See wiring diagrams.
Uppstart
OBS! Vid första användningstillfället eller
vid uppstart efter ett längre uppehåll, kan
en mindre rök- och luktutveckling tillfälligt
förekomma, vilket är helt normalt.
Maintenance
To ensure performance and reliabilty of
the unit, inspection and cleaning should be
carried out reguarly. Inspection should be
carried out at least twice a year. Clean the
unit when needed. During inspection the
power supply must always be disconnected.
Cleaning the fan
Cleaning intervals of the fan is due to filter
(if any) and air quality.
To ensure performance and reliabilty of
the unit, inspection and cleaning should be
carried out reguarly. Inspection should be
carried out at least twice a year. Clean the
unit when needed. During inspection the
power supply must always be disconnected.
If the impellers are not cleanded properly,
vibrations/noise can occur and severly
damage the bearings. If the vibrations/noise
remain after cleaning, please contact a
certified technician.
Lossen the clamps on the fan plate and let
it hang down. Use compressed air from the
inside out to clean the watercoil. Use a soft
brush tp clean the impellers. If water or steam
is used for cleaning, ensure that the motor is
protected from water.
Residual current circuit breaker
(applies to units with electric heater)
When the installation is protected by means
of a residual current circuit breaker, which
trips when the appliance is connected,
this may be due to moisture in the heating
element. When an appliance containing a
heater element has not been used for a long
period or stored in a damp environment,
moisture can enter the element.
This should not be seen as a fault, but is
simply rectified by connecting the appliance
to the mains supply via a socket without a
safety cut-out, so that the moisture can be
eliminated from the element. The drying
time can vary from a few hours to a few days.
As a preventive measure, the unit should
occasionally be run for a short time when it is
not being used for extended periods of time.
Safety
• For all installations of electrically heated
products should a residual current circuit
breaker 300 mA for fire protection be used.
•
Ensure that the area around the intake is
kept free from material which could
prevent the air flow through the
appliance!
• The appliances have hot surfaces during
operation!
• This product is not designed to be used by
children or persons with reduced physical
or mental ability or a lack of experience
and knowledge, unless instruction
regarding the product's use has been
given by a person with responsibility for
their safety or that this person supervises
operation. Children must be kept under
supervision to ensure they do not play with
the product.
• Lifting aids should be used to lift the
appliance.