SIRe Advanced Fan Heater Water
34
GB
>Installer menu>Heating
settings
Control range limit
Heating step diff.
Sensor calibration
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
Outdoor temp. sensor
•
0.0 K
>Installer menu>Heating
settings
Stepless heat control
•
ON
>Installer menu>Heating
settings
Control range limit
Return water temp.
Stepless heat control
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Not connected
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
•
Stepless heat control
Sensor calibration
Return water temp.
>Installer menu>Heating
settings
Connected
Installer menu>Heating
settings>Return water temp.
Return temp. limit
•
OFF
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
>Installer menu>Heating
settings
Heating step limit
•
>Installer menu>Heating
settings
Sensor calibration
Eco / Comfort
Heating step limit
1.0 K
Control with mixing cabinet, with falling outlet
temp
Comfort:
1. Opens the valve gradually to fully open
valve.
2. Gradually closes damper to night mode
3. Slows down the fan.
Eco:
1. Gradually closes damper to night mode
2. Opens the valve gradually to full heating.
3. Slows down the fan.
Max. outlet temp. limit +32°C.
Heating step diff.
When the temperature falls below the set
point value the fan speed increases (the high
speed limit is position 4). Which temperature
difference the speed is to be increased by a
step for is selected in Heating step diff.
Factory setting
Heating step diff.: 1.0 K (-10 K – 10 K)
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for e2K gives an increase of the
displayed value of 2 degrees).
Return water temp.
If there is a demand for the temperature
of the return water not to exceed a certain
value, this function is activated under Return
water temp. A return water temperature
sensor (proximity sensor SIReWTA, option)
must then be installed on the return water
pipe.
Install Return temp. Sensor to Connected
and select max return temperature (15-90 °C)
using the turn wheel. During operation, this
function limits the valve’s degree of opening,
which reduces the flow and the return
temperature.
Factory setting
Return temp. sensor: Not connected
(Connected)
Return temp. limit: Off (15 – 90°C)
Stepless heat control
To use Advanced fully, stepless heat control
must be used.
Factory setting
Stepless heat control: ON (Off - not
selectable)
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10
K)