GB  

17

General Instructions 

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid if the product is used 
in the manner intended and in accordance 
with the instructions. 

Application area 

The SFS air curtain unit is supplied with 
electrical heating or hot water heating.
SFS is intended for revolving doors.

SFS is mounted vertically next to the door.  

Protection class: IP20. 

Operation 

Air is drawn in at the side of the unit and 
blown out against the entrance, so that it 
shields the door opening and minimizes heat 
loss. To achieve the optimum curtain effect 
the unit must extend the full height of the 
door opening.

 The grille for directing exhaust air is 

adjustable and is normally angled towards the 
revolving door to achieve the best protection 
against incoming cold air.

 The efficiency of the air curtain depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure.

 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced. 

Mounting

The air curtain is mounted to the left of the 
door seen from inside. The unit has a curved 
design which makes it an integrated part of 
the door.  The unit can be extended to max 
3000 mm (extension without fans). Extension 
hood, for heights up to 4 m, is available.

 The air curtain is installed on adjustable 

feet which makes it possible to compensate 
for any surface undulations. The feet 
are attached to the floor with fasteners 
appropriate to the surface and covered by a 
frame. The air curtain must always be secured 
at the top.

Electrical installation  

The installation, which should be preceded by 
an omnipolar switch with a contact separation 
of at least 3 mm, should only be wired by a 
competent electrician and in accordance with 
the latest edition of IEE wiring regulations. 
The control system is pre-installed in the air 
curtain with an integrated control card. SIRe 
is supplied pre-programmed with quick-fit 
connections. Modular cables are connected to 
the control board. The control card is always 
placed at the top of vertical units.
 See manual for SIRe.
 

Unit with water heating

The electrical connection may be done from 
above or below, according to ordering key. 
Control (230V~) should be connected to a 
terminal block. 
  

Unit with electrical heating 

The electrical connection may be done from 
above or below, according to ordering key.  
Control (230V~) and power supply for heat 
(400V3~) should be connected to a terminal 
block. Modular cables for SIRe control board 
should be drawn inside the unit when the 
connection is made from the bottom. Bundle 
the cables inside the unit to prevent that they 
will be drawn into the fans or get in contact 
with the heating elements.

 The largest cable diameter for the terminal 

block is 16 mm². The cable glands used must 
meet the protection class requirements. In 
the distribution board it is to be indicated 
that ”the air curtains can be supplied from 
more than one connection”. 
See wiring diagrams. 
 

Ensure that the service hatch is accessible 
and can be fully opened.

 See Fig. 4.

Assembly and operating instructions

Type

Output

[kW]

Voltage 
motor 
[V]

Minimum
area

 

[mm

2

]

All Control

-

230V~

1,5

SFS23E08

8,1

400V3~ 

2,5

SFS30E12

11,7

400V3~ 

4

SFS38E16

16,2

400V3~ 

6

SFS56E23

23,4

400V3~ 

10

Содержание SFS E Series

Страница 1: ...SFS Original instructions 12 SE 17 GB 21 DE 26 ES 31 FR 36 IT 41 NL 46 NO 51 RU 56 PL ...

Страница 2: ...nglischer Sprache siehe die entsprechenden Sprachseiten DE Las páginas introductorias contienen básicamente imágenes Consulte la traducción de los textos en inglés que las acompañan en las páginas del idioma correspondiente ES De inleidende pagina s bevatten hoofdzakelijk afbeeldingen Voor een vertaling van de gebruikte Engelse teksten zie de pagina s van de resp taal NL Le pagine introduttive con...

Страница 3: ...SFS 3 Fig 1 Dimensions 2 4 7 2200 50 296 581 M8 1 1 6 ...

Страница 4: ...ig 4 Minimum mounting distance Seen from above Connection above Seen from above Connection below Fig 3 Connections E Seen from above Connection above Seen from above Connection below min 120 377 339 118 168 Ø48 2x 380 339 118 168 ...

Страница 5: ... SIReCC415 15 m Accessories SIRe C SIReB SIReAC SIReAA SIReRTX SIReUR SIReWTA SIReCC SIReCJ4 SIReCJ6 FH1025 Flexible hose DN25 1 inside thread for easy connection to the pipe system SFSEH Extension hood 100 1000 mm SFSEH FH1025 VKF15LF DN15 VKF15NF DN15 VKF20 DN20 VKF25 DN25 VKF32 DN32 SD230 BPV10 SDM24 ST23024 VOT15 DN15 VOT20 DN20 VOT25 DN25 VKF SDM24 ST23024 SD230 BPV10 VKF VLSP VLP VOT ...

Страница 6: ... Transformer 230V 200V 170V 145V 120V 100V N Black Black Grey Blue Blue White White Supply 230V C2 C1 ROOM Internal sensor Motor protection C C C Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue N SFS30 38E C C C SFS56E N L SFS E ...

Страница 7: ...ormer 230V 200V 170V 145V 120V 100V N Black Blue White White Supply 230V C2 C1 ROOM Internal sensor Motor protection C C C Transformer 230V 200V 170V 145V 120V 100V N Yellow Orange Red Brown Black Green Blue SFS30 38W C C C SFS56W 230V SFS W ...

Страница 8: ...OOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1 SIReRTX optional L 2m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC ...

Страница 9: ...nit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC SIReCC6XX max 50 m SIReCC6XX max 50 m SIReUB1 SIReRTX optional SD230 SD230 SD230 L 1 5m L 2m ...

Страница 10: ...2 5 Output charts water SFS Supply water temperature 60 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 60 40 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C Water flow l s Pressure drop kPA Output 2 kW Outlet air temp C Water flow l s Pressure drop kPA SFS23WL max 2400 14 1 40 0 17 10 0 14 1 35 2 0 17 10 min 1150 6 6 32 0 06 1 4 8 3 39 ...

Страница 11: ...odels that have a smaller number of motors Type Output 5 kW Output 6 kW Airflow 1 m3 h t 4 5 C t 4 6 C Water volume l Sound power 2 dB A Sound pressure 3 dB A Voltage V Amp A Height 7 mm Weight kg SFS23WL 8 14 24 1150 2400 21 17 36 29 3 0 79 44 63 230V 2 6 2200 75 SFS30WL 8 21 35 1550 3250 24 18 40 32 4 4 80 46 64 230V 3 6 2200 80 SFS38WL 8 23 38 1700 3700 23 18 39 30 4 4 83 48 67 230V 4 9 2200 80...

Страница 12: ... to the floor with fasteners appropriate to the surface and covered by a frame The air curtain must always be secured at the top Electrical installation The installation which should be preceded by an omnipolar switch with a contact separation of at least 3 mm should only be wired by a competent electrician and in accordance with the latest edition of IEE wiring regulations The control system is p...

Страница 13: ...e water system or an open water system Note that the unit shall be preceded by a regulating valve see Frico valve kit Water connection can be made from above and below according to the order key via DN25 1 internal thread connections When connection is made from below the connection is placed in altitude between the first and second motor Flexible hoses are available as an accessory see accessorie...

Страница 14: ...grille filter is not dirty Functions and settings of the SIRe control system see manual for SIRe If there is no heat check the following Functions and settings of the SIRe control system see manual for SIRe For units with electrical heating also check the fol lowing Power supply to electric heater coil check fuses and circuit breaker if any That the overheat protection for the motors has not been ...

Страница 15: ...d with clothing or similar materials as overheating can result in a fire risk E Lifting equipment must be used to lift the unit This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and und...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ... Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no 208030 2017 01 03 HH SÄ SÅ ...

Отзывы: