Frico Pamir 3200 Скачать руководство пользователя страница 9

Pamir 3200

9

EN

Electrical installation  

The installation, which should be preceded by 

an isolator switch with a contact separation 

of at least 3 mm, should only be wired by a 

competent electrician and in accordance with 

the latest edition of IEE wiring regulations.  

The air curtain has an integrated PC board 

which is connected to the selected external 

control system FC. FC must be ordered 

separately. The PC board is accessed via cable 

glands on the top of the unit. See Fig. 2. FC is 

supplied pre-programmed. Communication- 

and sensor cables are connected to the PC 

board. 

Should more than one air curtain be 

controlled by a single FC, an additional 

communication cable FCBC per unit will be 

required. See manual for FC.  

    The electrical connection is made on the top 

of the unit. Pierce the gland with a screwdriver 

before entering the cable. See Fig. 2. Control 

(230V~) and power supply for heat (400V3~) 

should be connected to a terminal block in the 

terminal box. 2-metre and longer units require 

dual power supplies. See dimension drawing 

and wiring diagram. 

The largest cable diameter for the terminal 

block is 16 mm². The cable glands used must 

meet the protection class requirements. In the 

distribution board, it is to be indicated that ”the 

air curtains can be supplied from more than 

one connection”. 

General Instructions 

Read these instructions carefully prior to 

installation and use. Keep this manual for 

future reference.

The product may only be used as set out in 

the assembly and operating instructions. The 

guarantee is only valid should the product be used 

in the manner intended and in accordance with 

the instructions. 

 

Application 

Pamir 3200 is an air curtain with electrical 

heating and a recommended installation height 

of 3,2 m. Protection class: IP20.  

Operation 

Air is drawn in at the top of the unit and blown 

downwards shielding the door opening and 

minimizing heat loss. To achieve the optimum 

curtain effect the unit must extend the full 

width of the door opening. 

The grille for directing the outlet air is 

adjustable and is normally angled outwards to 

achieve the best protection against incoming 

air. 

The efficiency of the air curtain depends on 

the air temperature, the pressure differencial 

across the doorway and any wind load. 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 

curtain. The ventilation should therefore be 

balanced. 

Mounting

The air curtain is installed horizontally with 

the outlet air grille facing downwards as close 

to the door as possible. The product must be 

mounted in such a way to allow future service 

and maintenance. Minimum distance from 

outlet to floor for electrically heated units is 

1800 mm. For other minimum distances, see 

fig. 1

Mounting with wall brackets (fig. 4) 

1. 

Mount the brackets on the wall, see fig.4A 

and dimension drawing. If the wall is uneven 

the brackets must be compensated for this. 

2. Hook on the unit at the lower edge of the 

brackets. (Fig.4B)

3. Bend the top of the console over the the unit 

and slide the units screws along the rail into 

the slots on the consoles. (Fig.4C) When the 

bracket is bent once, it must be replaced if 

bent back more than 45 °. 

4. Lock the nuts against the brackets. (Fig.4D)

   

Horizontal mounting on the ceiling  

Threaded rods, hanging brackets and ceiling 

mounting brackets for ceiling mounting are 

available as accessories, see accessories pages 

and separate manuals.

 

 

 

[kW]

 

 

[V]

 

 

[mm

2

]

0

230V~

1,5

PAF3210E08

8

400V3~ 

2,5

PAF3215E12

12

400V3~ 

4

PAF3220E16*

1

8

400V3~

2,5

8

400V3~ 

2,5

Type 

Output  Voltage 

Minimum 

area*

Control 

*

1

) 2 m units are connected with two power supplies.  

*

2

) Dimensioning of external wiring shall comply with 

applicable regulations and local deviations may occur. 

Installation and operating instructions

Содержание Pamir 3200

Страница 1: ...Pamir 3200 9 EN 12 FR Original instructions...

Страница 2: ...55 2045 1068 1578 2068 256 10 458 167 min 500 99 min 500 min 500 167 165 1045 1555 2045 1068 1578 2068 256 10 458 167 min 500 99 min 500 min 500 167 165 2 m PAF3220 1045 1555 2045 1068 1578 2068 256 1...

Страница 3: ...2 5 25 5 20 5 17 5 Gland Gland FC Frico Control Gland press toupe Knock out opercule PC board FC is integrated within the air curtain at delivery La carte lectronique de la r gulation FC est int gr e...

Страница 4: ...Pamir 3200 4 min 500 mm Fig 4 Mounting with wall brackets Installation avec des consoles pour montage mural PAF3210 2 pcs PAF3215 2 pcs PAF3220 3 pcs A B C D 8 3x 7 16 213 37 260 75 35 20...

Страница 5: ...sions 25256 PA3PF15 PAF3210 3215 4 pcs 25257 PA3PF20 PAF3220 6 pcs 18056 PA34TR15 PAF3210 3215 4 pcs L 1 m 18057 PA34TR20 PAF3220 6 pcs L 1 m 19568 PA2P15 PAF3210 3215 2 pcs L 1 m 19569 PA2P20 PAF3220...

Страница 6: ...X 39x39x23 mm 74699 FCLAP 89x89x26 mm 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703 FCTXRF for FC Smart FC Pro 89x89x26 mm Accessories Acces...

Страница 7: ...00V3N 17 3 42 251419 PAF3220E16 6 10 16 2300 3500 22 13 76 50 60 366 1 3 400V3N 23 1 59 3 Electrical heat Chauffage lectrique Pamir 3200 E IP20 Technical specifications Voltage motor 230V 1 D bit d ai...

Страница 8: ...F2 F3 F1 H1 H2 N Heating Trafo Motor Brown M Left motor C Blue Run Black Run Ri ght m otor M Brown C Blue Black White Blue N Mid c1 Low b1 L Black Red Orange Yeloow Yellow Low N L Mid Blue Black Red...

Страница 9: ...tion Air is drawn in at the top of the unit and blown downwards shielding the door opening and minimizing heat loss To achieve the optimum curtain effect the unit must extend the full width of the doo...

Страница 10: ...the bent edge at the bottom Fig 3 3 After the service repair and maintenance reattach the front hatch Place the hatch at the lower edge with the bent edge and fasten on top with screws Note that when...

Страница 11: ...ary for the functionality of the product but potentially dangerous for the environment The product should not be disposed of mixed with general household waste but delivered to a designated collection...

Страница 12: ...2021 02 12 CH Main o ce Frico AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact...

Отзывы: