Replacing heating elements/heating 

package (E) 

1. Mark and disconnect the cables to the 

heating elements/package 

2. Remove the mounting screws securing the 

heating elements/package in the unit and lift 

the heaging elements/package out.

3. Install the new heating elements/package in 

reverse order to the above.  

Replacing motor or impeller 

1. Remove the front.  

2. Remove gable end. 

3. Remove the screw between motor and fan.   

4. Disconnect the cables to the motor. 

5. Remove the screws securing the motor and 

lift it out together with the impeller.

6. Install the new motor and/or the new 

impeller as above in reverse order.  

vary depending on local conditions. Undertake 

cleaning at least twice a year. Inlet and exhaust 

grilles, impeller and elements can be vacuum 

cleaned or wiped using a damp cloth. Use a 

brush when vacuuming to prevent damaging 

sensitive parts. Avoid the use of strong alkaline 

or acidic cleaning agents. 

 

Replacing the water coil (W)

1. Shut off the water supply to the unit. 

2. Disconnect the connections to the water coil.

3. Remove the mounting screws securing the 

coil in the unit and lift out. 

4. Install the new coil in reverse order to the 

above. 

Draining the water coil (W) 

The drain valve is on the underside of the coil 

on the connector side. It can be accessed via 

the front hatch.

 

Temperature control 

Temperature control of FC maintains the 

exhaust temperature. Should the temperature 

exceed the preset value, the overheating alarm 

will activate. For more information see the FC 

manual.  

 

Overheating 

Unit with electrical heating 

The air curtain unit with electrical heating is 

equipped with an overheat protection. If it is 

deployed due to overheating, reset as follows: 

1. Disconnect the power supply with the isolator 

switch. 

2. Determine the cause of overheating and 

rectify the fault. 

3. Remove the front hatch.

4. Press the red button located inside the air 

curtain unit, at the inner gable of the terminal 

box. 

5. Reattach the front hatch and connect the unit 

again.

 

All units

All motors are equipped with an integral 

thermal safety cut-out. This will operate, 

stopping the air curtain should the motor 

temperature rise too high. The cut-out 

will automatically reset when the motor 

temperature has returned to within the motor’s 

operating limits.

 

Replacing the PC board 

1. The PC board is located in the terminal box. 

Fig. 2  

2. Mark and disconnect the cables to the PC 

board. 

3. Remove the screws securing the board and 

lift out.  

4. Install the new PC board as above in reverse 

order. 

Troubleshooting  

If the fans are not running or do not perform 

properly, check the following: 

•  The power supply. 

• 

That the intake grille/filter is not dirty. 

•  That the motor's safety cut-out has not been 

deployed.

•  Functions and settings of the FC control 

system, see the FC manual.  

If there is no heat, check the following: 

•  Functions and settings of the FC control 

system, see the FC manual. 

For units with electrical heating, also check the 

following:

•  Power supply to electric heater coil; check 

fuses and circuit-breaker (if any).

•  That the overheat protection has not been 

deployed.

  

Содержание PAF2500

Страница 1: ...Pamir 2500 Original instructions 13 EN 17 SE 22 NO 27 FR 32 DE 38 NL 43 ES 48 IT 53 PL 58 RU 64 FI DK 69...

Страница 2: ...sprechenden Sprachseiten DE Las p ginas introductorias contienen b sicamente im genes Consulte la traducci n de los textos en ingl s que las acompa an en las p ginas del idioma correspondiente ES De i...

Страница 3: ...1050 1560 2050 Cu 15 53 71 40 min 500 min 500 157 157 Cu 15 345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu 15 53 71 40 min 500 min 500 157 157 Cu...

Страница 4: ...Pamir 2500 4 Gland Knock out Knock out Knock out Gland Gland Fig 2 PC board FC is integrated within the air curtain at delivery PC board FC Gland 17 5 17 5 32 5 25 5 20 5 17 5...

Страница 5: ...Pamir 2500 5 Fig 3 Open the unit TX20 Fig 4 Minimum distance min 60 A B C...

Страница 6: ...min 500 mm 20 35 75 210 33 8 3x 5 10 162 Pamir 2500 6 Fig 6 Mounting with wall brackets Mounting with wall brackets PAF2510 2 pcs PAF2515 2 pcs PAF2520 3 pcs A B C D...

Страница 7: ...510 PAF2515 4 pcs 19417 PA2PF20 PAF2520 6 pcs 14875 PA2EF10 PAF2510W 14876 PA2EF15 PAF2515W 14877 PA2EF20 PAF2520W 27279 PAWAK PAF2500W 77179 FHDN15 PAF2500W See separate manual PA2EF PAWAK FHDN15 SDM...

Страница 8: ...39x39x23 mm 74695 FCOTX 39x39x23 mm 74699 FCLAP 89x89x26 mm 74702 FCWTA for water heated units 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703...

Страница 9: ...V IN L PE N Heating Blue Right motor Black Left motor M C Brown Blue C2 Lo C1 Mid C3 Run C C1 Mid M Brown Black C3 Run C2 Lo Only 2 m version Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 Inlet sensor A...

Страница 10: ...Mid C3 Run C C1 Mid M Brown Black C3 Run C2 Lo Only 2 m version N F2 F3 F1 H1 H2 N FCBASEPCB T3 230V IN L PE N Heating Motor GND 0 10V PWM Alarm Sensor I1 I2 O1O2 A1 A2 GND GND B1 B2 D1 D2 ON OFF Ter...

Страница 11: ...a2 c2 C4 C3 N F2 F3 F1 H1 H2 N FCBASEPCB T3 230V IN L PE N Heating Motor Blue Right motor Black Left motor M C Brown Blue C2 Lo C1 Mid C3 Run C C1 Mid M Brown Black C3 Run C2 Lo Only 2 m version Moto...

Страница 12: ...900 1450 17 11 68 42 51 115 0 5 400V3 7 2 19 246824 PAF2510E08 3 0 5 0 8 0 900 1450 27 17 68 42 51 115 0 5 400V3 11 5 20 246827 PAF2515E08 2 7 5 3 8 0 1400 2200 18 11 69 40 52 115 0 7 400V3 11 5 30 2...

Страница 13: ...unit See Fig 2 FC is supplied pre programmed Communication and sensor cables are connected to the PC board Should more than one air curtain be controlled by a single FC an additional communication cab...

Страница 14: ...he unit with 15 mm smooth copper pipe with a suitable coupling and internal liner Soldering is not recommended The connections to the heating coil must be equipped with shut off valves to allow troubl...

Страница 15: ...e the overheating alarm will activate For more information see the FC manual Overheating Unit with electrical heating The air curtain unit with electrical heating is equipped with an overheat protecti...

Страница 16: ...otection should be used Keep the areas around the air intake and exhaust grilles free from possible obstructions The unit must not be fully or partially covered as overheating can result in a fire ris...

Страница 17: ......

Страница 18: ...AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 247250 2...

Отзывы: