IHMC6-3

10

APPLICATIONS

Any application were high inrush current is an 
issue or control is required.  Typical use is for 
Infrared Heating lamps and Garden lighting. 

FEATURES

Soft Start

Up to 30% extended life of Lamp

Variable 
Control 

Ability to find comfort level  

Remote 
Control

Ease of use

HMI

Vary output and switch channels on 
and off

IP Rated

HMI and IHMC6-3 are IP65 rated, 
suitable for outdoor installation

Additional 
Channels

Multiple units can be added and 
function from 1 off HMI

SET UP

CAUTION! Ensure the 3 phase supply is 
disconnected before proceeding.

Connect the 3 phase supply 415VAC with Neutral 
and Earth to the terminals marked ‘L1, L2, L3 
Neutral and Earth’ ensuring the phase rotation is 
correct, so connect the leads like this:

Brown (L1) 

Black (L2) 

 

Grey (L3)

Connect the 3 X 2KW Lamp Loads to the 
terminals marked ‘T1, T2, T3, star connected to 
Neutral’.

Configure the oscilloscope to measure AC mains 
voltage and connect one of the scope’s channels 
across a lamp load. 

Connect the HMI unit to the main controller using 
four core twisted cable (included) to the terminals 
marked A, B, 24v. COM on both units.

Set DIP SW1 to 1000 this sets the controller to 
operate on channels 1,2 and 3 using either the 
handset or HMI unit, see Table A and B on the 
right hand side of the control pcb.

TEST

CAUTION! Beware of hazardous voltages while 
testing!

Switch on the 3 phase supply to the IHMC6-3 and 
verify the green ‘POWER’ LED is lit and the HMI 
digits are lit. When the main power controller 
is sending data back to the HMI unit the red 
‘STATUS’ LED will pulse.

Using the HMI push buttons step through the 

channels and power levels indicated by the UP 
and DOWN arrows on the fascia. 

Leave all three channels powered up to three 

different output levels, press the ALL ON/OFF 
button once this will turn all three channels off, 
press the button again this will reinstate the 
outputs to the power levels previously selected.

Pressing the CH OFF button turns the indicated 

channel off, to turn it on again use the POWER up 
button.

Switch off the mains power to the controller 

and wait a few seconds then re-apply the mains 
power, all the controller outputs will be in the off 
state, when the ALL ON/OFF button is pressed the 
previously selected channels and output levels will 
be re-instated.

These tests can also be done using the handset, 

with the handset the channels can be selected 
individually by pressing the buttons numbered 1, 
2 and 3.

With the DIP switch code set to 1000 the HMI 

unit will scroll around channels 1 2 and 3, with 
the code set to 1100 the HMI unit will display and 
scroll around channels 4, 5 and 6. With the code 
set to 1110 channels 7, 8 and 9 will be activated 
in the same manner.

Next set the controller to three phase three 

channel tracking where all three outputs are 
controlled as one channel this mode is selected by 
setting the DIP switch code to 0001. 

With DIP switch code set to 0001 channel 1 
will be selected and displayed on the HMI unit.  
Adjusting the POWER up and down buttons will 
result in all three phases having the same output 
levels through 0 to F.
Check that the HMI unit does not respond to any 
other channel selection.

After testing return the DIP SW1 code to 1000.

Switch off the 3 phase 415VAC mains supply 
and disconnect the IHMC6-3 - the test is now 
complete.

Содержание IHMC6-3

Страница 1: ...IHMC6 3 Original instructions 8 GB 2 FR ...

Страница 2: ...RNING It is important that the IHMC6 3 is not mounted directly to any flammable material i e wood It is recommended that the heatsink be speced off the mounting wall using pillars to aid in heat dissipation General Instructions Read these instructions carefully before installation and use Keep this manual for future reference The product may only be used as set out in the assembly and operating in...

Страница 3: ...k up to an additional 2 power units allowing you to control 9 individual 2kW outputs or 8 other power units allowing you to control 9 power units the 3 outputs within each power unit will increase at the same level in this configuration up to 54kW in total 2kW x3 outputs x 9 Power units Note see installation for output options HMI BUTTONS CHANNEL Increment channel selection 1 to 9 CHANNEL Decremen...

Страница 4: ...ll pulse Using the HMI push buttons step through the channels and power levels indicated by the UP and DOWN arrows on the fascia Leave all three channels powered up to three different output levels press the ALL ON OFF button once this will turn all three channels off press the button again this will reinstate the outputs to the power levels previously selected Pressing the CH OFF button turns the...

Страница 5: ...IHMC6 3 is designed to accept a 230V one phase supply The unit has a 2 stage supply filter to meet EMC legislation and comes in an IP65 rated enclosure complete with glands A 4 core low voltage cable is required to wire the Power unit to the HMI allow it to be mounted neatly away from the main installation The Interface unit is designed to be used with the Remote handset however you can also contr...

Страница 6: ...IHMC6 3 12 INSTALLATION CIRCUIT Table A Table B 4 core low voltage cable Neutral 3 phase supply 400V AC 50Hz Earth Load 1 Output Max 2kW Load 2 output Max 2kW Load 3 Output Max 2kW ...

Страница 7: ...up 1000 Switch setup 1100 Switch setup 0111 Mapped channels 1 2 3 Mapped channels 4 5 6 Mapped channels all 7 TABLE A TABLE A TABLE B Example 2 Control 1 Control 2 Control 3 Switch setup 1000 Switch setup 0100 Switch setup 0101 Mapped channels 1 2 3 Mapped channels all 4 Mapped channels all 5 TABLE A TABLE B TABLE B Option 2 shows 9 Power units offering 9 channels which can vary from 1 to 10 note ...

Страница 8: ...19 04 26 CH Main office Frico AB Tel 46 31 336 86 00 Industrivägen 41 SE 433 61 Sävedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net ...

Отзывы: