background image

FCR-230

1

FCR-230

INSTRUCTION

 

FCR230

Room controller for controlling fan-coil units

FCR-230 is a room controller intended for controlling fan-coil heaters/
coolers and thermal actuators or 3-point actuators. Installation is 
directly on the wall or on an electrical connection box. The fan can be 
set to one of three speeds.
FCR-230 has change-over function and can be used for 2-pipe or 
4-pipe systems.
 
For integration into a system, FCR-230 has communication via 

RS485 (Modbus, BACnet or EXOline). The device can be configured 

using the application Regio tool (version 1.3-1-05 or later), which can 
be downloaded from the Regin web site (www.regin.se).

Technical data

Supply voltage 

 

230 V AC ±10 %, 50/60 Hz

Power consumption 

< 3 W

Ambient temperature 

0...50°C

Ambient humidity   

Max 90 % RH

Storage temperature  

-20...+70°C

Built-in temperature sensor  NTC type, range 0...50°C
Inputs   

 

Refer to connection illustrations and    

 

 

 

table below 

Outputs  

 

Relays for fan control, 230 V AC, 3 A 

 

 

 

DO4, DO5 for actuators, Triac, 230 V AC,  

 

 

 

max. 300 mA 

Communication   

RS485: Modbus, EXOline (using 

 

 

 

automatic detection/switching) or BACnet

Modbus  

 

8 bits, 1 or 2 stop bits. Odd, even 

 

 

 

(FI) or no parity

Communication speed 

9600, 19200, 38400 bps (EXOline, Modbus  

 

 

 

and BACnet) or 76800 bps (BACnet only)

Terminal blocks    

Lift type for a maximum cable area 2.1 mm

2

Protection class    

IP20 

Pollution degree   

Overvoltage category 

3

Material casing    

Polycarbonate, PC

Dimensions  

 

102 x 120 x 29 mm

Installation

Place the controller in a location that has a temperature representative for 

the room. A suitable location is approx. 1.6 m above floor level in a place 

with unobstructed air circulation. 
Depress the locking tab in the upper edge of the controller with a 
screwdriver. Carefully turn the screwdriver until the bottom plate and the 

electronics unit are slightly separated (see figure 1). Then 

use the cutout 

that becomes visible in the edge of the bottom plate to open the upper 

edge completely (see figure 2). Do the same thing in the lower edge of the 

controller. 

Figure 1

Figure 2

Lift the electronics unit up from the bottom plate. The bottom plate with 
terminals has a number of hole combinations. Select suitable holes and 
fasten the bottom plate on the wall or connection box, so that the arrows 
on the bottom plate point upwards. Do not tighten the screws too hard!

Note: FCR-230 does not indicate fan breakdown or overheating of the 

heating coil. Therefore, all connections must be made externally. An 

overheating protection or similar can be used to disconnect the supply 
voltage.

 Disconnection

FCR-230 should be connected to a switch or circuit breaker in the 
building installation. This switch should be in close proximity to the 
controller and within easy reach of the operator, and should be 
marked as the disconnecting device for the equipment.
Always use the circuit breaker to disconnect the controller from the 
mains supply during maintenance of the fan-coil and actuators.

Settings

Control modes

FCR-230 can control heating and cooling in sequence or be set to 
seasonal switching between heating and cooling (change-over, see 
below).

Change-over function

FCR-230 has an input for change-over that automatically resets the 
output DO4 to operate with heating or cooling function. When the con-
troller is used together with a 3-position actuator, output DO5 is also 

affected by the change-over function in accordance with the above. A 

sensor of type PT1000 can be connected to the input and be mounted 
so that it senses the temperature on the supply pipe to the coil.
When the temperature exceeds 28°C, the output function is set to 
heating and when the temperature drops below 16°C, the output is 
set to cooling. As an alternative, a potential-free contact can be used. 
The input function can be set to NO/NC.
To ensure satisfactory functioning when using a sensor, the system 
must have continuous primary circuit circulation. When the change-
over function is not used, the input must be left disconnected.
When using an electric heater and the change-over function is set to 
heating, the sequence of operation for FCR-230 will be heating/heat-

ing and DO5 will be activated first.

If a change-over sensor is not connected, the sequence will be heat-
ing/heating. If cooling is to be used in the sequence, parameter 2 
(change-over mode) must be changed manually.

Operating mode

There are four different operating modes. Switching between these 

modes is performed locally.

Comfort: 

 is shown in the display. Heating and cooling have a 

smaller neutral zone NZC. An occupancy detector can be connected 
to the DI in order to select between Comfort and Economy. Switching 

between Comfort/Economy and Off can also be done via the On/Off 

button. Comfort/Economy is selected via the parameter list.

EN

  

Instruction for products with software version 1.2. 

Read this instruction before installation and wiring 

of the product. This product is BTL listed from 

software version 1.2-1-00 (BACnet stack 3.0.4).

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

i

Отзывы: