– = at the current water temperatures and airflows, the air outlet temperature will be less than 35 °C.
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
AR3500
12
Supply water temperature:55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL
max
2300
10,7
29
0,10
1,2
14,3
36,2
0,17
3,1
min
1100
5,3
29
0,05
0,4
8,2
39,8
0,10
1,2
AR3515WLL
max
3400
16,2
28
0,15
1,6
22,2
37,2
0,27
4,8
min
1550
7,6
28
0,07
0,4
12,3
41,2
0,15
1,7
AR3520WLL
max
4800
22,7
28
0,20
1,5
31,1
37
0,38
4,5
min
2200
10,6
27
0,09
0,4
17,3
41
0,21
1,0
Supply water temperature:50 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 50/30 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL
max
2300
10,8
30
0,13
2,0
10,7
31,6
0,13
1,9
min
1100
5,3
29
0,06
0,5
6
33,9
0,07
0,7
AR3515WLL
max
3400
16,4
29
0,19
2,7
17
32,6
0,21
3
min
1550
7,5
27
0,08
0,6
9,3
35,5
0,11
1
AR3520WLL
max
4800
22,9
29
0,27
2,5
23,7
32,5
0,29
2,8
min
2200
10,7
27
0,11
0,6
13,1
35,4
0,16
1
Supply water temperature: 45 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 45/35 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL
max
2300
11,0
32
0,20
4,3
12,4
33,8
0,30
8,5
min
1100
5,2
29
0,08
0,8
7,1
36,9
0,17
3,1
AR3515WLL
max
3400
16
30
0,26
4,7
19,1
34,4
0,46
12,7
min
1550
7,6
28
0,11
1
10,4
37,7
0,25
4,3
AR3520WLL
max
4800
22,3
30
0,37
4,5
26,7
34,3
0,64
11,9
min
2200
10,7
28
0,15
0,9
14,7
37,5
0,35
4,1
Supply water temperature: 40 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 40/30 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510WLL
max
2300
11,3
35
0,55
25,2
9,2
29,7
0,22
5,1
min
1100
5,2
30
0,13
1,9
5,2
32
0,13
1,9
AR3515WLL
max
3400
15,8
32
0,51
15,4
14,2
30,3
0,34
7,7
min
1550
7,3
29
0,15
1,9
7,8
32,8
0,19
2,7
AR3520WLL
max
4800
22,2
32
0,71
14,5
19,9
30,2
0,48
7,2
min
2200
10,3
29
0,22
1,8
11
32,7
0,27
2,5
Output charts water AR3500
AR3500WLL Special coil