AR3500
21
Output charts water
AR3500W Standard coil
Incoming / outgoing water temperature 90/70 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510W
max
2000
19
43
0,23
19
17
46
0,21
16
min
1000
12
51
0,15
9
11
53
0,14
6
AR3515W
max
2800
28
44
0,34
13
25
47
0,31
11
min
1400
18
52
0,22
6
16
54
0,20
5
AR3520W
max
4000
40
44
0,49
32
36
47
0,45
27
min
2000
25
52
0,31
14
23
54
0,28
12
Incoming / outgoing water temperature 80/60 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510W
max
2000
16
38
0,19
14
14
41
0,17
12
min
1000
10
45
0,13
7
9
47
0,11
4
AR3515W
max
2800
23
39
0,29
10
21
42
0,26
8
min
1400
15
46
0,18
5
13
48
0,16
4
AR3520W
max
4000
33
40
0,41
24
30
42
0,37
20
min
2000
21
46
0,26
11
19
48
0,23
9
Incoming / outgoing water temperature 60/40 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510W
max
2000
9
29
0,12
6
8
32
0,10
4
min
1000
6
33
0,08
3
5
35
0,06
1
AR3515W
max
2800
14
30
0,17
4
11
32
0,14
3
min
1400
9
34
0,11
2
7
36
0,09
1
AR3520W
max
4000
20
30
0,25
11
17
33
0,21
8
min
2000
13
34
0,16
5
11
36
0,13
4
Incoming / outgoing water temperature 60/30 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510W
max
2000
7
25
0,06
2
5
28
0,04
1
min
1000
5
29
0,04
1
3
31
0,03
1
AR3515W
max
2800
10
26
0,08
1
8
28
0,06
1
min
1400
7
29
0,06
1
5
31
0,04
0,4
AR3520W
max
4000
15
26
0,13
3
12
29
0,09
2
min
2000
10
30
0,08
2
8
32
0,06
1
Incoming / outgoing water temperature 55/35 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AR3510W
max
2000
8
27
0,10
5
6
29
0,08
3
min
1000
5
30
0,06
2
4
32
0,05
1
AR3515W
max
2800
11
27
0,14
3
9
30
0,11
2
min
1400
7
31
0,09
2
6
33
0,07
1
AR3520W
max
4000
17
28
0,21
8
13
30
0,16
5
min
2000
11
31
0,13
4
9
33
0,11
3
Содержание AR3500 W
Страница 4: ...AR3500 3 Fig 2a Mounting on threaded bars Mounting Fig 2b Mounting on threaded bars inside unit...
Страница 9: ...Wiring diagrams Without heat Basic Basic parallell SIReB1 SIReUB1 SIReB1 SIReUB1 SIReB1 AR3500 8...
Страница 49: ...AR3500 48 RU Thermozone AR3500 c 3 5 IP 44 IP20 AR3500 1 4 1 2 8 3 1 2 3 3...
Страница 51: ...AR3500 50 RU 2 1 2 3 1 2 2 3 40 C SIRe 1 2 3 4 AR3500E 1 2 3 AR3500W 1 2 3 4 AR3500W AR3500E...
Страница 52: ...AR3500 51 RU AR3500W 300 AR3500E 23...