TIGHT-FIT KIT

UV LIGHT FOR PTACS & FAN COILS

INSTALLATION GUIDE

 

TIGHT FIT KIT

 is installed inside PTACs, Fan Coils, and air handlers with limited access to reduce 

biological contamination for reduced system maintenance and improved indoor air quality.

1

 Installation in PTACs and Fan Coils

US patent #7,704,463

TUV-TFK-MAN 090721 

© Fresh-Aire UV

Parts Included

A

 UV Lamp & Shield

      PIG TAIL

B

 “ER” Power Supply*

C

 “ST” Power Supply*

D

 Self-Tapping Screws

E

 Replacement O-Rings

F

  Tap-in Connectors (ER model)

G

 Spade Connectors (ST model)

H

 Sight Glass

I

 Slit-Loom protector

J

 Warning sticker

K

 Zip-Tie

L

 Zip-Tie Base

* Kit includes one power supply 

“ER” or “ST” depending on model

IMPORTANT!

•  Install so that direct UV light is not visible in occupied space

•  Only qualified technicians should install this product*

•  Install in accordance with relevant building codes

WARNING

PROTECT EYES FROM UV LIGHT

TURN OFF UNIT OR DISCONNECT

BEFORE SERVICING

*Installation of this product by anyone other than licensed HVAC or electrical contractors voids warranty.

PTAC

Front

Front

Front

Side

Side

Side

Fan Coil (vertical)

Fan Coil (horizontal)

1. 

Determine the best position for placement of the UV lamp and power supply. (see examples)

2.

 Position lamp for best UV exposure and to minimize light leakage into room

3. 

Locate lamp so it irradiates wet side of coil and/or blower areas where fouling is present

4.

 Mount lamp with magnet or self-tapping screws

5.

 Turn off power or disconnect HVAC unit before installing power supply

6.

 Connect to 18-32 VAC or 110-277 VAC power depending on model (see wiring diagram)

7.

 Apply warning/replacement sticker to outside of unit