2. Optional 12” Stand-off

Conduit

1

 Assembly & installation

3

1. L-Bracket 

mounting

L-Bracket

L-Bracket

UVC Lamp

1/2” EMT Tubing

Optional 

12” Stand-Off

Optional 

12” Stand-Off

APCO Module

Optional 12” stand-offs can 

be used in place of L-Brackets. 

1. 

In most situations, when the system is mounted to surfaces 

perpendicular to the surface to be irradiated, 

L-Brackets

 are 

attached to the wall or support with 

Self-Tapping Screws

.  

2.

 

Optional 12” Stand-off 

adaptors are available if there is no 

suitable wall surface for mounting parallel to the coil. Use 

self-tapping screws to attach a 

1/2” Pipe

 

Strap

 onto the end 

of the stand-off then mount using 

Self-Tapping Screws

 

2a. Alternate Mounting:

 Attach 

L-Bracket

 with 

1/2” Pipe

 

Straps

  

to interior of 

Stand-off

. This allows lamps to be positioned less 

than 12” from coil.

3.

 

Optional Vertical Support 

adds strength to the conduit tubing 

support framework and prevents sagging on installations with 

two or more lamps per tubing length. Measure the distance 

from floor to ceiling then measure and cut tubing 1.75” less than 

that length. Use the 

1/2” Pipe

 

Couplings 

to extend the 

Vertical 

Support

 to floor and ceiling for a snug fit.

2a. Alternate Mounting of 12” Stand-off

3. Optional Vertical Support

Conduit

Conduit/

conduit 

Clamp

Vertical Support

First, determine the ideal mounting location within the air system then 

configure the 

APCO® Rack

 

System

 accordingly. The 

APCO® Rack

 

System

 can be mounted to the air handler wall or similar support 

several ways depending on the size, orientation, and distance 

of the mounting surfaces and surfaces to be irradiated. 

1/2” Pipe 

Coupling

1/2” Pipe 

Coupling

Conduit