![Freedom Won Lite Commercial 100/80 HV Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/freedom-won/lite-commercial-100-80-hv/lite-commercial-100-80-hv_installation-and-user-manual_2329981011.webp)
Freedom Lite Commercial Installation Manual Revision 3
P a g e
10 | 29
1.
The maximum (peak) and continuous current and power ratings are the same for the Lite Commercial HV and
HV+ battery range. The maximum values given apply to both charge and discharge. For systems requiring more
than 400kW from the Commercial HV range and 630kW for the HV+ range, two or more batteries must be
installed in parallel.
2.
Higher voltage custom batteries are available on request ranging up to 750V DC (nominal) should this be required
for other types of inverters. Note that custom voltages may result in different battery capacities from what is
included in this specification sheet – please contact Freedom Won for further details.
3.
Fly Leads 3.0m long as standard, power cable Red = Positive, Black = Negative, conductors in table refer to one
electrode i.e. per positive and negative connections. Up to 5m long available at extra cost (must be specified in
order). Note that the fly leads exit the battery on the right-hand side near the floor on all the Lite Commercial HV
and HV+ models. This is to suit the bottom entry of the floor standing ATESS inverters. A cable trench is
recommended for routing this cable along with all the other cables going to and from the inverter (a cable tray is
an alternative).
4.
Charging below 0°C not permitted. Extended time above 45°C not recommended for optimal battery life.
5.
See Freedom Won Warranty document for further detail.
Figure 2.4 CANdapter for Programming Freedom Lite Commercial Range