Installation

Important Safety Messages

Franklin Fueling Systems equipment is designed to be used to pump volatile hydrocarbon liquids such as 
gasoline and diesel fuel. Installing or working on this equipment means working in an environment in which 
these highly flammable liquids are present. 

This presents a risk of severe injury or death if these instructions 

and standard industry practices are not followed. Read and follow this entire instruction booklet before 

installing or working on this equipment.

 

As you read these instructions, watch for the following safety symbols:

 

WARNING

 

This symbol identifies a potentially hazardous situation which, if the instructions that follow 
it are not adhered to, could result in death or serious bodily injury.

 

CAUTION

This symbol identifies a potentially hazardous situation which, if the instructions that 
follow it are not adhered to, could result in serious property damage, including possible 
environmental contamination as a result of the leakage of fuel from the equipment.

   

WARNING

Follow all federal, state, and local laws governing the installation of this product and its 
associated systems. When no other regulations apply, follow NFPA codes 30, 30A, and 70 
from the National Fire Protection Association. Failure to follow these codes could result in 
severe injury, death, serious property damage and/or environmental contamination. 

 

WARNING

Always disconnect both power supplies (240V Hook and the 415 input) before installing or 
servicing. Be sure to use proper lock and tag out techniques to ensure no power is applied 
accidentally. Failure to do so could result in severe injury or death.

Installer:

 This instruction booklet MUST be left with the owner of the service station at which the equipment is 

being installed.

Station Owner:

 Retain these instructions for future use and provide them to persons servicing or removing this 

equipment.

Содержание STP-SCIIIC

Страница 1: ...3 PHASE SMART CONTROLLER STP SCIIIC INSTALLATION GUIDE...

Страница 2: ...ringement of patents or other rights of third parties that may result from use of this manual or the products We make no warranty of any kind with regard to this material including but not limited to...

Страница 3: ...ant Safety Messages 5 Installation Instructions 6 Calibration 6 Calibration Tips 6 Master Slave Alternating Circuit 7 Wiring Diagram 1 10 Troubleshooting Guide 11 Resetting The Controller 11 Disabling...

Страница 4: ...4 Intentionally Blank...

Страница 5: ...ions that follow it are not adhered to could result in serious property damage including possible environmental contamination as a result of the leakage of fuel from the equipment WARNING Follow all f...

Страница 6: ...ibration process has been completed an alarm can be silenced when an abnormal condition is present by briefly depressing the push button See Troubleshooting Guide for details 2 Press and hold the push...

Страница 7: ...ain wire of shielded cable to Ground G at one end only Wire per NFPA 30A and NFPA 70 For the signal wires use 18 AWG 3 conductor cable 300V min with conductors twisted and within a common jacket Cut w...

Страница 8: ...POWER SUPPLY L1 L2 L3 M2 M1 M3 L1 L2 L3 M1 M2 M3 M1 L2 L1 L3 L2 L1 L3 M2 M1 M3 M2 M3 To STP To STP RS 485 G CONNECTION USE THREE CONDUCTOR SHIELDED CABLE WITH DRAIN WIRE 22 AWG MINIMUM RS 485 TO ADDIT...

Страница 9: ...tion Table Motor Horsepower Rating Pole 4 Pole 5 Off Off 1 5 Off On 3 On Off 5 On On Table 3 Fault Readout Selection Table Pole 6 Setting Description Off Normal Operation On With this mode selected th...

Страница 10: ...THE CONTROL BOX WILL BE ENERGIZED PROVIDING POWER TO THE STP NOTE SEE PRODUCT INSTALLATION INSTRUCTIONS FOR FURTHER DETAILS WIRING MUST CONFORM TO ALL FEDERAL STATE AND LOCAL ELECTRICAL CODES MOTOR CO...

Страница 11: ...the dispensers are turned off there may be some power still applied to the STP SCIIIC Hook Connector If this condition exists call Franklin Fueling Systems Technical Service for assistance No lights...

Страница 12: ...ew installation reinstall extractable Note PMA can have a locked rotor during startups if it has been exposed to a corrosive environment such as a ballasted tank Turn on power to the STP SCIII unit an...

Страница 13: ...M2 M1 to M3 and M2 to M3 and compare the values with the values found in the STP IST Installation Manual High Capacity Installation Manual or TB004 6 Troubleshoot the wiring to determine the cause of...

Страница 14: ...ep If condition is still present continue to next step 3 Disconnect power at load centers lock and tag circuit breakers 4 Replace Relay see Replacement Parts section 5 Turn on power to the STP SCIII u...

Страница 15: ...or present proceed to the next step 4 With the power still off measure the resistance of the windings See TB004 for the proper values If the measurements are not within the acceptable limits replace P...

Страница 16: ...223879102 r2 A Franklin Fueling Systems Brand...

Отзывы: