Section 5 –
Eliwell Controller Error Codes:
The Eliwell Controller provides error code messages on the temperature display when the HCMF
freezer is not performing as required. Alarms are indicted by the error code and an alarm icon
which appears on the controller display.
The Problem
Possible Cause
What To Check & Do
Error Code E1
Displayed – Probe
1 Faulty
Measured values outside
operating range
Probe faulty, short
circuited or open
Check probe for damage
Check probe wiring for damage. If faulty:
Replace temperature probe.
(See Tips T-3)
Error Code E2
Displayed – Probe
2 Faulty
Measured values outside
operating range
Probe faulty, short
circuited or open
Check probe for damage
Check probe wiring for damage. If faulty:
Replace defrost probe.
(See Tips T-4)
Error Code AH1
Displayed – Alarm
for HIGH probe
temperature
Value measured by probe
greater than HAL (50
F)
after (
tAL
) factory set
time???
Wait for value read by probe (Pb1) to return
below HAL
Error Code AL1
Displayed – Alarm
for LOW probe
temperature
Value measured by probe
greater than LAL (-50
F)
after (
tAL
) factory set
time???
Wait for value read by probe (Pb1) to return
below LAL
This is typically a probe failure. If faulty,
replace temperature probe.
(See Tips T-3)