background image

INSTALLATION DEMENSION 

 

Panel cut-out   136   x   136mm 

c JKL Controllers 

5. Functional code table 

Functional 

code 

Name Setting 

range  Unit 

Min. 

value 

Factory setting 

value 

F-0 COS

φ

 0.90-0.99 

 

0.01  0.98 

F-1 Delay 

10-99 S 

1 30 

F-2 Overvolt

age 

410-470 V 5 430 

F-3 Number 

of

return 

circuits

1-10/12 

(1-57) 

 1 

10/12 

(5/7) 

F-4 Self-test

0. 

YES 

1. NO 

 —  1 

F-5 Throwin/

out cycle

Unable for setting

100 cycles 

0XX 

 

 

6 Notes 

6.1  After connecting with power supply, 0.CC denotes that load current is less than 5% of 

designed rating, or no load or input current is open. 

 

6.2  After connecting with power supply, it is unable to throw in the capacitor but leading or power 

factor is more than 0.90 and less than 0.30 in the display, denoting wrong selection of phase 

of input current and voltage. If so, reconnect the wire. 

 

6.3  If self-test is required, the self-test F-4 shall be set at 0. Disconnect with power supply and 

then restart the power supply. In this case, self-test cycle will begin. After completion of 

self-test, F-4 will be automatically set at 1 under the control of the controller. 

 

    Installation dimension 

 

 

 

 138 x 138mm 12steps,             

68X68mm 5-7steps 

Содержание GMKPc JKL Series

Страница 1: ...tp www frankegmkp com Berlin Frankfurt Germany Tel 0049 30200033043 Email info frankegmkp com C1607 Software Park National Hi Tech Industry Development Area Wuxi Tel 0086 510 85211911 Fax 0086 510 85215070 Email info frankeenergy com Save energy and reduce Carbon Dioxide emission For a better Power ...

Страница 2: ...ly Wide applicability The Controller can automatically meet the distribution systems of different parameters while the transformation ratio of current transformer and capacitance of compensation capacitor are not required Over voltage protection Automatically and quickly throw out the thrown in capacitor unit step by step when the voltage of power network exceeds the setting value Low reactive loc...

Страница 3: ...P is connected with the contact B when the coil voltage of contactor is 380 V see the diagram at the back The contact P is connected with the contact N when coil voltage is 220 V 4 Parameter setting 4 1 In the setting state automatically return to automatic state if not pressing any key within 20 seconds 4 1 Press key the manual light will turn on Then press key for gradually throwing in and key f...

Страница 4: ...oad current is less than 5 of designed rating or no load or input current is open 6 2 After connecting with power supply it is unable to throw in the capacitor but leading or power factor is more than 0 90 and less than 0 30 in the display denoting wrong selection of phase of input current and voltage If so reconnect the wire 6 3 If self test is required the self test F 4 shall be set at 0 Disconn...

Страница 5: ... 380V contact P connects with contact B Drilling size 68x68mm for 5 steps and 7 steps 113x113mm for 10 steps and 12 steps Mounting size 72x72mmx213mm for 5 steps and 7 steps 138x138mmx150mm for 10 steps and 12 steps c JKL controllers Connection power factor correction GMKPcJKL Controllers ...

Страница 6: ...GMKP is partner of major projects like Olympic projects CCTV EXPO2010 Beijing airport Moreover FRANKE is supplier of many famous foreign brand capacitor manufacturers for their OEM production of capacitors In addition to our capacitor manufacturing FRANKE GMKP ENERGY CONTROL provides a wide range of products for power factor correction PFC and energy management systems such like References FRANKE ...

Отзывы: