3.8 Trouble shooting

Situation

Probable causes

-

Corrective action

Fire difficult to start. Fire goes
out.

Wood green… or too damp

-

Use hard wood logs, which have been cut for at least
two years and stored, under a ventilated shelter.

Logs are too big

-

To light the fire, use small, very dry twigs. To maintain
the fire, use split logs.

Poor quality wood

-

Use hardwood that have a higher calorific value per cu
metre (Yoke-elm, oak, ash, maple, birch, elm, beech,
etc..).

Not enough primary air

-

Open air control.

-

Open the outside fresh air inlet grid.

Insufficient draught

-

Open temporarily the flue damper control.

þ

-

Check that the flue is not obstructed, sweep it if
necessary.

-

Seek advice from a chimney specialist.

Fire burns too quickly.

Too much draught

-

Partially close the air control.

Excessive draught

-

Check that the chimney-flap does not remain opened.

þ

-

Install a draught stabiliser to the connector pipe.

Poor quality wood

-

Do not continuously burn small wood, sticks, bundles,
carpentry offcuts (plywood, pallets), etc...

Smokes when lighting up.

The flue damper is closed

-

Open the flue damper.

Flue duct is cold

-

Burn paper and kindling wood to increase heat.

Room is in decompression
(negative pressure)

-

In houses equipped with mechanical ventilation, partly
open a window until the fire is well established.

Smokes while burning.

Insufficient draught

-

Open temporarily the flue damper control.

þ

-

Consult a chimney specialist.

-

Check that the flue is not obstructed, sweep it if
necessary.

Down draught

þ

-

Install an anti-down draught cowl.

Room is in decompression
(negative pressure)

-

In houses equipped with mechanical ventilation, an
outside air intake must be installed in addition to the
chimney itself.

Low heat output.

Poor quality wood

-

Use the recommended fuel.

Poor mixing of the convection air

þ

-

Check the air flow system (air inlet, piping, air outlet).

-

Check that the next rooms are equiped with ventilation
grids to help out the hot air circulation.

Technical manual “1274”

9

“SAVOY MK2” - model : 134 08 09

Instructions for user

þ

: This sign means that you should ask

for a qualified engineer to do the work.

Содержание SAVOY MK2 ELEGANCE 134 08 09

Страница 1: ...rtificate Document n 1274 8 20 09 2011 Multifuel stove Norm DIN EN 13240 2005 10 Model 134 08 09 Output 8 kW Technical manual to be saved by the user for future reference FR EN NL IT SAVOY MK2 ELEGANC...

Страница 2: ...ant to burn wood or solid fuel safely WARNING Incorrectly installed this appliance can be dangerous and possibly cause serious accidents We recommend that you engage the services of a professional eng...

Страница 3: ...mity with DIN EN 13240 2005 10 Intermittent burning heating appliance Detachable flue spigot for rear or top chimney connection Front loading door fitted with large refractory glass panel Adjustable p...

Страница 4: ...te this load Make sure they are not combustible or covered with combustible material as per the Building regulations There must be a clearance of at least 150 mm at each side of the appliance and at t...

Страница 5: ...combustible material walls cross members It must permit an easy sweeping 2 4 Mounting the flue collar The stove is supplied with a connection flue spigot with an inner diameter of 125 mm and an outer...

Страница 6: ...e utilisation check Check that the seals of the smoke line are in good condition Check that the door closes correctly Check that the glass is not damaged Check that the smoke passages are not obstruct...

Страница 7: ...or infirm people 3 1 Fuel This appliance is not an incinerator Use hard wood logs which have been cut for at least two years and stored under a ventilated shelter Use hardwood that have a higher calor...

Страница 8: ...ard to the live embers 3 5 Maintenance of the Chimney Very important In order to avoid any incident chimney fire etc maintenance tasks must be carried out regularly If the appliance is regularly used...

Страница 9: ...mall wood sticks bundles carpentry offcuts plywood pallets etc Smokes when lighting up The flue damper is closed Open the flue damper Flue duct is cold Burn paper and kindling wood to increase heat Ro...

Страница 10: ...10 Technical manual 1274 SAVOY MK2 model 134 08 09 Note Note...

Страница 11: ...38 Reducing plate A B C D 01 23 237406 Reducing plate A B C D 01 24 237427 Reducing plate A B C D 01 25 259015 Fixing plate A B C D 04 26 262607 Heat shield A B C D 01 27 270402 Air control flap A B C...

Страница 12: ...Technical manual 1274 SAVOY MK2 model 134 08 09 Spare parts Figure 8 Spare parts view 20 50 21 7 51 51 6 0 52...

Страница 13: ...42 327910 MK Tray D 01 43 331132 EF Main door A 01 43 331132 RH Main door B 01 43 331132 RP Main door C 01 43 331132 MK Main door D 01 44 332004 Air duct A B C D 01 45 352176 EF Top plate A 01 45 352...

Страница 14: ...e exception of closed combustion fireplace and inserts for which our guarantee is 5 five years excluding the following 1 Indicator lights fuses electrical elements and fans 2 Parts subject to wear or...

Отзывы: