Description of the menu | 41
FRAKO | Operating Manual | Power Quality Controller – PQC
6.2.3 Service
Main menu > Display > Service
6.2.3.1 Configuration
Main menu > Display > Service > Configuration
Control status
Automatic or manual control
mode
Switching sequence
Display of the capacitor stages
detected. The relative values
(switching sequence) can be
distributed over the available stages as desired. The largest
permitted relative value is 16, the smallest 0.
Available stages
Number of capacitor stages detected
c/k setting [mA]
The response current is determined from the smallest capaci-
tor stage detected
Connection type
Type of connection for L1, L2 and L3 current transformers.
See Table in
Section 5.3.4 “Manual connection and stage
6.2.3.2 Stage status
Main menu > Display > Service > Stage status
No.
No. of the stage [1–12]
Stat. (status)
ON / OFF / [x seconds]
ON: Switches stage in manually
OFF: Switches stage out manu-
ally [x seconds]: Time remaining
until the capacitor stage can be switched in again (discharge
time)
Q[var]
This is the stage corrective power in var (3-phase stage
corrective power).
Switching cycles
Number of stage switching cycles