Current Simulate Functions: 

 
The FracSim meter can sink or source 

0 up to 22mA

 while 

simultaneously measuring loop voltage. To access the current 

simulation from the main menu select 

SIM=>

 and 

mA

. Use the 

following pin outs: 

 

 
 

 

 
 
 

As previously stated the current simulation also shows the measured 
loop voltage for quick loop diagnostics. The loop voltage function is 
only useful while sinking current. Most transmitters require a 

minimum 8 to 10 volts

. So if you see a loop voltage lower than this 

or the transmitters recommended voltage minimum, then this is an 
issue. The FracSim meter will work because it is internally powered 
but the transmitter may not 

 

 

Pressing the turn knob down quickly will increment the 
output value by 4mA each press

 

 

Turning the turn knob clockwise will increment the output 
value by 0.1mA 

 

 

Turning the turn knob counter-clockwise will decrement the 
output value by 0.1mA 

 

 

 

 

 

 

▪ 

Sinking:

     

- Supply volts from equipment to red socket on meter  

                        - Black socket to signal input of equipment   
 

▪ 

Sourcing:  - Red socket to signal input of equipment   

 

         - Frame ground to black socket on meter 

 

12 

 

Frequency Simulation Function: 

 
The FracSim meter will simulate an 

AC / DC square wave

 frequency 

from 

1 to 5000 Hz

 with a range from 

0 to 18 volts 

(maximum is 

proportional to battery voltage). To access the frequency simulation 

from the main menu select 

SIM=>

 and 

Hz

. Use the following pin 

outs: 

 

 

 

 

Adjustments: 

 

 

Default output is 18V (battery voltage) DC coupled at 100 Hz 

 

Turning the knob will increment / decrement the frequency 
output 

 

Pressing the turn knob down quickly will enter an adjustment 
sub menu

 

 

First Select AC or DC for the correct type of coupling 

 

 

Second turn the knob left and right to adjust the voltage level  

 

For devices that have a very  low level switching point use the 
AC mode. An example of a low level input could be the Red 
Lion silver tube amplifiers (Part: ASTC0000). 

  
 

 

 

 

Red socket to device input  

 

Black socket to device ground 

 

Содержание FracSim mini

Страница 1: ...ur goal is to provide quality tools with a robust design to meet the needs of well service technicians If you have any questions or concerns please contact us at FracSim Meters Grande prairie Alberta...

Страница 2: ...5 Warnings 6 Using this manual 7 Using the interface turn knob 7 Main Menu 8 Voltage Measure 9 Current Measure 9 Continuity Measure 9 Diode Measure 10 Frequency Measure 10 Scope View 10 Current Simul...

Страница 3: ...ed to the colder weather The FracSim meter is calibrated at 22 C the highest level of accuracy is at 22 C the temperature where it was calibrated at Fail Safe Contrast boot If the meter s displays con...

Страница 4: ...2 seconds causes the meter to exit the current mode This icon marks all the pin outs for each function All measurement function use the Red Socket positive and Black socket negative This icon marks i...

Страница 5: ...nd the display will flash OL Continuity Measure The FracSim meter will measure continuity An audio and visual feedback will trigger at approximately 50 To access continuity measure mode from the main...

Страница 6: ...crement the output value by 0 1mA Sinking Supply volts from equipment to red socket on meter Black socket to signal input of equipment Sourcing Red socket to signal input of equipment Frame ground to...

Страница 7: ...r data burst Turn the turn knob to scroll through the data buffer DAT COMPANY SPECIFIC The baud rate and format is pre determined The data input is application specific The display shows the data inpu...

Отзывы: