Foxtron DALImiw30 Скачать руководство пользователя страница 3

Control of DALImiw30 is done by standard DALI messages. Their meaning for DALImiw30 
is shown in following table:

DALI command

Meaning to illuminance sensor DALImiw30

Direct arc power control, Off,

Up, Down, Step up, Step down,

Recall max level, Recall min

level, Step down and off, On and

step up

Stop of the regulation

GoToScene 0 – 15

Function is dependent on the setting Light sensor → Advanced settitng
→ Set response to scene recall

Automatic

 –  Start of the regulation

OFF

 – stop of the regulation, regulated lights are switched off

Actual-auto

 – Start of the regulation. Current illuminance level is set 

as desired level.

MASK

 – no function (stop of the regulation)

STORE DTR AS MIN LEVEL

Set of the desired illuminance level

1)

QUERY MIN LEVEL

Read of the desired illuminance level 

1) 

QUERY ACTUAL LEVEL

Actual illuminance level 

1) 

Illuminance range is 0-1000lx.

1) 

Data format is stated in the following table.

Illuminance data format

Data - 1byte (binary notation)

Illuminance level [lx]

0000xxxx

0 – 15lx (step 1lx)

0001xxxx

16 – 46lx (step 2lx)

0010xxxx

48 – 108lx (step 4lx)

0011xxxx

112 – 232lx (step 8lx)

0100xxxx

240 – 480lx (step 16lx)

0101xxxx

496 – 976lx (step 32lx)

0110xxxx

1008 – 1968lx (step 64lx)

Illuminance level is set and read as an 8bit number in format

0 E E E M M M M

And its value is given according to the relation

2

4

+

E

16

+

2

E

M

Example

65 = 0x41 = 01000001b ~ 256lx
50 = 0x32 = 00110010b ~ 128lx

3

www.

foxtron

.eu

Содержание DALImiw30

Страница 1: ...r DALImiw30 since versions firmware 1 6 and hardware 4 0 DALImiw30 Microwave sensor up to 2 6 meters height Illuminance sensor Regulation to constant level Range 0 1000 lx Powered from DALI bus or 230V Can power DALI bus 1 www foxtron eu ...

Страница 2: ... by DALImiw30 no other master is required Based on movement the lights can be regulated to various lux levels Addressing and setup is done by software DALIconfig which is downloadable for free on the web of manufacturer Start or stop of the regulation or setting the desired illuminance level is done by standard DALI messages from any DALI controller Control of the DALImiw30 is done by commands to ...

Страница 3: ...set as desired level MASK no function stop of the regulation STORE DTR AS MIN LEVEL Set of the desired illuminance level1 QUERY MIN LEVEL Read of the desired illuminance level 1 QUERY ACTUAL LEVEL Actual illuminance level 1 Illuminance range is 0 1000lx 1 Data format is stated in the following table Illuminance data format Data 1byte binary notation Illuminance level lx 0000xxxx 0 15lx step 1lx 00...

Страница 4: ...lute Absence value Control speed Regulation speed The most common setting is 3 Lower values mean faster regulation higher values mean slower regulation Switch on level First value send at the beginning of the regulation Minimum level sends the command Recall min level Maximum level sends the command Recall max level Calculated will compute the value dependent on the surrounding illuminance Flying ...

Страница 5: ...time on Dimming speed to 1 Presence value 4 Run on time The time without any movement after which is activated absence mode 5 fade time to absence Dimming speed to 2 Absence value 6 Switch off delay Absence time after which are luminaires dimmed or switched off If the function never off is activated luminaires remain on level 2 Absence value 7 fade time to off Dimming speed to off 6 Switch off del...

Страница 6: ... one DA terminal with OUT terminal and the other DA terminal with OUT terminal DA terminals are interchangeable Power supply of DALI bus can provide current up to 50mA which allows to power up to 25 DALI ballasts For this function the DALIpir20 must be powered from 230V If the DALI bus is powered by any other supply terminals OUT and OUT are not connected External input Lex is external input to wh...

Страница 7: ...ith respect to following conditions No light source controlled not controlled by sensor should point directly to sensor Sensed area should not point towards the windows In sensed area should not be any shiny objects which reflection affects the sensor In case of installation multiple sensors in one room their sensed area should not overlap Maximal mounting height is 2 6 meters 7 www foxtron eu ...

Страница 8: ...Detection diagrams 8 www foxtron eu ...

Страница 9: ...Dimensions mm tel 420 274 772 527 e mail info foxtron cz web www foxtron eu 9 www foxtron eu ...