ISSUE DATE 10-09-03 REV. DATE 12/17 REV. LEVEL: 17 ECO 1-7383 OIPM P/N 8329
MINIMUM CLEARANCES TO COMBUSTIBLES
•
Dimensions are listed in inches
•
Dimension “B” indicates the
required clearance to combustibles;
it DOES NOT indicate the required
mounting height.
EXPLOSION HAZARD
FIRE HAZARD
BURN HAZARD
•
Serious injury or death may
occur.
•
Do not use in locations containing
hazardous atmospheres.
•
Do not touch any part of heater
while in operation or directly
thereafter. It is very HOT.
END VIEW – 0 DEGREE TILT
6”
B”
C”
TOP VIEW
- 2 UNITS SHOWN
Multiple Heaters may be butted
together on end surfaces
C”
C”
24”
FROM A
VERTICAL OR
COMBUSTIBLE
SURFACE
OR
36”
FROM
ANOTHER
HEATER
END VIEW – 0-45 DEGREE TILT
B” Dimension
2-Lamp units:
-72” for a single unit
-72” for (2) or more
heaters being
mounted end-to-end.
3-Lamp units:
-72” for a single unit
-96” for (2) or more
heaters being
mounted end-to-end.
C” Dimension
TYP. BOTH SIDES AND
ENDS
24”
FROM A VERTICAL
OR COMBUSTIBLE
SURFACE
36”
FROM ANOTHER
HEATER
WARNING!
Heaters should be installed so that the minimum clearance to vehicles, as marked on the
heater, will be maintained. If vehicle lifts are present, ensure that the minimum clearance
to combustibles will be maintained from the highest raised vehicle.
B”
B”
B”
6”
8