OAC: AUX output configuration: 

(AL, Li, UL, Ip, AA, rE, dF, C2)

AL:

 alarm output; 

Li: 

light of the cabinet; 

UL: 

for the ultra-violet light (It is actionable only when the controller is

in OFF position); 

Ip:

 to extract the insert probe

 

(It is actionable only when the controller is in OFF position); 

AA:

anti - condensation; 

rE:

 the IV relay works as a thermostat, with direct action (cooling) (OAH>0), and inverse

actions (heating) (OAH<0); 

dF: 

the IV relay is activated during the defrost, at the end of the defrost it remains

ON for the OAt time; 

C2: 

second compressor. See 1c2 parameter for different settings.

OAP

AUX output polarity (

OP 

÷

 CL) 

OP

= normally open; if it is ON the terminals 6-8 are closed. 

CL

= normally

closed; if it is ON the terminals 6-7 are closed.

OAt

 AUX output timer

: (0÷255 min) time in which the AUX output stays ON. It is enabled when OAC = Li or

UL or Ip or AA or dF.

OAS Set point for AUX output 

(-50÷50; ris.1 °C/ 1°F)

OAH Differential for AUX output: 

(-12.0

÷

12,0; ris.0,1°C/1°F, always 

0) Intervention differential for the set point

of the auxiliary, with OAH<0 the action is for heating, with OAH>0 it is for cooling. 

COOLING:

 AUX cut IN is

OAS Plus Differential (OAH>0). AUX cut OUT is when the temperature reaches the set point OAS.

 

HEATING:

 AUX cut IN is OAS Plus Differential (OAH<0). AUX cut OUT is when the temperature reaches the set

point OAS.

OAi

Probe selection for the AUX output (rP, EP, iP) 

rP = thermostat probe, EP = evaporator probe; iP =

insert probe

DEFROST
tdF

Defrost type (not present in the XB350C)

: (

rE

= electrical heater; 

in

 = hot gas).

dPO Defrost before the holding: no

= no defrost;  

YES

= defrost at the start of a holding cycle.

IdF

Interval between defrost cycles

: (0.1

÷

 24.0; res. 10 min) Determines the time interval between the

beginning of two defrost cycles. (with 0.0 the defrost is disabled)

dtE

Defrost termination temperature (not present in the XB350C)

: (-50

÷

50 °C/°F) Sets the temperature

measured by the evaporator probe, which terminates the defrost.

MdF Maximum length for defrost

: (0÷255 min)  When EPP = no (timed defrost) it sets the defrost duration, when

EPP = YES (defrost termination based on temperature) it sets the maximum length for defrost.

dFd

 Temperature displayed during defrost

: (rt , it, SEt, dEF

) rt: 

real temperature; 

it:

 temperature at the start

of defrost; 

SEt:

 set point; 

dEF:

 “dEF” message

Fdt

Drip time (not present in the XB350C)

: (0 

÷

 60 min) Time interval between reaching defrost termination

temperature and the restoring of the controllers' normal operation. This time allows the evaporator to eliminate
water drops that might have formed during defrost.

FANS
FnC Fans operating mode during the holding phase

:

C-n

= runs with the compressor, OFF during defrost; 

o-n

 = continuous mode, OFF during defrost; 

C-Y

 = runs

with the compressor, ON during defrost; 

o-Y

 = continuous mode, ON during defrost; 

FSt

Fan stop temperature

: (-50÷50°C/°F; res. 1°C/1°F) if the temperature, detected by the evaporator probe is

above FSt fans are stopped. It serves to avoid blowing warm air around the room.

AFH Differential for the stop temperature and for the alarm 

(0.1 

÷

 25.0 °C; ris.0.1°C/1°F) Fans carry on working

when the temperature reaches the FSt-AFH value, the temperature alarm recovers when the temperature is
AFH degrees below the alarm set.

Fnd Fan delay after defrost:

 (0 

÷

 255 min) The time interval between end of defrost and evaporator fans start.

ALARM
ALU MAXIMUM temperature alarm

: (1 

÷

 50 °C/°F) When the “SET+ALU” temperature is reached  the alarm is

enabled, (possibly after the “Ald” delay time).

ALL Minimum temperature alarm

: (1

÷

50°C/1°F) When the “SET-ALL” temperature is reached  the alarm is

enabled, (possibly after the “Ald” delay time).

ALd Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm condition and alarm

signalling.

EdA Temperature alarm delay at the end of defrost: (

÷

 255 min) Time interval between the detection of the

temperature alarm condition at the end of defrost and alarm signalling.

tbA Silencing alarm relay: 

(Yes= silencing buzzer and alarm relay, no= only buzzer silencing).

OTHER
Ad1 Address 1 for RS485: (

÷

 94)

Ad2 Address 2 for RS485 (

÷

 94)

Lod:

Local display:

 

(rP, EP, iP, nr)

 Select which probe is displayed by the instrument.

 rP:

 Thermostat probe.

EP: 

Evaporator probe. 

iP:

 Insert probe,

 nr: 

During a temperature cycle the insert probe is displayed, during the

holding phase the room probe is displayed. If the cycle is made by time the time remaining is displayed (in
minutes).

rEd

Remote display:

 

(rP, EP, Ip)

 select which probe is displayed by the XR REP.

 rP:

 thermostat probe; 

EP:

evaporator probe; 

iP:

 insert probe.

Loc

Set point of the holding phase lock 

(no - YES) It locks the set point of the holding phase.

Содержание QC 11 Service

Страница 1: ...QC 11 QC 600 Blast Chiller BQCF 40 Chill Freeze Bakery Cabinet ...

Страница 2: ...d operation 5 Cycle Parameter Definitions 5 Cycle Parameter Access 5 QC 11 Cycle Parameters 5 to 6 QC 600 Cycle Parameters 6 BQCF 40 Cycle Parameters 6 to 7 Function Menu 7 to 8 Parameter Access and modification 8 Parameter Settings 8 to 9 Parameter Definitions 9 to 11 Printer Management 11 Alarm Signals 11 Controller Electrical Connections 11 Technical Data 12 Wiring Diagram Numbers 12 ...

Страница 3: ...than 90 minutes and is ideal for chilling meat pies lasagne pasta and individually portioned meals The air temperature for this process goes down to 15 c for the first 70 of the cycle to extract the maximum amount of heat from the product quickly The air temperature then increases to 2 c for the final 30 of the time to reduce surface damage and ensure quality Longer Term Storage Hold Mode Conserva...

Страница 4: ...am Mode Program Type Program Time Air Temperature Chill Temperature Hold Temperature SOFT 90 90 minutes 2 c N A 3 c 70 minutes 15 c HARD 90 20 minutes 2 c N A 3 c HARD 240 240 minutes 15 c N A 3 c 75 15 c 75 6 c HARD 25 3 c 25 2 c 3 c IMPORTANT Please note Program 3 is for specialist markets only and not for normal use Introduction There are four main programmes that you will need to use your Blas...

Страница 5: ...cle press and release the START STOP key for the cycle to continue from the point it was interrupted Alternatively the cycle will restart automatically after the time set in parameter PAU see parameter list on page Stopping the Cycle Press and hold the START STOP until the display shows End the buzzer will sound and the unit will enter the stand by mode LED s and there meanings A series of LED s n...

Страница 6: ... is ended rS2 50 to 50 C 1 C or 1 F Air Temperature Set Point prevents the air temperature going to low during the first phase Pd2 OFF to 4 0 hours 10 minutes Maximum Time For The Second Phase Third Phase iS3 50 to 50 C 1 C or 1 F Food Probe Set Point when the temperature measured by the food probe reaches this value the whole cycle is ended rS2 50 to 50 C 1 C or 1 F Air Temperature Set Point prev...

Страница 7: ...6 ...

Страница 8: ...d2 OFF Pd3 OFF Hard Chill Time For general purpose chilling based on time Cy2 dbC no iS1 15 C iS2 2 C iS3 18 C dbH no rS1 15 C rS2 2 C rS3 30 C HdS 3 C Pd1 1 1hours Pd2 0 2 hours Pd3 OFF Hard Chill This program is for specialist chilling only and is not recommended for normal use Cy3 dbC no iS1 15 C iS2 18C iS3 18 C dbH no rS1 15 C rS2 30 C rS3 15 C HdS 3 C Pd1 4 hours Pd2 OFF Pd3 OFF Hard Chill T...

Страница 9: ...no parameters are present in the menu Pr2 will be displayed Pr2 Installer Parameters Includes all the instrument parameters at installer level It can only be accessed using the security code On entering the parameters it is possible to modify all parameters and add or remove parameters from Pr1 user level by pressing SET UP When a parameter is enabled at user level LED 5 Alarm LED is on Fcy Cycle ...

Страница 10: ...P Evaporator probe presence YES NO YES YES EPO Evaporator probe calibration 0 0 0 0 iPP Insert probe presence YES YES YES YES iPO Insert probe calibration 0 0 0 0 CF Temperature measurement unit C C C C rES Resolution for C IN IN IN IN PAU Time of stand by 1 1 1 1 PFt Maximum acceptable duration of power failure 2 2 2 2 iPd Temperature difference for the automatic recognition of the insert probe 3...

Страница 11: ...ence no YES no not present YES present iPO Insert probe calibration 12 0 12 0 res 0 1 C 1 F CFTemperature measurement unit C Celsius F Fahrenheit rES Resolution for C in integer de with decimal point PAU Time of stand by 0 60min after this time the controller restart the cycle PFt Maximum acceptable duration of power failure 0 250 min if power failure duration is less than PFt the cycle restarts f...

Страница 12: ...perature it temperature at the start of defrost SEt set point dEF dEF message Fdt Drip time not present in the XB350C 0 60 min Time interval between reaching defrost termination temperature and the restoring of the controllers normal operation This time allows the evaporator to eliminate water drops that might have formed during defrost FANS FnC Fans operating mode during the holding phase C n run...

Страница 13: ...gnals Mess Cause Outputs EE Data or memory failure Alarm output ON Other outputs unchanged rPF Thermostat Probe failure Alarm output ON Compressor output according to parameters COn and COF EPF Evaporator Probe failure Alarm output ON Defrost termination is timed No temperature control on fans iPF Insert probe failure Alarm output ON Other outputs unchanged The cycle is made by time rtC Real Time ...

Страница 14: ... Evaporating Temperature 15 C 15 C Refrigerant Control TEV TEV Refrigerant R404a R404a Refrigerant Quantity 1000g TBA Electrical Supply 230 1 50 13amp 230 1 50 13amp Total Heat Rejection 1500w 2080w Wiring Diagram Numbers Model Wiring Diagram Number Fuse Rating QC 11 01 233728 13 Amp QC 600 01 233729 13 Amp BQCsF 40 13 Amp ...

Страница 15: ...QC 11 Wiring Diagram ...

Страница 16: ...2 QC 600 Wiring Diagram ...

Страница 17: ...3 BQCF 40 Wiring Diagram Sheet 1 of 2 ...

Страница 18: ...4 BQCF 40 Wiring Diagram Sheet2 of 2 ...

Страница 19: ...cial fosterfrance com Germany Foster Refrigerator Gmbh Tel 49 2333 839375 Fax 49 2333 839377 Email info foster gmbh de Foster Refrigerator Oldmedow Road Kings Lynn Norfolk PE30 4JU Tel 01553 691122 Fax 01553 691447 Website www fosterrefrigerator co uk Email sales foster uk com a Division of ITW UK Ltd BC11 BC600 SM 08 04 ...

Отзывы: