MICROPROCESSOR CONTROLS

Thermostat Function

SPL 

Min set point (°C)

 

Maximum allowable low alarm setting (°C)

SPh 

Maximum set point (°C)

 

Maximum allowable high alarm setting (°C)

hyS

 

Temperature hysteresis (°K)

coF

 

Compressor minimum off time (mins)

con

 

Compressor minimum on time (mins)

cdc

 

Cooler duty cycle.  Compressor on duration during a ten minute 

cycle e,g. 

cdc

 = 04, 4 min on time, 6 min off time (active only 

under probe fault conditions, 

PF1

)

crS

 

Compressor start delay (secs)

drE 

Time between defrosts (hrs)

dLi 

Defrost termination temperature (°C)

dto 

Defrost termination time (mins). Unused if set to zero

Defrost Function

Alarm Function

ALo

  Low temperature alarm setting (°C)

Ahi

 

High temperature alarm setting (°C)

AdL 

Alarm delay (min)

 

00 

=  Instantaneous audible alarm

         01.120 

=  Duration of delay (min) 

        — 

01 

=  Alarm is disabled

Ain

 

Determines which probe is monitored for alarm functions

 

=  Air probe (prode 1)

 

=  Evaporator probe (probe 2)

 

=  Food probe (probe 3)

Thermal Mass Simulation

oS1

 

Air probe offset (°K)

oS2

 

Evaporator probe offset (°K)

oS3

 

Food probe offset (°K) — where fitted

SiM

 

Controls the thermal mass volume simulated by the controller 

and displayed on the fascia.  The greater the value the greater 

the  resulting  display  slow  down.    The  controlling  function 

remains to operate directly on air temperature.

 

00 

=  Instantaneous air temperature display

         01.200 

=  Thermal mass simulation

Adr

 

Controller peripheral number — only used where controllers 

are networked

drP 

Drain down time (mins)

diS

 

Display during defrost

 

00 

=  Temperature display

        — 

01 

DEF

 is displayed during defrost and until air 

 

 

 

temperature falls below the value setpoint — 

 

 

 

hysteresis.

        

 1.30 (mins) 

dEF 

is  displayed  during  defrost  and  until  the 

set 

 

 

 

time has elapsed after defrosting or until air 

 

 

 

temperature falls below the value se 

 

 

 

hysteresis.

dtY

 

Defrost type

 

FAn 

=  Off cycle defrost

         

ELE 

=  Electric heater defrost

        

   GAS 

=  Hot gas defrost

doP

  Defrost optimisation

 

con 

=  At regular intervals of 

drE

 (hrs)

         

Acc 

=  Defrost  timer  only  runs  while  evaporator 

temperature is below 0°C, defrosting occurs when 

drE

 time 

has elapsed e.g. if compressor cycle time is 5 min run and 5 

min stop and 

drE

 = 4, defrosting will take place every 8 hours 

Evaporator Fan Control

Fct

 

Evaporator fan control during cooling

        — 

01 

=  Continuous operation

       

00 

=  Cycle on/off with compressor

      

1.10 (mins) 

=  Start with compressor, set time delay stop 

 

 

 

after compressor

Frs

 

Fan delay temperature following defrost (°C)

Fid

 

Evaporator fan operation during defrost

 

00 

=  off until fan delay temperature 

FrS

 (°C) 

 

 

 

is reached

         01 

=  On while evaporator temperature is below 

 

 

 

value 

FrS

 (°C) 

         

02 

=  On during defrost

Duet ‘M’ and ‘L’ Series

All controller parameters are factory set for optimum storage conditions.  

The parameters should only be adjusted by persons familiar with the 

unit operation and controller functions.  Certain parameters however 

may be adjusted within limits, to suit certain storage needs.

1

5

6

3

4

7

2

Check Set Point —

 Low point of temperature band

Press button 1  

Increase Set Point

Press and hold button 1  
Press button 3  

 until required temperature is displayed

Decrease set point

Press and hold button 1  
Press button 4 

 until required temperature is displayed

Manual Defrost

Press and hold button 2  
Press button 4 

 a timed defrost will follow

Indicators

LED 5 Compressor on 

 

LED 6 Evaporator fan on 
LED 7 Defrost on 
PF1 or PF2: Indicates a probe failure — call engineer

Adjustment Parameters

Freezer: Set Point -21°C

Meat:     Set Point -2°C

Control Panel

The control panel contains a microprocessor temperature controller indicator automatically controlling the required process to maintain the correct 

storage temperature within the coldroom and initiate and control defrost and evaporator fan functions.

The  controllers  are  pre-set  prior  to  leaving  the  factory  but  should  it  be  necessary  to  make  an  adjustment  the  following  procedures  should  be 

followed.

MICROPROCESSOR CONTROLS

Duet ‘H’ Series

All controller parameters are factory set for optimum storage conditions.  The parameters should only be adjusted by persons familiar with the unit 

operation and controller functions.  Certain parameters however may be adjusted within limits, to suit certain storage needs.

DUET HIGH TEMPERATURE UNITS WITH LDU 15 CONTROLLER – 00-555357

Temperature Controller

When the controller is switched on a single line appears on the display for 3 seconds to indicate the autotest period.

After this period the air temperature measured by the T1 probe is displayed.

It is strongly advised that before adjusting any Service Parameters a thorough understanding of the following instructions should be obtained.

LDU 15 CONTROLLER

lae

aux

Check temperature set point. 

Check set point by pressing the “set” button

To increase set point press “set” +   

To decrease set point press “set” +  

Factory Temperature Set Point +3°C.

Exit from set up occurs after 10 seconds if no button is pressed.

Controller Set Up.

The parameters are accessed by pressing the following keys in succession                  + “set” +                 and keeping them pressed for 3 seconds. 

Access to the parameters has been achieved with the first parameter SCL being displayed. 

To pass from one parameter to the next press either the                  or                  key

To display the value press. “set”

To change the value press “set” +                  to increase, or  “set” +                 to decrease.

Exit from set up by pressing “aux” or is automatic after 30 seconds if no buttons are pressed.

set

aux

8

9

CDC 122

Содержание FKS 10-4

Страница 1: ...T e c h n i c a l M a n u a l Duet Condensing Unit Cooler ...

Страница 2: ...al management Product Support and Installation contractors are required to 1 Ensure that wherever possible waste is removed from the client s site where arrangements are in place all waste should be retumed to Foster Refrigerator s premises In certain circumstances waste may be disposed of on the clients site if permission is given if the client has arrangements in place for the type of waste 2 If...

Страница 3: ...defrost heaters FKS Range with and without defrost heaters Control Panel Microprocessor Controller c w function indicators Ten metre sensing probes Component contactors Component circuit breakers Not included Interconnecting pipework Pipe installation Mechanical fasteners screws pipe clamps etc Refrigerant Mains supply wiring Lockable isolator switch White enclosure Remote alarm contacts Ancillari...

Страница 4: ...4 Cooler Specification ...

Страница 5: ... 50 3 2 6 2 9 7 27 20 1 x 400 3100 1 x 160 64 102 595 x 1075 x 532 10 22 DCU1 1L 0 75 R 404a 1 50 1 6 28 0 2 230 1 50 0 8 3 8 7 28 16 1 x 250 750 1 x 90 60 46 368 x 660 x 330 10 16 DCU2 1L 1 8 R 404a 1 60 2 5 28 0 2 230 1 50 1 4 8 6 16 40 20 1 x 300 1400 1 x 90 60 60 458 x 880 x 400 10 22 DCU3 3L 2 3 R 404a 1 60 2 5 28 0 2 400 3 50 1 8 4 5 6 2 25 16 1 x 300 1400 1 x 90 61 65 458 x 880 x 400 10 22 ...

Страница 6: ...FKS Cooler Dimensions 6 ...

Страница 7: ... pipe size should be determined by application Recommended maximum vertical change 5 metres The suction lines have been selected to achieve a pressure drop of 2psi or less whilst maintaining refrigerant velocity in the horizontal plane of 3 5m s 700ft min and in the vertical plane of 7 0m s 1500ft min to achieve oil return Model 43 C Ambient Liquid Line Pipe Size Suction Line Pipe Size Horizontal ...

Страница 8: ... a single line appears on the display for 3 seconds to indicate the autotest period After this period the air temperature measured by the T1 probe is displayed It is strongly advised that before adjusting any Service Parameters a thorough understanding of the following instructions should be obtained LDU 15 CONTROLLER lae aux Check temperature set point Check set point by pressing the set button T...

Страница 9: ...is 1 30 mins dEF is displayed during defrost and until the set time has elapsed after defrosting or until air temperature falls below the value setpoint hysteresis dtY Defrost type FAn Off cycle defrost ELE Electric heater defrost GAS Hot gas defrost doP Defrost optimisation con At regular intervals of drE hrs Acc Defrost timer only runs while evaporator temperature is below 0 C defrosting occurs ...

Страница 10: ...lternate between ALM and air temperature while the alarm condition persists Display Parameter LDU151E B Duet High Temp Default Values Used in Panels F H L SCL Readout Scale 2 C 2 C SPL Minimum Temperature Set Point 05 0 SPH Maximum Temperature Set Point 01 8 SP Effective Temperature Set Point 03 2 HYS Hysteresis 3 3 CRT Compressor Rest Time minutes 10 2 CDC Compressor Regulation with T1 Fail 20 7 ...

Страница 11: ... 23 24 25 26 DUET C F M L AND IC SERIES 00 OFF 01 Te FrS 02 Always ON Units Deg Deg Deg Min Min Sec Hrs Deg Min Min Min Flag Flag Min Deg Flag Deg Deg Min Flag Deg Deg Deg Flag 01 Mnemonic SPL SPh hYS coF con cdc crS drE dLi dto drP diS dtY doP Fct FrS Fid ALo Ahi AdL Ain oS1 oS2 oS3 SiM Adr Min Limit 50 SPL 01 00 00 00 00 01 01 00 00 01 FAn con 01 50 00 50 SPh 01 01 20 20 20 00 1 ELE 00 01 00 02 ...

Страница 12: ...Cables for three phase supply Condensing Unit Unit Cooler Liq Line Solenoid 1mm2 3 core Evaporator Fan 1mm2 3 core Defrost Heater if fitted 1mm2 5 core Drain Line Heater 1mm2 3 core Wiring Diagram 00 838359 00 00 838362 00 See page 11 for model reference Compressor Fan 2 5mm2 5 core Supply In 230v 50 1 N Control Panel HP LP Switch 1mm2 3 core Optional Condenser Fan Pressure Switch Crankcase Heater ...

Страница 13: ... of an oil separator should be considered especially on low temperature applications plus the position of the oil P trap and the size of the suction line to maximise oil return to the compressor 4 EVAPORATORS COOLERS FTG Range Ceiling Mounted These are used for small coldroom applications and are available for both high and low temperature conditions The low temperature models have defrost heaters...

Страница 14: ...r Oldmedow Road King s Lynn Norfolk PE30 4JU England Tel 01553 691122 Fax 01553 691447 Website www fosterrefrigerator co uk E mail sales foster uk com a Division of ITW UK Ltd DUET TM 05 05 T e c h n i c a l M a n u a l ...

Отзывы: