english
GB
Figure 28
4
Figure 27
Detail shows positions of 2 of the
screw hole positions, the 3rd is
not shown
Door Jamb
Fitting
Select the door jamb without the door, apply
mastic to the edge of the floor, top of the 'L'
shaped section and the left hand side of the jamb
(see fig 5 and 7) as described previously, and fit
and lock into place (see fig 25).
STEP 10.
Threshold Plate
The threshold plate is the stainless steel portion of
the door jamb and requires fixing to the cold-
room floor (see fig 27). With the jamb locked into
position, using the .42mm drill bit, drill three
holes in the coldroom floor through the pre-
drilled holes in the threshold plate.
Using the zinc platted countersunk screws cut a
thread in the drilled holes, remove and discard.
Insert the flat headed stainless screws into the
threaded holes taking care not to over tighten.
STEP 12.
Door Fitting
Offer the door up to the door jamb, whilst hold-
ing it at a 90˚ angle to the jamb lower the door
so that both portions of the hinge assembly join
together. Once in position allow the door to
close. If the door does not close lift the door off
the hinges and check that the cam is located cor-
rectly on both portions of the hinge assembly. If
required make the necessary adjustments and re-
fit the door.
The door should close with the handle coming
into contact with the strike and hold the door
firmly against the jamb creating a positive seal
with the gasket. If there is movement of the door
when in the closed position adjust the strike posi-
tion using a pozi screwdriver.
STEP 13.
Sealing Joints
Seal all external joints with silicone sealer (see fig 28)
taking care not to overfill.
STEP 14.
Cleaning
The finished coldroom should be cleaned thoroughly
before loading.
STEP 15.
Figure 20
Capping Lock
Holes
Capping lock holes in walls and ceiling.
Insert the white plastic caps provided and tap in
using the shaft of a hammer ensuring they are
tight and flush fitting.
Capping lock holes Floors
To ensure an adequate fixing the lock hole plugs
for the floor are provided as a two part
component (see fig 20).
Insert the outer body into the hole and tap the
central pin in with a light hammer.
STEP 8.
Shelving
Assembly
A.
Remove all packaging from the shelves
and posts..
B.
Determine the position of the lowest shelf
(it is recommended that at least a 150mm
clearance from the floor is left to allow for
cleaning).
C.
Snap on one half (see
fig 23) of the plastic col-
lar onto the post (with
the thick end down).
Snap on the remaining
half of the collar and
slide up or down until
secured into the groove.
Repeat this for all four
posts.
D.
Standing the shelf
poles upright, lower the shelf onto the poles
until the collars fit inside the corner of the
shelves (see fig 24).
E.
With the shelf in position use a rubber
mallet to 'knock down' the shelf until it is
completely secured.
F.
Repeat steps B, C, D
& E for the remaining
shelves.
G.
The foot of each
pole can be adjusted to
compensate for uneven
surfaces.
NOTE: Assemble the first set of racking out
of the coldroom and place inside (see fig 21).
For rooms FPC 1.8 x 1.2, FPC 1.8 x 1.5 and FPC
1.8 x 1.8 the second and subsequent racks
will have to be assembled inside the room
(see fig 22).
For all of the remaining models the racking
can be assembled and placed inside when
assembled.
STEP 9.
Figure 23
Figure 21
Figure 25
Figure 26
Figure 22
Figure 24
Front Right
Hand Corner
Select the front right hand corner (see fig 26),
apply mastic to the edge of the floor, both sides
and the top of the ‘L’ shaped section of the corner
(see fig 5 and 7) as described previously, and lock
the corner into place.
STEP 11.
Before proceeding further assemble
the racking and position inside the
coldroom. Refer to the ‘Shelving
Arrangement’ on the separate sheet
for the shelving layout for your
particular coldroom.