Service Level Parameters

M

nemomic

Description

MDL

Do not adjust

SPL

Minimum limit for SetPoint 
setting

SPH

Maximum limit for SetPoint 
setting

SP

Setpoint

 Temperature value to be maintained in the product

HY0

Thermostat OFF -> ON 
differential

 In Cooling Mode - ‘MDL’ = ‘HYS’

HY1

Do not adjust

CMD

Compressor start delay ‘run’ 
mode

The time between mains power being applied and the compressor starting when in ‘run’ 
mode (i.e. following a mains power cut)

CRT

Compressor rest time

Minimum time compressor is switched off following cycle operation (i.e. pull down, hot 
gas defrost)

CT1 Compressor output on time

Followed by ‘CT2’ when probe Ta (T1) is faulty

CT2 Compressor output off time

Followed by ‘CT1’ when probe Ta (T1) is faulty

PB

Do not adjust

IT

Do not adjust

DT

Do not adjust

CT

Do not adjust

AR

Do not adjust

CMS

Do not adjust

CRS

Do not adjust

CRD

Do not adjust

CDS

Do not adjust

CFF

Do not adjust

CSS

Do not adjust

CSO

Do not adjust

CST

Do not adjust

DFM

Defrost start mode
Defrost start mode

‘NON’ - defrost function is disabled - no defrosts will occur

‘TIM’ - Time. Defrosting occurs on a time base determined by ‘DFT’, accumulated only in 
run mode

‘FRO’ - Do not use

‘DoD’  - Do not use

‘TAD’ - Do not use

DFT

Time interval between defrosts When this time has elapsed since the previous defrost (in run mode), a new defrost cycle 

is initiated

DSP

Do not adjust

DST

Do not adjust

DMI

Do not adjust

DLI

Defrost end temperature

DTO Maximum defrost duration

DTY

Defrost type

‘OFF’ - Off cycle defrost (Compressor and Heater OFF)

‘ELE’ - Electric defrost (Compressor OFF and Heater ON)

‘GAS ‘ - Hot gas defrost (Compressor and Heater ON)

DSY

Defrost start synchronization

‘OFF’ - none. The defrost will occur without delay

‘LO’ - defrost start will be postponed to compressor cut-out (SOD = max delay)

HI’ - defrost start will be postponed to compressor cut-in (SOD = max delay)

SOD

Do not adjust

DPD

Evaporator pump down

At the beginning of defrost, defrost outputs (determined by ‘DTY’) are ‘OFF’ for ‘DPD’ 
seconds

DRN

Pause after defrost (evaporator 
drain down time)

DDM

Defrost display mode.

RT’ - the real / actual temperature

LT’ - the last temperature displayed before defrost initiation

SP’ - the setpoint value

dEF’ - ‘dEF’

Service Level Menu

To access service level menu, press button 3 then press and hold buttons 2 and 4 for 5 seconds and the display will show ‘MDL’.  Press button 3  to 

display the current value.  If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value.

Содержание ECORPO G3 EP1440G

Страница 1: ...Service Manual EP700H EP700M EP700L EP700G EP700F EP700SH EP700SL EP700P EP1440H EP1440M EP1440L EP1440G EP700HH EP700HL EP700LL EP700H2 EP700L2 EP700LL Cabinets...

Страница 2: ...your appliance Service Function Parameters Alarm Indicators Probe Data Relay Test Factory Reset Wiring Diagrams Maintenance Welcome to your interactive Foster service manual Here s how it works To re...

Страница 3: ...ce should be located on a flat level surface correctly loaded Do not use mechanical devices to accelerate the defrost process Care should be taken not to damage the refrigeration circuit and or system...

Страница 4: ...liance produces warm air when operating normally and requires adequate ventilation The dimensions indicated are a minimum As the operating temperature has been pre set no adjustments are required Allo...

Страница 5: ...ernal temperature and button 3 Icon Button 1 Compressor running 1 Information menu 2 Keypad locked 2 Increase value 3 Evaporator fans running 3 Standby Exit Confirm 4 Defrost in progress 4 Decrease va...

Страница 6: ...nd the shelf above Do not place product on the base of the appliance If it is required to store product on the base of the appliance please contact the Foster parts team to purchase the necessary shel...

Страница 7: ...e If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value User Level Parameters Mnemonic Description SP Appliance Set Point Loc Keypad Lock tA Actual air pr...

Страница 8: ...DFT accumulated only in run mode FRO Do not use DoD Do not use TAD Do not use DFT Time interval between defrosts When this time has elapsed since the previous defrost in run mode a new defrost cycle i...

Страница 9: ...essor stop FT2 Timed fan stop When FT2 0 the fans remain on all the time FT3 Timed fan run When FT3 0 and FT2 0 the fans remain OFF all the time ATM Alarm threshold management NON all temperature alar...

Страница 10: ...ler R1 Do not use R1F Do not use R1 Do not use FAN Output enabled for evaporator fan switching FAN Do not use DEF Output enabled for defrost switching DEF Do not use ALO Contacts open when an alarm co...

Страница 11: ...ed rate of change toward setpoint actual value away from setpoint mathematical algorithm applied A E the AVG weighted average between TAir T1 and TEvaporator T2 probes T3 TAuxiliary T3 probe value whe...

Страница 12: ...60 60 0 0 0 0 0 CT1 4 4 4 4 5 5 4 4 5 4 4 5 5 4 5 4 4 5 CT2 7 6 6 7 5 5 7 6 5 6 7 5 5 6 5 6 6 5 PB 7 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 IT 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1...

Страница 13: ...0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FT2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FT3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ATM REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL ALA 30 30 30 3...

Страница 14: ...R DOR DOR NON NON DOR DOR DOR OS3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D3A OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN AHM NON NON NON NON NON NON NON NON NON NON NON NON NO...

Страница 15: ...the bottom edge of the front cover If the cover is hinged up or removed for access purposes the door switch will not function and the door open alarm will be displayed tA Air probe has failed Call you...

Страница 16: ...522 113 347 117 294 25 84 823 87 559 90 374 20 66 27 68 237 70 255 15 52 229 53 65 55 104 10 41 477 42 506 43 557 5 33 147 33 892 34 651 0 26 678 27 219 27 767 5 21 63 22 021 22 417 10 17 643 17 926...

Страница 17: ...ve at all other times subject to the parameter FCM Door Switch The appliance is fitted with a magnetic door switch located in the underside of the front cover Where the door switch is open and followi...

Страница 18: ...parameter DTO or the temperature set in parameter DLI is reached Where parameter TE is set to NO defrost will function on a time basis only Upon completion of the defrost cycle the appliance will resu...

Страница 19: ...skets Door gaskets should be inspected periodically and cleaned where necessary with a warm damp cloth Do not use aggressive cleaning materials on the door gaskets Where door gaskets are damaged or no...

Страница 20: ...20 www fosterrefrigerator com Wiring Diagrams EP700H Integral Condensing Unit...

Страница 21: ...21 G3 Cabinets Service Manual EP700H Remote Condensing Unit...

Страница 22: ...22 www fosterrefrigerator com EP700G Integral Condensing Unit...

Страница 23: ...23 G3 Cabinets Service Manual EP700G Remote Condensing Unit...

Страница 24: ...24 www fosterrefrigerator com EP700P Integral Condensing Unit...

Страница 25: ...25 G3 Cabinets Service Manual EP700P Glass Door Integral Condensing Unit...

Страница 26: ...26 www fosterrefrigerator com EP700F Integral Condensing Unit...

Страница 27: ...27 G3 Cabinets Service Manual EP700F Remote Condensing Unit...

Страница 28: ...28 www fosterrefrigerator com EP700M EP700L Integral Condensing Unit...

Страница 29: ...29 G3 Cabinets Service Manual EP700M EP700L Remote Condensing Unit...

Страница 30: ...30 www fosterrefrigerator com EP700HH Integral Condensing Unit...

Страница 31: ...31 G3 Cabinets Service Manual EP700HH Remote Condensing Unit...

Страница 32: ...32 www fosterrefrigerator com EP700HL Integral Condensing Unit...

Страница 33: ...33 G3 Cabinets Service Manual EP700HL Remote Condensing Unit...

Страница 34: ...34 www fosterrefrigerator com EP700LL Integral Condensing Unit...

Страница 35: ...35 G3 Cabinets Service Manual EP700LL Remote Condensing Unit...

Страница 36: ...36 www fosterrefrigerator com EP820HU Integral Condensing Unit...

Страница 37: ...37 G3 Cabinets Service Manual EP1440H Integral Condensing Unit...

Страница 38: ...38 www fosterrefrigerator com EP1440H Remote Condensing Unit...

Страница 39: ...39 G3 Cabinets Service Manual EP1440G Integral Condensing Unit...

Страница 40: ...40 www fosterrefrigerator com EP1440G Remote Condensing Unit...

Страница 41: ...41 G3 Cabinets Service Manual EP1440M EP1440L Integral Condensing Unit...

Страница 42: ...42 www fosterrefrigerator com EP1440M EP1440L Remote Condensing Unit...

Страница 43: ...43 G3 Cabinets Service Manual...

Страница 44: ...sterrefrigerator com Document ID code 00 570505 v1 By Appointment to Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator King s Lynn For service and spares For ser...

Отзывы: