Breaker specification of AC input in single phase
Communication connection
Battery capacity (recommended)
Note 1:
Also, you can use a 16A breaker for the 1KW model, 32A for the 2KW model and a 48A for the 3KW model with
only 1 unit, and install one breaker at the AC input of each inverter.
Note 2:
Regarding the three-phase system, you can use a 4-pole breaker directly. When choosing a breaker, the current
rating of the breaker must be greater than or equal to the maximum current of each phase of the inverter.
7.3. Parallel connections on a single-phase system
Two inverters in parallel:
Power connection
WARNING!
Make sure all inverters share the same battery bank. Otherwise, the inverters will go into fault mode.
Model
2 units
3 units
4 units
5 units
6 units
7 units
8 units
9 units
1KW
32A
48A
64A
80A
96A
112A
128A
144A
2KW
64A
96A
128A
160A
192A
224A
256A
288A
3KW
96A
144A
192A
240A
288A
336A
384A
432A
Number of parallel
inverters
2
3
4
5
6
7
8
9
Battery capacity
400Ah
600Ah
800Ah
1000Ah
1200Ah
1400Ah
1600Ah
1800Ah