background image

Setting
CF ENA: converter mode enabled
CF DIS: converter mode disabled

Setting
ENA: ECO mode enabled
DIS: ECO mode disabled

Setting
The initial frequency may be set on battery 
mode:
BAT 50: current output frequency is 50Hz
BAT 60: current output frequency is 60Hz
If the converter mode is enabled, you may 
choose the following output frequency:
CF 50: current output frequency is 50Hz 
CF 60: current output frequency is 60Hz

Setting
Press the Down key or Up key to set the 
acceptable high voltage point and acceptable 
low voltage point:
HLS: High loss voltage in ECO mode (For 
208/220/230/240 VAC models, the setting 
range is from +7V to -24V of the nominal 
voltage. For 110/115/120/127 VAC models, 
the setting range is from +3V to -12V of the 
nominal voltage). LLS: Low loss voltage 
in ECO mode (For 208/220/230/240 VAC 
models, the setting range is from -7V to -24V 
of the nominal voltage. For 110/115/120/127 
VAC models, the setting voltage is from +3V 
to -12V of the nominal voltage)

02: Frequency Converter enable/disable Interface

03: Output frequency setting Interface

04: ECO enable/disable Interface

05: ECO voltage range setting Interface

Содержание Atlas 2-3KVA

Страница 1: ...2 Y e a r W a r r a n t y Atlas 2 3KVA Model Power Inverter UPS System Service Manual...

Страница 2: ...nce there is dangerous voltage at several points in this product Turn off the UPS and disconnect the input power cable before removing the external protective cover AC voltage may be present when AC p...

Страница 3: ...that that there is input power available before re connecting the battery connectors After servicing the UPS and before restarting it perform a polarity test on the batteries and make sure the screws...

Страница 4: ...Step 2 Step 3...

Страница 5: ...y have encountered Due to the unique features of this UPS series Uninterruptible Power System this unit is very easy to maintain and service The PBC has all the major power components All PCBs are int...

Страница 6: ...ow the entire system works Picture 1 shows how the major circuits are connected and how the entire system works Picture 1 Circuit connection for 2 3KVA Includes 1 a charger 2 a DC power supply 3 a pow...

Страница 7: ...The location of the assemblies in the machine are shown in picture 2 The location of the assemblies in the machine are shown in picture 2...

Страница 8: ...ply is transferred immediately from the inverter to the AC mains by a bypass relay This operation will be explained in another section This ON LINE UPS system resorts to high frequency PWM techniques...

Страница 9: ...cuits The purpose of the charger is to provide power to keep the batteries full Refer to picture 4 The voltage flyback switching power supply delivers a constant DC voltage 83 8 VDC to the batteries A...

Страница 10: ...the level of the input current is less than 1 as shown in picture 7 The primary role of a UPS is to deliver accurate AC power to the loads connected to it whether the AC line exists or not The batteri...

Страница 11: ...that the UPS is delivering constant AC voltage to the loads When the main is applied and the switch is turned on a 10 second timer is triggered The bypass relay stays at bypass position in this time...

Страница 12: ...ected or an abnormal inverter operation occurs 2 Battery over or under shut down 3 Inverter output abnormal protection 4 Over temperature protection 5 Bus over under unbalance voltage protection When...

Страница 13: ...ed and the buzzer will beep every 1 second Remote shutdown signal is enabled only when the line fails The front panel consists 2 parts push button and display LCD set The push button is used to turn o...

Страница 14: ...ing mode Switching the LCD messages Press this button to display the following messages showing values related to input voltage input frequency battery voltage output voltage and output frequency The...

Страница 15: ...ity Press ON button for 2 seconds to turn EUT on Waiting for 10 seconds to make sure the EUT work in line mode according to the LCD display Check reading on DVM 360VDC 10V DC Bus Voltage Baterry Mode...

Страница 16: ...If the panel LCD light and fan rotates If the panel LCD display normally If I P relay continuouly open and close If D C start works properly Change CNTL SUB ASSY If DC start works properly DC DC fail...

Страница 17: ...ry level indicator at 0 25 26 50 51 75 and 76 100 of its capacity Battery fault indicator Low battery level and low voltage indicator Input voltage or frequency or battery voltage indicator VAC Input...

Страница 18: ...disable ECO voltage range setting Bypass enable disable Bypass voltage range setting programmable outlets enable disable programmable outlets setting and exit Setting For 208 220 230 240 VAC models y...

Страница 19: ...et the acceptable high voltage point and acceptable low voltage point HLS High loss voltage in ECO mode For 208 220 230 240 VAC models the setting range is from 7V to 24V of the nominal voltage For 11...

Страница 20: ...e low voltage point HLS Bypass high voltage point LLS Bypass low voltage point For 208 220 230 240 VAC models 230 264 setting the high voltage point from 220Vac to 264Vac 170 220 setting the low volta...

Страница 21: ...still charge battery under this mode When the input voltage is beyond the acceptable range or when power is failing the alarm will beep every 4 seconds and the battery will start supplying power to th...

Страница 22: ...nd Beeping every second Fault event Inverter voltage Low Inverter output short Battery voltage too high Battery voltage too low Over temperature Over load Fault code 01 02 03 04 11 12 Icon flashing Al...

Страница 23: ...ecked components Instrument function Reference Value Failed condition 1 2 3 F1 F2 F3 Q14 Q13 Q7 Q8 D S R64 R85 R90 R91 DIODE short 0 47 47 open short or open open Step Checked components Instrument fu...

Страница 24: ...have not been found When everything seems to be working turn off the switch on the panel and remove the DC power supply Plug in the power cord and supply the UPS with the mains Test the output of the...

Страница 25: ...75 VAC 5 Full Load 300 VAC 5 285 VAC 5 110 VAC to 300 VAC 2 2000 3000 8A 11A 3 5 mA maximum UPS only 0 95 40 Hz to 70 Hz circuit protector O P Power Power VA Power Watts Output Power Factor Rating Loa...

Страница 26: ...ion is indicated in illustration VI 1 Note that the computer will control information exchange by a query followed by cr Character Return UPS will respond with information followed by a cr or action U...

Отзывы: