2.3    PULSE OUTPUT 

The PM834 meter is equipped with a pulse output which is fully separated from 

the inside circuit. That generates pulses in proportion to the measured 
energy .include the testing pulse output of active energy and reactive energy. 8/ 
12 Test pulse output contact (P+/P-)

9/ 12 Test pulse output contact (Q+/Q-)   

The test pulse output is a polarity dependant, passive transistor output requiring 
an external voltage source for correct operation. For this external voltage source, 
the  voltage  (U)  should  be  5-27V  DC,  and  the  maximum  input  current  (Imax) 
should  be  27mA  DC.  To  connect  the  impulse  output,  connect  5-27V  DC  to 
connector 8&9 (anode), and the signal wire (S) to connector 12 (cathode). The 
meter pulses is indicated on the front panel. 
 

 

2.5    BUTTON 

The PM834 transformer connected meter has 2 buttons, which are used to set the 
current transformer ratio 

 
2.6    CT RATIO 

There are 27 ratios to be chosen to set the current transformer ratio. 
Please set the Secondary CT ratio after installation otherwise the CT Meter will 

count the Secondary energy consumption by default Ratio (5:5).   

Procedures of setting the CT of the CT Meter: 
2.6.1    Press  the  PRG  button  after  auto-detect,  then  you  can  set  the  CT 

changing- ratio. The LCD shows   

 

 
2.6.2    Press the SEL button, and there are 27 Ratios (“5:5” to “7500: 5” ) you 

can choose from. 

Example Secondary CT ration is 75:5   
 

Содержание PM834

Страница 1: ...975591 60975593 1 Panel Meter User Manual PM834 Power Control Electricity Monitoring System Power Safe Programmable Management Relay Forlong Power Intelligent Power Meter Mini Power Mini Power Energy...

Страница 2: ...Therefore it must be insured that the terminals are not touched during operation When installing the PM834 all voltages must be switched off 2 PRODUCT DESCRIPTION This chapter contains a description...

Страница 3: ...display it is possible to view information the energy consumption and various status information The display has 7 characters of 7 segment type with a height of 6 mm and a number of other specific seg...

Страница 4: ...voltage source the voltage U should be 5 27V DC and the maximum input current Imax should be 27mA DC To connect the impulse output connect 5 27V DC to connector 8 9 anode and the signal wire S to con...

Страница 5: ...after 60 seconds set up the CT will be forbidden If forget to close the switch of program meter will close the program operation automatically after 60mins the disappear on LCD NOTE In the sense of s...

Страница 6: ...data Power supply 65 to 275 Volts AC Universal AC DC Supply Frequency Hz 50 60Hz Frequency range 5 Temperature Operating 10 to 65 Storage 25 to 70 Humidity 75 RH Non Condensing Environment IP54 stand...

Страница 7: ...____ www china meters com Email sale01 china meters com 86 021 60975591 60975593 7 voltage 5 27V DC Connection area main terminals Flexible 1 mm2 0 2 5 Solide 1 mm2 0 2 5 LED Pulse wide 80ms 20ms Puls...

Страница 8: ...ified environmental conditions If degradation in the accuracy is observed the meter has probably been partly damaged for example due to lightning strike or extreme environmental conditions etc and sho...

Страница 9: ...0086 21 60975593 E mail sale01 china meters com Website www china meters com CAUTION During reparation and maintenance do not touch the meters connecting clamps directly with your bare hands with meta...

Отзывы: