Problem
Check
Solution
The LCD energy
register can’t run.
Is the load
running ?
Is the operating
power too low ?
Maybe there is a
fault in the inside
circuit.
Only when load is running, RED
LED is burning continue, the LCD
energy register will run.
If the operating power is too low,
the spacing interval of the pulses
will take some more time. This is
why it seems like the LCD energy
register can’t run
Please contact your technical
supporter to replace this meter.
No pulse output.
Is DC power supply
connected to the
meter ?
Is the connecting
correct ?
Maybe there is a
fault in the inside
circuit.
Check the external voltage source
(Ui) is 5-27V DC.
Check correct connecting:
Connect 5-27V DC to connector 3
(anode), and the signal wire (S)
to connector 2 (cathode).
Please contact your technical
supporter to replace this meter.
Pulse output rate
wrong.
Maybe there is a
fault in the inside
circuit.
Please connect with technical
supporter to replace this meter.