![Fonrich FR-DCMG Series Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/fonrich/fr-dcmg-series/fr-dcmg-series_user-manual_2315910032.webp)
0xXX1B
Current of channel 20 of the
wireless node
Short
Unit mA,symbol means direction
R
System information
0x00F7
The supported wireless
node number by gateway
Unsigned
short
The support max number of
wireless node, only available in
gateway mode.
R
0x00F8
The online number of the
wireless node
Unsigned
short
The online wireless node number
only available in gateway mode
R
0xFF0A
FMB current direction
configure register1
Unsigned
short
Bit0: the current direction of
channel 1
bit1 the current direction of
channel 2
…
bit15 the current direction of
channel 16
0: positive direction,1 negative
direction
WR
0xFF0B
FMB current direction
configure register2
Unsigned
short
Bit0: the current direction of
channel 17
bit1: the current direction of
channel 18
…
bit7: the current direction of
channel 24
0: positive direction,1 negative
direction
WR
0xFF0C
Temperature too high alarm
Unsigned
short
Bit0 :on board temperature too
high alarm
bit1 : external temperature too
high alarm
0: normal,1: alarm
R
0xFF0D
Voltage alarm
Unsigned
short
Bit0 :voltage too high alarm
bit1 :voltage too low alarm
0: normal,1: alarm
R
0xFF0E
Current alarm1
Unsigned
short
bit0-bit2: channel 1,no current ,
current low,current high alarm
bit3-bit5:channel 2,no current ,
current low,current high alarm
bit6-bit8 :channel 3,no current ,
current low,current high alarm
bit9-bit11: channel 4,no current
R