30
Register description in word unit (function code 03 04 06)
Modbus address
Function description
Data Type
instruction
R/W
Hex
Decimal
Address 0x0100
~
0x0158, a total of 89 consecutive addresses
Address 0x0100
~
0x0123, a total of 36 consecutive addresses (data in this address supports data freeze)
0x0100
256
Retain
0x0101
257
Retain
0x0102
258
Retain
0x0103
259
Retain
0x0104
260
bus voltage
Unsigned
short
Unit V, default 0
R
0x0105
261
Temperature sensor 1
short
Unit: 0.1 ° C, default -424
R
0x0106
262
Temperature sensor 2
short
Unit: 0.1 ° C, default -424
R
0x0107
263
Switch input
Unsigned
short
bit0: DI1, bit1: DI2,
bit2: DI3, bit3: DI4
0: open, 1: closed, default 0
R
0x0108
264
Quantity of online Hall
channels
Unsigned
short
Shows the quantity of Hall channels currently
connected. default 0
R
0x0109
265
Total reverse current
short
Unit is 10mA, default is 0
R
0x010A
266
Total current
Short
Unit is 10mA, default is 0,
R
0x010B
267
Average current
Short
Unit mA, default 0,The unit is 10mA when
using a large range Hall
0x010C
~
0x0123
268
~
291
Channel 1 to 24 current
Short
Unit mA, default 0
R
Address 0x012A
~
0x0158, a total of 45 addresses (function code 04 read, but the data is not latched)
0x012A
298
Shunt trip status 1
Unsigned
s
hort
Bit0 bus arc, trip code is (01)
Bit1 channel arc, (02)
Bit3 overvoltage, (04)
bit4 high temperature 1, (05)
bit5 high temperature 2, (06)
bit6 channel current value is reversed, (07)
bit7 reverse total current is high, (08)
bit9 the total current is high, (10)
bit10 channel current value is zero, (11)
bit11 channel current value is undercurrent,
(12)
bit12 channel current value is overcurrent,
(13)
bit13 channel current value is low, (14)
bit14 channel current value is high, (15)
R
0x012B
299
Shunt trip status 2
Unsigned
short
Bit0 DI1
,
(17)
bit1 DI2
,
(18)
bit2 DI3
,
(19)
bit3 DI4
,
(20)
bit14
:
Being tripped remotely,(31)
0
:
No tripping
,
1
:
Already tripped, default 0
R
0x012C
300
Shunt trip status 3
Unsigned
short
Bit15: Total trip status (not open)
0: no trip, 1: tripped, default 0
0x012D
301
Alarm status 1
Unsigned
short
Bit0 bus arc,
bit1 channel arc,
bit2 low voltage,
bit3 high voltage,
bit4 high temperature 1,
bit5 high temperature 2,
bit6 channel current value is reversed
bit7 reverse total current is high,
bit8 total current is low,
bit9 total current is high,
bit10 channel current value is zero,
bit11 channel current value undercurrent
bit12 channel current value overcurrent
R