background image

89

–With  the  domestic  hot  water  potentio-

meter  knob  on  maximum,  the  domestic

hot  water  tap  open  and  the  burner  igni-

ted,  turn  the  screw  (2)  keeping  locked

the nut (3) to achieve the minimum pres-

sure value given in 

Table 4

: to reduce the

p r e s s u r e ,   t u r n   t h e   s c r e w   c o u n t e r -

clockwise; to increase the pressure, turn

it clockwise.

– Operate  the  main  switch  a  number  of

times, keeping the D.H.W. tap open all the

time,  and  check  that  the  pressure  corre-

sponds to the values given in 

Table 4

.

–Restore electric power to the modulator.

–Replace the plastic cap (1) in position.

4.3.3

Maximum pressure adjustment

valve HONEYWELL 

(fig. 28/a)

To  set  the  maximum  pressure,  proceed  as

follows :

– Connect the pressure column to the pres-

sure inlet downstream of the gas valve. 

–For the 

“BF” 

models connect the pressu-

re column as shown in fig. 27/b. 

–Remove  the  plastic  cap  on  the  modula-

tor (1).

–Set  the  knob  of  the  D.H.W.  potentiome-

ter to the maximum value.

–Ignite the boiler and open the D.H.W. cock.

–Using  a  ø  9  spanner,  turn  the  nut  (3)  to

achieve  the  maximum  pressure  value

given in 

Table 4

: to reduce the pressure,

turn the nut counterclockwise; to increa-

se the pressure, turn it clockwise.

– Operate  the  main  switch  a  number  of

times, keeping the D.H.W. cock open all the

time,  and  check  that  the  pressure  corre-

sponds to the values given in 

Table 4

.

4.3.4

Minimum pressure adjustment

valve HONEYWELL 

(fig. 28/a)

After  adjusting  maximum  pressure,  pro-

ceed to calibrate minimum pressure:

– Disconnect  the  electric  power  supply

from the modulator. 

– With  the  hot  wat er  pot entiomet er

knob  set  t o  t he  maximum,  t he  ho t

water tap turned on and the burner lit,

hold nut (3) locked in place and simulta-

neously  turn  nut  (2)  using  a  fixed  ø  7

wrench  to  identify  the  minimum  pres-

sure  value  shown  in 

Table  4

:  turn  the

nut  anti-clockwise  to  reduce  pressure

or clockwise to increase it. 

–Turn  the  boiler  on  and  of f  repeatedly

while  keeping  the  hot  water  tap  turned

on,  checking  that  pressure  corresponds

to the values shown in 

Table 4.

–Connect  up  the  power  supply  to  the

modulator again.

–Replace the plastic cap (1).

4.4

ADJUSTMENT OF HEAT 

OUTPUT FOR HEATING

To  adjust  boiler  heat  output  for  heating  pur-

poses, i.e., modifying the setting made at the

factory  which  is  approximately  16  kW,  use  a

screwdriver to adjust the heating heat output

trimmer (1 fig. 21). To increase working pres-

sure,  turn  the  trimmer  clockwise;  to  reduce

pressure, turn the trimmer counterclockwise.

To  facilitate  the  operations  of  adjusting  heat

output,  see  the  pressure/heat  output  dia-

grams for natural gas (methane) and butane

or propane gas (figg. 29 - 29/a - 29/b).

KEY
1

Plastic cap

2

Minimum pressure adjusting screw

3

Maximum pressure adjusting nut

Fig. 28

Fig. 28/a

KEY
1

Plastic cap

2

Minimum pressure adjusting nut

3

Maximum pressure adjusting nut

11

10

9

8

7

6

5

4

3

2

1

8,1 (7.000) 11,6 (10.000)

17,4 (15.000)

23,2 (20.000)

POTENZA TERMICA kW (kcal/h)

PRESSIONE UGELL

O mbar

29,0 (25.000)

25

30

Fig. 29

Pressure/heat output diagram for natural gas (methane)

25

20

15

10

8,1 (7.000) 11,6 (10.000)

17,4 (15.000)

23,2 (20.000)

POTENZA TERMICA kW (kcal/h)

PRESSIONE UGELL

O mbar

30

5

29,0 (25.000)

25

30

Fig. 29/a

Pressure/heat output diagram for butane gas (G30)

HEAT OUTPUT kW (kcal/h)

N

OZZLE

PRESSURE

mbar

HEAT OUTPUT kW (kcal/h)

N

OZZLE

PRESSURE

mbar

Содержание FORMAT 25 BF

Страница 1: ...for the outlet of the products of the combustion is unobstructed and has been pro perly installed Make sure that any shutoff valves are open Make sure that the system is charged with water and is tho...

Страница 2: ...h electronic ignition and modulation natural draught FORMAT 25 BF 30 BF with electronic ignition and modulation room sealed forced draught The instructions given in this manual are provided to ensure...

Страница 3: ...1 1 CH setting range C 40 80 40 80 40 80 40 80 D H W setting range C 40 60 40 60 40 60 40 60 D H W flow rate EN 625 l min 10 5 12 7 10 5 12 7 Continuous D H W flow rate t 30 C l min 11 1 13 6 11 1 13...

Страница 4: ...n pump 11 Expansion vessel 12 Safety valve 13 Boiler discharge 14 Flowmeter 15 Thermomanometer 16 Automatic by pass 17 D H W filter 18 C H return cock optional 19 C H flow cock optional 20 D H W cock...

Страница 5: ...her makes optional The kit code 8093900 is supplied comple te with mounting instructions 2 3 CONNECTING UP SYSTEM Before proceeding to connect up the boiler you are recommended to make the air cir cul...

Страница 6: ...smokes coo ling in particular if located outside the building or in unheated ambiences Be set at an adequate distance from combustible or easily inflammable mate rial by means of an air gap or suitabl...

Страница 7: ...han 78 KEY 1a b Coaxial duct kit code 8084805 2a Extension L 1000 code 8096100 2b Extension L 500 code 8096101 3 Vertical extension L 200 with take off point code 8086908 4 Supplementaty 90 elbow code...

Страница 8: ...H2O vers 30 For head losses in the fittings refer to Table 2 79 TABLE 2 Accessories 80 Head loss mm H2O 25 version 30 version Inlet Outlet Roof outlet Inlet Outlet Roof outlet 90 elbow MF 0 30 0 40 0...

Страница 9: ...xceed 7 00 mm H2O 25 vers and 11 00 mm H2O 30 vers When calculating the lengths of pipe take into account the parameters given in the Table 2 80 Fig 13 120 80 160 KEY 1 Sponge rubber gasket 125 95 2 F...

Страница 10: ...emove the front panel and the two screws that anchor the control panel to the sides see point 4 7 The panel will tilt forward at a sufficient angle to allow access to the components To remove the prot...

Страница 11: ...as valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A SIT 503 control box TS 100 C safety stat TF Smoke stat FL Flowmeter P Circulation pump VP Divertor valve TAG Antifreeze st...

Страница 12: ...nals 22 23 2 10 5 25 OF 30 OF wiring diagram with HONEYWELL control box Fig 20 b KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A HONEYWELL S4565CF control box TS...

Страница 13: ...read with the temperature set on the potentio meter The adjustment range is between 40 and 60 C When the heating flow sensor is at 75 C the electronic limiter will trip and switch off the burner The b...

Страница 14: ...uent re ignition will depend on a tempe rature difference of 3 C detected by the SM sensor heating flow sensor ATTENTION It is essential that the opera tions described above be carried out by authoriz...

Страница 15: ...Y DEVICE This is a safety device against possible smoke emission into the ambience 14 fig 3 The safety device goes into action by blocking operation of the gas valve when the return of the smoke into...

Страница 16: ...tore TA 22 23 L N TA TA1 P R P1 R1 CIRCUITO CON VALVOLE DI ZONA CIRCUITO CON POMPE DI ZONA Fig 26 KEY TA TA1 Zone room stat VZ VZ1 Zone gas valve R R1 Zone relay CR CR1 Zone microvalve or relay contac...

Страница 17: ...mini mum values are factory set Consequently they must not be altered Only when you switch the appliance from one type of gas supply methane to another butane or propane it is permitted to alter the...

Страница 18: ...ater potentiometer knob set to the maximum the hot water tap turned on and the burner lit hold nut 3 locked in place and simulta neously turn nut 2 using a fixed 7 wrench to identify the minimum pres...

Страница 19: ...of the boiler Unscrew the connection 1 and the lock nut 5 Remove the bracket and the expansion vessel 4 NOTE Before refilling the system using a pressure gauge attached to the valve 3 make sure that...

Страница 20: ...he control box is faulty replace it Gas valve fails to modulate in D H W and C H modes The sensor is interrupted replace it The modulator has a break in winding replace it Check that the current to th...

Страница 21: ...ure that the requi red temperature is kept constant With the rotary switch in the winter position once the boiler has reached the value set on the heating potentiome ter it will start to modulate in a...

Страница 22: ...entive maintenance and checking of the efficient operation of the equipment and safety devices must be carried out exclusively by the authorized technical staff The boiler is supplied with an electric...

Страница 23: ...the clock display together with an indication of the incorrect program me To cancel all the programmes move the selector to the P position and press buttons 3 and 5 simultaneously Setting the SKIP fun...

Отзывы: