background image

01134592 – REF20/25 LB, PH, BB 

 

27

Parameter

Default Value

Range

Description

P4 Graph Display No

Yes, No

Determines whether to graph probe 4

P5 Graph Display No

Yes, No

Determines whether to graph probe 5

Door Heater
Door Heater

UR REF with 
Heated Glass 
Door: Yes 
All others: No

Yes, No

Controls door heater output

Door Heater Off 
(mins)

UR REF with 
Heated Glass 
door: 10

0 to 100

Off time for door heater if dht = on

Door Heater On 
(mins)

UR REF with 
Heater Glass 
door: 10

0 to 100

On time for door heater if dht = on

Error control
Probe Error

BPr

NO, BPr, R1 relay, R2 relay

Action to take when probe error detected

Control On Time 
(mins)

UR REF: 4

0 .0 to 120 .0 minutes

Compressor on time when control probe error 
(minutes)

Control Off Time 
(mins)

UR REF: 8

0 .0 to 120 .0 minutes

Compressor off time when control probe error

Calibration
Calibrate probes

Calibrate probes through a second menu

Viewable
Cut In

View cut in temperature

Cut Out

View cut out temperature

Probe 1 temp

View temperature of probe 1

Probe 2 temp

View temperature of probe 2

Probe 4 temp

View temperature of probe 4

Probe 5 temp

View temperature of probe 5

Power On Time 
(hrs)

View cumlitive hours that the unit was in service

Compressor 
cycles

The number of compressor starts

Compressor run 
time (hrs)

Veiw cumulative hours that the compressor was 
energized

Door open Cycles

The number of door opening

Door open time 
(hrs)

View cumulative hours that the door was open

Factory Reset
Reset

No

No, Yes

Reset all parameters to factory reset

Содержание REF20-BB

Страница 1: ...EF 20 25 PH REF 20 25 BB Order parts online www follettice com 01134592R15 H E A LT H C A R E TM 801 Church Lane Easton PA 18040 USA Toll free 877 612 5086 1 610 252 7301 www follettice com healthcare...

Страница 2: ...and care of the LCD touchscreen 8 Chart recorder set up if so equipped 15 Removing drawers 15 Removing slides 16 Network Enabled Device 16 Cleaning 16 Interior cleaning 16 Exterior cleaning 16 Annual...

Страница 3: ...less steel drawers Exterior width 29 75 76 cm 29 75 76 cm 29 75 76 cm 29 75 76 cm 29 75 76 cm 29 75 76 cm Exterior depth 29 74 cm 35 89 cm 29 74 cm 35 89 cm 29 74 cm 35 89 cm Exterior depth with handl...

Страница 4: ...ceed 60 RH A heated door is recommended for higher humidity ambients Clearances The top of the refrigerator must have 10 inches 25 4 cm of clear space above the refrigerator to ensure proper ventilati...

Страница 5: ...592 REF20 25 LB PH BB 5 Detail drawing REF20 30 5 78cm REF25 36 5 93cm 76 75 195cm 79 5 202cm 29 75 76cm 10 0 25 4cm Required Clearances 1 0 2 5 cm for power cord 2 0 2 5 cm if outlet directly behind...

Страница 6: ...nstall casters Fig 1 1 5 Install casters by hand one at a time using channel locks to tighten until caster meets against the bottom of cabinet Fig 1 2 6 Peel protective film from exterior walls of sta...

Страница 7: ...accine and Handling Toolkit cdc gov for proper placement of the probe within the cabinet to ensure proper performance 1 Remove probe and cap from the top bottle and fill with glycerine supplied with u...

Страница 8: ...when blinking Refrigeration set points Sleep functions Centrigrade to Fahrenheit Functions and Settings Probe set points Alarming functions Alarm mute Reset Product temperature is displayed in the upp...

Страница 9: ...and DOWN arrows to select product temperature Press to accept or to cancel Sleep Temperature Display Toggle ON to hide the temperature reading immediately on the home screen Set the Sleep Delay To au...

Страница 10: ...Alarm that will sound if the unit loses power for more than five minutes The Power Loss Alarm box will display every five minutes then the screen will sleep An audible alarm will sound every 30 second...

Страница 11: ...Settings 2 Select Advanced settings and enter code 1 1 1 1 Confirm with Check mark 3 Using the DOWN arrow scroll through Advanced Settings to Calibrate screen and select Calibrate 4 Place desired prob...

Страница 12: ...1 15AM 38 5F 39 8F 3 1 13 01 45AM 39 7F 39 8F 3 1 13 02 00AM 39 8F 39 9F 3 1 13 02 30AM 40 0F 39 7F 3 1 13 02 15AM 39 9F 39 8F 3 1 13 03 00AM 41 8F 39 5F 3 1 13 02 45AM 41 9F 39 6F 3 1 13 03 15AM 40 7...

Страница 13: ...right hand corner 4 A yellow alert box with downloading data will appear 5 Press to accept or to cancel 6 After the unit is done downloading a second yellow alert box will appear asking if you want t...

Страница 14: ...mpty Done Edit Master Code User Access Codes Electronic Lock Override Insert key turn lock Remove panel Depress plunger with screwdriver Light To turn the interior light on or off touch the Light icon...

Страница 15: ...t paper 1 Press and hold 3 button until pen begins to move off chart 2 Once the pen moves completely off chart unscrew knob counter clockwise at center of chart 3 Remove old chart and place new chart...

Страница 16: ...switch off located on the upper front facade panel and removing the power cord from the receptacle Interior cleaning Using a sponge or soft cloth clean unit with a non abrasive non chlorinated all pu...

Страница 17: ...ing The side panel in front of condenser may be completely removed for easier cleaning by disconnecting facade and removing upper side panel See Face Removal for facade removal instructions 3 Inspect...

Страница 18: ...tial determine the cut in and cut out points of the cooling system For instance a unit running with a defaulted set point of 3 3 C 38 F will have the cooling system cut in at 5 5 C 42 F and cut out at...

Страница 19: ...ounding strap when handling and installing control board Fig 33 1 Turn off power to unit and unplug 2 Disconnect electrical plugs and remove facade 3 Remove screw securing ground screw to refrigerator...

Страница 20: ...to a left hinged configuration requires a new door For heated door options other parts may be required If the unit has a heated door option consult technical service by calling 877 612 5086 or 1 610...

Страница 21: ...01134592 REF20 25 LB PH BB 21 Wiring diagram Embraco...

Страница 22: ...22 01134592 REF20 25 LB PH BB Wiring diagram Tecumseh...

Страница 23: ...01134592 REF20 25 LB PH BB 23 Refrigeration System HIGH PRESSURE VAPOR HIGH PRESSURE LIQUID LOW PRESSURE LIQUID LOW PRESSURE VAPOR FILTER DRIER COMPRESSOR EVAPORATOR CAPILLARY TUBE CONDENSER...

Страница 24: ...ction will hide the home screen It will display a blank screen temperature or time and date Screen Saver Timer 0 seconds 0 to 600 seconds Amount of Time before the screen saver initiates Change Keypad...

Страница 25: ...or Alarm 3 Alarm3 Reset 1 degrees 0 to 10 degrees Temperature difference to reset Alarm 3 General Alarm Reset Alarm Ringback 10 minutes 0 to 120 minutes Defines the time delay until the alarm will res...

Страница 26: ...ith log P1 Datalog No Yes No Log P1 to event log P2 Datalog No Yes No Log P2 to event log P4 Datalog Yes Yes No Log P4 to event log P5 Datalog No Yes No Log P5 to event log Defrost Manual Defrost No Y...

Страница 27: ...minutes Compressor on time when control probe error minutes Control Off Time mins UR REF 8 0 0 to 120 0 minutes Compressor off time when control probe error Calibration Calibrate probes Calibrate pro...

Страница 28: ...311 3 Condenser fan motor with blade 01179704 Not shown Cap tube and drier 00945378 4 Compressor with start capacitor relay and overload 01096015 5 Start components TECUMSEH TP model compressor includ...

Страница 29: ...shown Filter drier 01334069 4 Compressor with start components and drier 01334192 5 Start components 01334135 6 Evaporator with drier 01334044 7 Condenser with drier 01334101 Not shown Cord and plug k...

Страница 30: ...ot shown Complete facade assembly without KP without chart recorder 01144138 Not shown Complete facade assembly with KP without chart recorder 01144120 Not shown Complete facade assembly without KP wi...

Страница 31: ...ayonet male 00179579 Not shown Bayonet female 00179556 Not shown Facade locking clip 00931501 10 Battery pack 01053222 Not shown Battery pack wiring harness 01040278 Not shown Batteries AA 01053651 No...

Страница 32: ...ed right hand hinge 00939884 Not shown Glass door heated right hand hinge 00940007 1 Solid door right hand hinge 00996603 Not shown Key glass door 00945436 2 Lock glass door 00945444 Not shown Key sol...

Страница 33: ...k door bracket 01151547 Not shown Electronic lock cover After S N XXXXXX 01289990 Not shown KP ready solid door handle 01152065 Not shown Solid door KP ready RH with hinges 01152149 Not shown Solid do...

Страница 34: ...shown Basket assembly REF20 00939728 6 Shelf REF25 with supports 01015841 6 Shelf REF20 with supports 01015858 7 Pilaster 00901173 Not shown Pilaster screws 00902213 8 Support shelf 00156240 Not shown...

Страница 35: ...01134592 REF20 25 LB PH BB 35...

Страница 36: ...a garant a y evaluaci n del equipo son importantes para que podamos realizar un seguimiento de nuestro equipo y registrar el rendimiento de la maquinaria Por favor registre las garant as del equipo Fo...

Отзывы: