Horizon Elite 1010/1410 Ice Machines (Remote Condensing)

Refrigeration charge

All service on refrigeration systems must be performed in accordance with all federal, state and local laws. It is the 
responsibility of the technician to ensure that these requirements are met. Recharging ice machine to other than 
factory specifications will void the warranty.

R404A ice machine charge specifications

Model

Line Run

Total Charge

1010/1410 single-phase (Tecumseh)

0-100 ft (0-30.5 m)

12.5 lbs (5.44 kg)

1010 three-phase (Tecumseh)

0-100 ft (0-30.5 m)

12.5 lbs (5.44 kg)

1410 three-phase (Larkin)

0-100 ft (0-30.5 m)

10 lbs (4.54 kg)

Note: Condensing unit shipped with 0.5 lb of R404A charge.

Refrigerant replacement requirements

1.  Non-contaminated refrigerant removed from any Follett refrigeration system can be recycled and returned to 

the same system after completing repairs. Recycled refrigerant must be stored in a clean, approved storage 
container. If additional refrigerant is required, virgin or reclaimed refrigerant that meets ARI standard 700-88 
must be used.

2.  In the event of system contamination (for example, a compressor burn out, refrigerant leak, presence of 

non-condensibles or moisture), the system must be repaired, evacuated and recharged using virgin or 
reclaimed refrigerant that meets ARI standard 700-88.

3.  Follett LLC does not approve of recovered refrigerants. Improper refrigeration servicing procedures will void 

the factory warranty.

Evacuation

Evacuate the system to a level of 500 microns. When the 500 micron level is reached, close all valves. Allow the 
system to sit for approximately 20 minutes. During this period the system pressure should not rise. If the system 
pressure rises and stabilizes there is moisture in the system and further evacuation is needed. If the pressure 
continues to rise check the system for leaks.

Evaporator Unit Low-side or ice making head

Ambients

Minimum

Maximum

Air temperature

50 F/10 C 

100 F/37.8 C

Water temperature

1

 

45 F/7 C 

90 F/32.2 C

1

Ambient water temperature is measured in the ice machine water reservoir.

Ice capacity test

Ice machine production capacity can only be determined by weighing ice produced in a specific time period. 
1.  Replace all panels on ice machine.
2.  Disconnect the drain solenoid.
3.  Run ice machine for at least 15 minutes.
4.  Weigh and record weight of container used to catch ice.
5.  Catch ice for 15 or 20 minutes.
6.  Reconnect the drain solenoid.
7.  Weigh harvested ice and record total weight.
8.  Subtract weight of container from total weight.
9.  Convert fractions of pounds to decimal equivalents (ex. 6 lbs 8oz = 6.5 lbs).
10. Calculate production using following formula:

1440 min. x wt. of ice produced
Total test time in minutes

=

Production capacity/24 hr.

11. Calculated amount per 24 hours should be checked against rated capacity for same ambient and water 

temperatures in Ice Production Tables.

Содержание Horizon Elite Chewblet HCD1010NPS

Страница 1: ...service review this guide carefully before you begin your installation Should you need technical help please call our Technical Service group at 877 612 5086 or 610 252 7301 Please have your model num...

Страница 2: ...ng unit Electrical Min Circuit Ampacity Max Circuit HVACR breaker size 1010 Single Phase Tecumseh AJA7490ZXDPN 208 230 V 60 Hz 10 7A 15A 1010 Single Phase Tecumseh ASFR9510ZNAMC1 10 7A 15A 1410 Single...

Страница 3: ...bing 3 4 MPT x 1 slip 3 4 barb x 3 4 FPT 1 1 4 per foot 6 4 mm per 0 3 m Chassis drain plumbing Plug must be removed from John Guest fitting Route 3 8 drain tubing through knockout in back of docking...

Страница 4: ...se Larkin Approximate net weight 250 lb 114 kg All others 180 lb 82 kg Tecumseh AJA7490ZXDPN 200 lb 91 kg Tecumseh ASFS9516ZNAMC1 260 lb 118 kg Tecumseh AWA9513ZXDPN 202 lb 92 kg Tecumseh ASFS9516ZNAM...

Страница 5: ...n sides The intake and exhaust air grilles must provide at least 250 sq in 1615 sq cm of open area Air cooled ice machines 18 458 mm minimum clearance between discharge and air intake grilles A 21 26...

Страница 6: ...in Maximum overcurrent protection single phase 15A three phase 15A single phase 30A Tecumseh AWA9513ZXDPN single phase 25A Tecumseh ASFS9516ZNAMC1 three phase 25A Tecumseh AWA9517ZXDPN three phase 15A...

Страница 7: ...ty Weekly exterior care The exterior may be cleaned with a stainless cleaner such as 3M Stainless Steel Cleaner Polish or equivalent Monthly condenser cleaning air cooled icemaker only 1 Use a vacuum...

Страница 8: ...eaning cup until CLEANER FULL light comes on Do not overfill 4 Place one SaniSponge cleaning sponge in remaining sanitizing and cleaning solution and retain for Step 9 Note Do not use bleach to saniti...

Страница 9: ...disposable foodservice grade gloves insert dry SaniSponge cleaning sponge 9 Insert SaniSponge cleaning sponge soaked in SafeClean Plus from Step 4 10 Push both SaniSponge cleaning sponges down ice tra...

Страница 10: ...r switch ON Ice pushes SaniSponge cleaning sponges through ice transport tube Fig 9 13 Place a sanitary 2 gal or larger container in bin or dispenser to collect SaniSponge cleaning sponges and ice for...

Страница 11: ...Remote Condensing 11 Wiring diagram evaporator unit Gearmotor data Gearmotor current 2 8A 115 V Gearmotor torque out high amp trip point 5 6A Resistance of windings 115 vac gearmotor Bison White to B...

Страница 12: ...IVER HEATER L3 L2 T3 T2 COMPRESSOR CONTACTOR COIL see note A TERMINAL BOARD P1 HP LP T3 L3 START CAPACITOR WITH BLEEDER RESISTOR 4 6 1 L2 L3 T3 T1 F1 F2 FC FAN 1 POTENTIAL RELAY see note B 5 2 FAN 2 L...

Страница 13: ...Horizon Elite 1010 1410 Ice Machines Remote Condensing 13 1010 Single phase condensing unit wiring diagram Tecumseh ASFR9510ZNAMC1...

Страница 14: ...14 Horizon Elite 1010 1410 Ice Machines Remote Condensing 1410 Single phase condensing unit wiring diagram Tecumseh ASFS9516ZNAMC1...

Страница 15: ...Horizon Elite 1010 1410 Ice Machines Remote Condensing 15 1010 Three phase condensing unit wiring diagram Tecumseh ASFR9511ZFAMC1...

Страница 16: ...16 Horizon Elite 1010 1410 Ice Machines Remote Condensing 3 phase condensing unit wiring diagram Larkin...

Страница 17: ...diagram EVAPORATOR UNIT CONDENSER CONDENSER UNIT HEAD CONTROL VALVE CHECK VALVE COMPRESSOR LOW SIDE SERVICE VALVE W SERVICE PORT RECEIVER HIGH SIDE SERVICE VALVE W SERVICE PORT FILTER DRIER SIGHT GLAS...

Страница 18: ...approve of recovered refrigerants Improper refrigeration servicing procedures will void the factory warranty Evacuation Evacuate the system to a level of 500 microns When the 500 micron level is reach...

Страница 19: ...g ice to jam auger 2 Damaged shuttle mechanism 3 Intermittent drive output from PC board Evaporator will freeze causing a HI AMPS error 4 Gearmotor is unplugged 1 Clean ice machine Increase flushing f...

Страница 20: ...6 Remove and clean 9 Blinking Lo water power time delay Machine did not see water consumption while trying to make ice 1 Lack of refrigeration low refrigerant charge leak 2 Debris shorting reservoir p...

Отзывы: