FOLGER ADAM SECURITY INC.
A member of the Yale Security Group
200 Strike
200 Series Parts
Installation:
1. For proper installation of the 200 strike refer to the appropriate template drawing.
2. Prior to installation, make the necessary wire connections per the appropriate wiring diagram.
3. Proper operating voltage must be supplied to the strike if it is to function correctly. Voltage at the strike must be /- 10% of the
required voltage listed on the strike label.
4. To install the strike into the frame opening.
a. Position the wiring either down or up toward the back of the hollow metal frame, making sure it stays completely out of the way of
the strike so as not to pinch it when installing.
b. Mount the strike using screws supplied:
STRIKE MODEL
MOUNTING SCREWS
METAL FRAMES
(2) 12-24 X 1/2 FH PHIL MACH SCS
WOOD FRAMES
(2) 12 X 3/4 FH PHIL WOOD SCS
5. After installation, check the horizontal alignment. Be certain that the centerline of the latchboltis aligned with the centerline of the
strike keeper.
Problem
Strike is not relocking
or is not unlocking
Strike does not operate
when supplied to the
strike.
Strike operates
intermittently.
Solenoid overheating
or burned out.
Solenoid plunger
binding (plunger will
not extend or retract).
Solution
Check for proper voltage being
supplied to the strike.
Check for proper voltage being
energized.
Check all wiring.
Check the coil resistance of the
solenoid and compare it to the
chart located on the wiring
diagram to insure the correct
solenoid is being used.
Check for loose wire
connection.
Check for proper alignment
between strike keeper and bolt.
Realign face plate if necessary.
The keeper may not be
returning to the fully locked
position.
Check the strike with the door
open, if the strike relocks check
the horizontal alignment
between the strike keeper and
the latchbolt.
Check the solenoid assembly to
insure the solenoid plunger is
moving freely.
Check alignment between
solenoid plunger and slide.
Operation:
The Folger Adam 200 series electric strike is a solenoid operated
device.
1. NFS Operating mode (NON-FAIL SAFE)
When power is applied, the solenoid pulls the locking slide into
the unlocked position, allowing the door to be opened. If power
fails, the strike will remain locked.
NOTE: Non-fail safe strikes
for use in fire rated doors can only be operated by momentary
contact switching (energized only when the push button is held
depressed) and cannot be held in the unlocked position.
2. FAIL-SAFE OPERATING MODE
When power is applied, the solenoid pushes the locking slide into
the locked position and the door cannot be opened. If power fails
the strike will unlock.
NOTE: Non-fail safe strikes for use in fire rated doors can only be
operated by momentary contact switching (energized only when
the push button is held depressed) and cannot be held in the
unlocked position.
1. SOLENOID VOLTAGE:
24VDC is standard. Optional voltages available are 12VDC,
12VAC or 24 VAC.
NOTE: When control power source is AC, the strike is supplied
with an externally attached bridge rectifier. The solenoid is rated
for DC and cannot be used with AC. It can be used with a rectifier
however.
2. FAIL-SAFE
The strike is locked when energized. This feature should be used
for applications that require automatic unlocking in case of power
failure.
CAUTION: Fail-safe is not permitted with the UL fire door
accessory label.
OPERATIONAL NOTE:
This product may be provided fail-safe (FS) or fail-secure (NFS).
Fail safe versions allow exit in case of power failure. Fail secure
versions do not allow exit in case of power failure. Consult with
the local authority having juristiction concerning the installation of
this type of product as to whether listed panic hardware is
required to allow emergency exit from the secured area.
OPTIONAL FEATURES: