D. TERMINAL ROOF LOCATIONS

“Distance”  = minimum distance required for positioning of the outlet to  

         avoid adverse effects with respect to:

A.   A ventilation opening serving an occupied room, a toilet or a bathroom.
B.   A heating air supply, when the supply flows through an occupied room.
C.   A window that can be opened and that is near an occupied room, 

    a toilet or a bathroom.

To avoid adverse effects

Distance : outlet A, B, ou C

At the same roof level

> 6 m (*)

At a diffeerent roof level

> 3 m (*) (**)

At a lower positioned wall

> 2 m (**)

At a higher sloping surface

> 6 m (***)

(*)   If the required distance cannot be achieved, the outlet position rules  

    take precedence.
(**)  If the outlet is positioned at least 1 m higher than the intake supply  

    opening, or a window that can be opened.
(***) If the required distance cannot be achieved, the position of the outlet  

    must be at least 1 m above the highest facade/roof.

 INSTALLATION OF THE STOVE

This appliance must be installed by a qualified (CORGI) gas engineer, and 

must be installed in accordance with the Regulations and Standards listed 

in the front of this Manual.

Failure to comply with the instructions in this manual, or the regulations 

and standards will result in the Guarantee being void and could have 

hazardous consequences.

A. STOVE LOCATION

These appliances are designed with the “Firebox” raised up off the ground 

level by the built in “Base unit”.

Thus these appliances require no special Hearth arrangements, as 

the floor will not get hot and is protected by the steel construction 

of the “Base unit”.

· 

The appliance must not be fitted against a rear wall constructed from 

  a combustible material; a gap of 300mm should be given all round the  

  stove before combustible materials may be used in the wall construction.

· 

If the appliance has to be located in an opening, a minimum clearance  

  of 50mm should be alowed to non-combustible materials.

· 

The stove must be located at least 280mm from any combustible  

 materials.

· 

A combustible shelf may be fitted over the appliance, if in the case 

  of a 150mm or less deep shelf; there is at least 280mm clearance above

  the top of the stove. The shelf depth may increase at the same rate  

  as the increase in clearance; i.e. a shelf depth of 200mm would require  

  a clearance of 330mm.

B. GAS CONNECTION

It is important to ensure that all pipe work installed is fitted in accordance 

with BS6891 and is capable of supplying sufficient gas flow and pressure to 

meet the minimum pressures Technical section of this manual. A minimum 

pipe size of 15mm should be used for the gas supply to within 1 metre of 

the appliance. 8mm pipe may only be used for the final connection to the 

stove, or within 1 meter of the appliance. An 8mm nut and olive is supplied 

with the stove for the final pipe joint.

A gas supply tap must be installed in the supply pipe work in a location that 

is easily accessible, such that the appliance may be isolated if necessary.

Do not make any connections to the appliance until all supply pipes have 

been purged to expel any dust or debris. Failure to do this may result in a 

bloque injector or tap and will invalidate the guarantee.

Although a gas soundness test is made on all appliances before they leave 

the factory, the appliance should be tested for soundness before operating 

the stove. This is to ensure that the burner has not been damaged in transit.

C. PRESSURE TESTING

The gas pressure to the burner must be measured; this should be 

measured with all gas appliances after the gas meter operating on full, 

including this stove.

D. FLOOR PROTECTION (HEARTH)

These appliances are designed with the “Firebox” raised up off the ground 

level by the built in “Base unit”.

Thus these appliances require no special Hearth arrangements, as the floor 

will not get hot and is protected by the steel construction of the “Base unit”. 

Installer section

Содержание PICTOFOCUS

Страница 1: ...PICTOFOCUS _____ BALANCED FLUE APPLIANCES Installation servicing and user instructions ...

Страница 2: ... E CHILD PROOF F MANUAL MODE handset G DESIGNATED LOW FIRE AND HIGH FIRE H COUNTDOWN TIMER I MODES OF OPERATION J THERMOSTATIC MODE K PROGRAM MODE L AUXILIARY FEATURE M ECO MODE MANUAL TURN OFF Installer section INSTALLATION A VENTILATION B GENERAL BALANCED FLUE NOTES C TERMINAL LOCATIONS WALL MOUNTING D TERMINAL ROOF LOCATIONS INSTALLATION OF THE STOVE A STOVE LOCATION B GAS CONNECTION C PRESSURE...

Страница 3: ... and should not be touched The glass and frame on this appliance acts as a fireguard conforming to BS 1945 1971 and satisfies the Heating Appliance Fireguards régulations 1991 No part of the window or frame should be permanently removed IT DOES NOT GIVE FULL PROTECTION FOR YOUNG CHILDREN OR THE INFIRM extra protection should be considered for these conditions conforming to BS 6539 or BS 6778 Beari...

Страница 4: ...ed instead of batteries The module for fan speed control and light dimmer includes mains power together with batteries in the receiver for automatic backup in case of power outage Without using a mains adapter battery replacement is recommended at the beginning of each heating season Old or dead batteries should be removed immediately If left in the unit the batteries can overheat leak and or expl...

Страница 5: ... buttons simultaneously Minutes flash 6 To select minutes press or button 7 To confirm press and buttons simultaneously or wait E CHILD PROOF ON To activate press and buttons simultaneously displayed and the handset is rendered inoperable except for the off function OFF To deactivate press and buttons simultaneously disappears F MANUAL MODE handset BEFORE OPERATING 1 Make sure MANUAL knob on the G...

Страница 6: ...e button ignition operation by pressing and holding button for 10 sec immediately after installing batteries ON is displayed and 2 is flashing When change is complete 2 will change to 1 NOTICE If the pilot does not stay lit after several tries turn the main valve knob to OFF p XX WARNING STANDBY MODE PILOT FLAME Handset Press and hold button to set appliance to pilot flame TO TURN OFF FIRE Handset...

Страница 7: ...oom temperature is lower than the set temperature the flame height stays on high for a longer period of time If the room temperature is higher than the set temperature the flame height stays on low for a longer period of time One cycle lasts approx 20 min J THERMOSTATIC MODE ON Press button displayed preset temperature displayed briefly and then room temperature displayed OFF 1 Press button 2 Pres...

Страница 8: ...ntinue to PROGRAM 2 and set on and off times or stop programming at this point and PROGRAM 2 remains deactivated NOTE PROGRAM 1 and 2 use the same on Thermostatic and off temperatures for and Daily Timer Once a new on Thermostatic and or off temperature has been set that temperature becomes the new default setting NOTE If or Daily Timer are programmed for PROGRAM 1 and PROGRAM 2 on and off times t...

Страница 9: ...nce needs to be turned OFF manually for instance if the remote control is lost or the batteries become totaly flat the control valve must be accessed and the switch flipped to OFF marked 0 The picture below shows the control valve User instructions ...

Страница 10: ...nner flue and are safely vented to the outside environment The gap between the inner and outer flues is the channel by which the stove is supplied with air for combustion These concentric flues terminate outside of the property in a terminal this terminal will keep the expelled gasses and the fresh air for combustion seperate It is important that the terminal is not blocked a suitable guard maybe ...

Страница 11: ...m a internal or external corner 600 I Above ground roof or balcony level 300 J From a surface facing the terminal 600 K From a terminal facing the terminal 600 L From an opening in the car port e g door window into the dwelling 1200 M Vertically from a terminal on the same wall 1500 N Horizontally from a terminal on the same wall 300 P From a vertical structure on the roof 600 Q Above intersection...

Страница 12: ...50mm should be alowed to non combustible materials The stove must be located at least 280mm from any combustible materials A combustible shelf may be fitted over the appliance if in the case of a 150mm or less deep shelf there is at least 280mm clearance above the top of the stove The shelf depth may increase at the same rate as the increase in clearance i e a shelf depth of 200mm would require a ...

Страница 13: ...ould be placed such that it is only on top of the grate and not sitting on top of the burner Place the remaining five logs as shown in the picture below i e the logs are placed so that one end of each log reaches to the front of the fire and the other end rests on top of the large log at the rear of the fire C LOG ARRANGEMENTS LPG GAS Place the Large Log across the rear of the fire as shown in the...

Страница 14: ...as shown in the picture below F PEBBLE ARRANGEMENTS LPG GAS Place two of the Pebbles one at each end of the burner against the firebox 1 2 Position another two pebbles at the very front of the burner one either side of the pilot shield 3 4 Place three more pebble at the rear of the burner ensuring that the Gas Ports at the rear of the burner are not blocked 5 to 7 The picture below shows show the ...

Страница 15: ...ay be dangerous TROUBLESHOOTING THE GAS PILOT WILL NOT IGNITE OR STAY LIT Ensure the gas is turned on at the appliance and the meter cylinder Depress the control knob for at least twenty seconds once the pilot is alight to ensure the operation of the safety thermocouple valve Ensure that the pilot injector is not obstructed or blocked and it is free from any dust or dirt Ensure that the thermocoup...

Страница 16: ...16 Technical informations APPLIANCE DIMENSIONS PICTOFOCUS 860 PICTOFOCUS 1200 ...

Страница 17: ...focus 860 Nominal Input Gross kW 10 5 10 5 10 5 10 8 8 10 9 Gas Rate max m3 hr 1 073 1 073 1 073 1 117 1 073 1 117 0 312 Burner Pressure Hot mbar 10 9 10 9 10 9 13 10 9 13 28 9 Burner Injector Bray 1200 7 x ø 1 2mm 1200 7 x ø 1 2mm 1200 7 x ø 1 2mm 1200 7 x ø 1 2mm 1200 7 x ø 1 2mm 280 7 x ø 0 3mm Pictofocus 1200 Nominal Input Gross kW 10 5 10 5 10 5 10 8 8 10 9 Gas Rate max m3 hr 1 073 1 073 1 07...

Страница 18: ... described here are in accordance with the appliances described in the EC Type Examination Certificate No UK LHD 0359 0657R1 delivered by INTERTEK and comply with the essential requirements applicable to EN 613 2001 A1 2008 and Regulation UE 2016 426 Signed for and behalf of the manufacturer by Laurent Gaborit Directeur Général Viols le Fort le 14 octobre 2016 Appendix ...

Страница 19: ...19 Note ...

Страница 20: ...tion Édition Distribution Atelier dominique imbert S A S au capital de 102 355 euros 34380 Viols le Fort France Tel 00 33 0 4 67 55 01 93 Fax 00 33 0 4 67 55 77 77 Web www focus creation com Email info focus creation com ...

Отзывы: