Operating Manual EMGZ621A
23
Max. limit
Use:
The digital output and the LED „Max. Limit A+B“ will be activated if the
tension feedback passes over the threshold value stored here. All other
function is identical with
Min. limit
.
|A–B| > limit
Use:
The digital output and the LED „|A–B| > limit“ will be activated if the
difference of
material tension
A minus
material tension
B exceeds the value
stored here. All other function is identical with
Min. limit
.
Lowpass output 1 (A–B)
Use:
Each channel provides a lowpass filter to prevent noise which is added to
the output signal. This parameter stores the cut off frequency. The lower
the cut off frequency, the more sluggish the output signal on the terminals
will be (ref. to wiring diagram, fig. 6). Due to this filter, the output signal
will be much more stable in the case of high fluctuations of the force value.
The lowpass filter of the each output is independent to the other filters.
Range:
0.1
to
200.0
Default:
10.0
Increment:
0.1
Unit:
[Hz]
Scale output 1 (A–B)
Use:
This parameter stores which tension feedback value will give the maximum
signal (10V resp. 20mA) at the output.
Range:
A force value can be input. The value consists of 4 digits. The position of
the decimal point depends on the parameter
Force of sensor.
Default:
-
Unit:
[N, kN, cN]
or
[lb, klb, clb]
Configuration output 1 (A–B)
Use:
This parameter configures the current output signal.
Range:
0...20mA, 4...20mA
Default:
0...20mA
Содержание EMGZ621A
Страница 8: ...Operating Manual EMGZ621A 8 6 Dimensions fig 3 Dimensions E611002e...
Страница 11: ...Operating Manual EMGZ621A 11 7 2 Wiring Diagram fig 6 Wiring diagram EMGZ621A E621A0011e...
Страница 26: ...Operating Manual EMGZ621A 26 10 Serial Interface RS232 Optional...
Страница 31: ...Operating Manual EMGZ621A 31 13 Interface CAN Bus Option 14 Interface DeviceNet Option...