Operating Manual CMGZ100 

 

2.5

 

Controller release 

The CMGZ100 Tension Controller can be released over a digital input (12-30V AC or DC). As long as there is 
no signal the Tension Controller is locked and the output is zero. When the voltage is applied the Tension 
Controller starts operating and the output signal goes from zero to the required value that is needed for the 
desired tension. 
 

2.6

 

Limit switches 

The CMGZ100 provides a minimum switch (GW1) and a maximum switch (GW2). If the threshold is overrun 
the appropriate front-mounted LED lights up and a relay switches on (24V, 0.5A). The thresholds are being set 
with front-mounted 10-turn potentiometers R3 ad R4. 
The threshold value can be measured at pin X4 and X5. 
The relay outputs are available on the connerctor at z14/z16 and d14/d16. 

 

2.7

 

Overlaid line speed 

If  the Tension Controller is used in a line drive application the dynamic can be increased by using an available 
line speed signal, which is fed to the Tension Controller. The tension control loop then is only responsible for 
the correction of this signal. By setting jumper X24 to X25 the part of this overlaid controller signal can be 
adjusted. 
 
 

Содержание CMGZ100

Страница 1: ...ese Bedienungsanleitung ist auch in deutsch erh ltlich Bitte kontaktieren Sie die Vertretung im zust ndigen Land This operation manual is also available in german Please contact your local representat...

Страница 2: ...in case of malfunction the person responsible for system design has to establish specific safety procedures such as emergency stop ciruits etc Caution Improper handling may damage the fragile electro...

Страница 3: ...line speed 5 3 Wiring diagram 6 4 View of the setting elements 6 5 Operating the strain gauge amplifier 7 5 1 Calibrating the strain gauge amplifier 7 5 2 Lowpass filter 7 5 3 Setting the limit switc...

Страница 4: ...released over a digital input that is operated with 24VDC or AC The Tension Controller also has also a minimum and a maximum limit switch with relay outputs The pcb is built to European standard size...

Страница 5: ...the threshold is overrun the appropriate front mounted LED lights up and a relay switches on 24V 0 5A The thresholds are being set with front mounted 10 turn potentiometers R3 ad R4 The threshold valu...

Страница 6: ...ensors are connected using 2x2x0 75mm2 AWG 18 shielded twisted pair cable With cable length below 15m 2x2x0 25mm2 AWG 23 is also suitable The shield must be connected only to the Tension Controller si...

Страница 7: ...r similar The adjustment of the cutoff frequency is done by means of a non polarized capacitor using the following table Setting the cutoff frequency The corresponding capacitor is chosen with the fol...

Страница 8: ...0k as standard giving 10 The resistor value in k gives the percentage With no line speed the Jumper has to be in position X24 to give exact 100 6 3 Internal external tension reference To use the inter...

Страница 9: ...short circuit proof Controller release isolated input 12 30V AC or DC if input is inactive integral part and output are set to zero Limit switch 1 Minimum Adjustable with potentiometer corresponding t...

Страница 10: ...Operating Manual CMGZ100 10...

Страница 11: ...Operating Manual CMGZ100 11...

Страница 12: ...MS Italy Via Baranzate 67 I 20026 Novate Milanese Tel 39 02 39487035 Fax 39 02 39487035 fmsit fms technology com FMS USA Inc 2155 Stonington Ave Suite 119 Hoffman Estates IL 60169 USA Tel 1 847 519 44...

Отзывы: