VenTing inSTallaTion

Continued

Figure 19 - Firestop Spacer with Living 

Space Above Ceiling

Figure 20 - Firestop Spacer with Attic 

Space Above Ceiling

Existing 

Ceiling 

Frame

Firestop 

Spacer

Screws or 

Staples 

(Min. of 8)

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

Existing 

Ceiling 

Frame

Figure 21 - 10 Foot Rule

10 FOOT RULE

All chimney terminations must extend a mini-

mum of 3 feet above the highest point where it 

passes through the roof and must be at least 2 

feet above roof with a 10 foot horizontal span 

(see Figure 21).

IMPORTANT:

 If an exposed portion of chim-

ney is greater than 4 feet above the roofline, 

use support wires to keep chimney secure. 

Support wires may be attached to outer pipe 

of  chimney  with  screws,  if  screws  do  not 

penetrate inner flue pipe.

MINIMUM

HEIGHT

15 FT.

(4.5m)

MAXIMUM

HEIGHT

CHASE

TERMINATION

40 FT.

(12m)

Figure 22 - Maximum Chimney Height

Storm 

Collar

Flashing

Firestop 

Spacer

RLT-12D

RLT-12D STL-12D

MINIMUM / MAxIMUM CHIMNEY 

HEIGHT

The  minimum  height  of  the  chimney  (mea-

sured from the base of the fireplace to the flue 

gas outlet-end of pipe) is 16 feet for a straight 

run, 16 feet minimum for a run with 1 elbow set 

and 25 feet minimum for a run with 2 elbow 

sets. (A set consists of one starter elbow and 

one return elbow.)

Uncommon  circumstances  such  as  neigh-

boring hills, tall trees, or strong wind areas 

can cause down drafts in chimney system. 

In  such  cases,  going  beyond  the  minimum 

recommended height would be preferable to 

provide a better draw.

The fireplace height approved for any chim-

ney run with this fireplace system is 40 feet 

measured  from  bottom  of  fireplace  to  flue 

outlet-end of pipe (see Figure 22).

  WARNING:  Do  not  oper-

ate an unvented gas log set in 

this fireplace with the chimney 

removed.

Содержание (V)3612ST

Страница 1: ...roved to ANS Z21 60 or Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to deter mine the need to obtain ...

Страница 2: ... place clothing or other flammablematerialsonornear the appliance Never leave children unat tended when a fire is burning in the fireplace IMPORTANT Check local codes before installing this fireplace Models V 3612STseriesisawoodburningfire place intended and approved for installation in either residential homes or buildings of standard construction This fireplace system requires the utilization of...

Страница 3: ...ARNING Use solid wood or processed solid fuel fire logs only When processed wood fuel fire logs are used do not poke or stir the logs while they are burning Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use WARNING Always leave glass doors fully opened or fully closed when operating fireplace W...

Страница 4: ...acers on Sides of Fireplace Provide Required 1 2 5 cm Clearance 2 5 cm Min Clearance From Pipe to Combustibles 3 7 6 cm 12 30 4 cm Min From Perpendicular Side Wall to Fireplace Opening Typ Figure 3 Fireplace Clearances selecting location To determine the safest and most efficient location for the fireplace you must take into consideration the following guidelines 1 The location must allow for prop...

Страница 5: ...r should extend under fireplace a minimum of 1 1 2 The ember protector should be made of galvanized sheet metal 28 gauge minimum to prevent corrosion 6 Using screws or nails secure fireplace to the framing through flanges located on sides of the fireplace see Figure 8 Fireplace Installation Continued Figure 7 Ember Protectors Ember Protector Typ of 2 1 2 1 2 cm Maximum Figure 8 Nailing Flanges Nai...

Страница 6: ...NSION 52 1 2 MIN 133 3cm 36 1 2 MIN 92 7cm 8 MIN 20 3cm 16 MIN 40 6cm Figure 9 Hearth Extensions the front face must not be placed within 9 of fireplace opening Combustible materials above and projecting more than 1 1 2 from the fireplace front face see Figure 11 must not be placed less than 12 from effective opening of the fireplace NFPA STD 211 Sec 7 3 3 3 Mantels or any other combustible materi...

Страница 7: ...imney together exception see Figure 17 page 8 WARNING The opening in the collar around the chimney at the top of the fireplace must not be obstructed Neveruseblowninsula tion to fill the chimney enclosure Figure 13 Outside Air Kit Installation Secure to Collars with Duct Tape or Screws Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air Inlet Termination V...

Страница 8: ...stop Spacers FS 10 Firestop spacers are required at each point where the chimney penetrates a floor or ceil ing joist space Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials When the pipe passes through a framed opening into a living space above the firestop must be placed onto the ceiling from below as shown in Figure 19 page 9 The...

Страница 9: ... flue pipe MINIMUM HEIGHT 15 FT 4 5m MAXIMUM HEIGHT CHASE TERMINATION 40 FT 12m Figure 22 Maximum Chimney Height Storm Collar Flashing Firestop Spacer RLT 12D RLT 12D STL 12D Minimum Maximum Chimney Height The minimum height of the chimney mea sured from the base of the fireplace to the flue gas outlet end of pipe is 16 feet for a straight run 16 feet minimum for a run with 1 elbow set and 25 feet...

Страница 10: ...roof Caulk Storm Collar Flashing Flashing Installation Determine flashing to be used with roof open ing chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 24 DO NOT NAIL THROUGH FLASHING CONE Storm Collar Installation SC 10 Place storm collar over pipe an...

Страница 11: ... tile or other noncom bustible materials may overlap the front face provided they do not obstruct essential open ings like louvered slots or any other opening When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive Installing fireplace facing Any noncombustible material may be used for facing glass tile brick etc as long as proper clearances are adhered to...

Страница 12: ...ping approved by local codes When installing a gas line a shutoff valve designed for installation outside the appliance is recommended The gas pipe is intended for connection to a decorative gas appliance that operates using natural or propane LP gas only This appliance must have an automatic shutoff device and must comply with the Standard for Decora tive Gas Appliances for Installation in Vented...

Страница 13: ...ge 15 must be installed when using an unvented gas log set Operation and Maintenance Guidelines Glass Doors Bi fold glass doors are optional with this fireplace Check with your local distributor for availability To install glass doors refer to installation instructions that are included with kit When fireplace is in operation doors must be fully open or fully closed position only or a fire haz ard...

Страница 14: ...erials Chimney Have your chimney system cleaned and in spected regularly to ensure safe and efficient operation damper Mechanism The damper control lever is located inside the fire chamber see Figure 32 Make sure lever is cool before handling Pull down to close and push up to open Damper must be open when lighting a fire Not doing so will cause smoke spillage into the room When fireplace is not in...

Страница 15: ...in triple wall Double Wall Pipe support assembly 12S 12DM Also available in triple wall Outside Air Kit AK4 Vent Plaster Collar Vent Hood Connector Duct 4 x 3 Storm Collar SC2 1 Firestop Spacer FS 10 for Straight Pipe 30FS 10 for 30 Angled Run Flashing V6F 10DM 0 to 6 12 Pitch V12F 10DM 6 12 to 12 12 Pitch Round Top Termination RLT 12D Econo Top Termination STL 12D Bi Fold Glass Doors DG368ST Brus...

Страница 16: ...115603 01 Rev D 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Отзывы: