AIR FOR COMbUSTION AND VENTILATION

 WARNING: This heater shall 

not be installed in a room or space 

unless the required volume of in-

door combustion air is provided 

by the method described in the 

National  Fuel  Gas  Code,  ANSI 

Z223.1/NFPA 54,

 the 

International 

Fuel Gas Code,

 or applicable lo-

cal codes. Read the following in-

structions to insure proper fresh 

air for this and other fuel-burning 

appliances in your home.

Today’s homes are built more energy efficient 

than ever. New materials, increased insulation 

and new construction methods help reduce 

heat loss in homes. Home owners weather 

strip  and  caulk  around  windows  and  doors 

to keep the cold air out and the warm air in. 

During heating months, home owners want 

their homes as airtight as possible.
While it is good to make your home energy 

efficient, your home needs to breathe. Fresh 

air must enter your home. All fuel-burning ap-

pliances need fresh air for proper combustion 

and ventilation.
Exhaust fans, fireplaces, clothes dryers and 

fuel burning appliances draw air from the house 

to operate. You must provide adequate fresh 

air for these appliances. This will insure proper 

venting of vented fuel-burning appliances.

PROVIDING ADEQUATE 

VENTILATION 

The following are excerpts from N

ational Fuel 

Gas  Code. ANSI  Z223.1/NFPA  54, Air  for 

Combustion and Ventilation.

All spaces in homes fall into one of the three 

following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 6 through 8 will help 

you classify your space and provide adequate 

ventilation.

Unusually Tight Construction

The air that leaks around doors and windows 

may provide enough fresh air for combustion 

and ventilation. However, in buildings of un-

usually tight construction, you must provide 

additional fresh air.

Unusually tight construction is defined as 

construction where:

a.  walls and ceilings exposed to the out-

side  atmosphere  have  a  continuous 

water vapor retarder with a rating of 

one perm (6x10

-11

 kg per pa-sec-m

2

) or 

less with openings gasketed or sealed 

and

b.  weather stripping has been added on 

openable windows and doors and

c.  caulking  or  sealants  are  applied  to 

areas  such  as  joints  around  window 

and door frames, between sole plates 

and floors, between wall-ceiling joints, 

between wall panels, at penetrations 

for plumbing, electrical and gas lines 

and at other openings.

If your home meets all of the three criteria 

above, you must provide additional fresh air. 

See 

Ventilation Air From Outdoors

, page 8. 

If your home does not meet all of the three 

criteria  above,  proceed  to 

Determining 

Fresh-Air Flow For Heater Location

.

Confined Space and Unconfined Space

The 

National Fuel Gas Code ANSI Z223.1/

NFPA 54

 defines a confined space as a space 

whose volume is less than 50 cubic feet per 

1,000 Btu per hour (4.8 m

3

 per kw) of the ag-

gregate input rating of all appliances installed 

in that space and an unconfined space as a 

space whose volume is not less than 50 cubic 

feet per 1,000 Btu per hour (4.8 m

3

 per kw) 

of the aggregate input rating of all appliances 

installed in that space. Rooms communicating 

directly with the space in which the appliances 

are installed*, through openings not furnished 

with doors, are considered a part of the un-

confined space.
* Adjoining rooms are communicating only if 

there are doorless passageways or ventilation 

grills between them.

DETERMINING FRESH-AIR FLOW 

FOR FIREPLACE LOCATION

Determining if You Have a Confined or 

Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space: 

Includes the room in which you will 

install fireplace plus any adjoining rooms with 

doorless  passageways  or  ventilation  grills 

between the rooms.

Содержание HDL18NA

Страница 1: ...tch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference UNVE...

Страница 2: ...s an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on page 6 of this manual This appliance may be in stalled in an aftermarket permanently located manufactured mobile home where not prohib ited by local codes This appliance is only for ...

Страница 3: ...sent even though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous SAFETY Continued WARNING Do not use a blower insert heat exchanger insertorotheraccessorynotap proved for use with this heater WARNING Donotallowfans toblow...

Страница 4: ...tial operation slight smok ing could occur due to log curing and heater burning manufacturing residues 10 To prevent the creation of soot follow the instructions in Cleaning and Maintenance page 19 11 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated thevaporsfromtheseproductsmay create a white powder residue within burner box or on adjacent walls or fu...

Страница 5: ...ates contain important warranty and safety information 1 Remove logs and heater base assembly from carton Note Do not pick up heater base assem bly by burners This could damage heater Always handle base assembly by grate 2 Remove all protective packaging applied to logs and heater for shipment 3 Check heater for any shipping damage If heater is damaged call FMI PRODUCTS LLC at 1 866 328 4537 for r...

Страница 6: ...y tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the out side atmosphere have a continuous water vapor retarder with a rating of one perm 6x10 11 kg per pa sec m2 or less with openings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or seala...

Страница 7: ...than the maximum Btu Hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If the extra space provides an unconfined space remove door to adjoining 40 000 31 500 71 500 AIR FOR COMBUSTION AND VENTILATION Continued Figure 2 Ventilation Air from Inside Building Or Remove Door into Adjoining Room Option 3 Ve...

Страница 8: ...tilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo stat controlled power vent Heated air entering the attic will activate the power vent AIR FOR COMBUSTION AND VENTILATION Continued NOTICE Stateorlocalcodesmay only allow operationofthisappli ance in a vented configuration Check your state or local cod...

Страница 9: ...ARANCE TO COMBUSTIBLE MATERIALS Side Wall 16 Ceiling 42 Front 36 Carefully follow the instructions below This will ensure safe installation into a masonry UL127 listed manufactured fireplace or certi fied vent free firebox Minimum Clearances For Side Combustible Material Side Wall and Ceiling A Clearances from the side of the fireplace cabinet to any combustible material and wall should follow dia...

Страница 10: ... shelf and top of fireplace opening a hood is not required see Figure 6 Figure 6 Minimum Mantel Clearances Without Using Hood Minimum Noncombustible Material Clearances If Not Using Mantel Note If using a mantel proceed to If Using Mantel If not using a mantel follow the infor mation below You must have noncombustible material s above the fireplace opening Noncombustible materials such as slate ma...

Страница 11: ... DAMPER CLAMP ACCESSORY FOR VENTED OPERATION Note When used as a vented heater ap pliance must be installed only in a solid fuel burning fireplace with a working flue and con structed of noncombustible material For Massachusetts Residents Only Instal lation of this gas log set as a vented appliance in the Commonwealth of Massachusetts re quires the damper be permanently removed or welded in the fu...

Страница 12: ... not level heater will not work properly Installation Items Needed hardware package provided with heater approved flexible gas hose not provided if allowed by local codes sealant resistant to propane LP gas not provided electric drill with 3 16 drill bit flathead screwdriver 1 Apply pipe joint sealant lightly to male threads of fitting to be threaded into gas regulator Connect approved flexible ga...

Страница 13: ...ropane LP supply WARNING For natural gas units never connect heater to private non utility gas wells This gas is commonly known as wellhead gas Installation Items Needed Before installing heater make sure you have the items listed below external regulator supplied by installer piping check local codes sealant resistant to propane LP gas equipment shutoff valve test gauge connection sediment trap t...

Страница 14: ...nt Tee Cap Pipe Joint Nipple 3 Min Sediment Trap Gas Regulator Equipment Shutoff Valve With 1 8 NPT Tap Approved Flexible Gas Hose if allowed by local codes Natural From Gas Meter 5 W C to 10 5 W C Pressure Propane LP From External Regulator 11 W C to 14 W C Pressure We recommend that you install sediment trap in supply line as shown in Figure 13 Locate sediment trap where it is within reach for c...

Страница 15: ...eaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 14 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter natural gas or propane LP supply to equipment shutoff valve see F...

Страница 16: ...m of log must seat over pins on base as shown in Figure 17 2 Place middle log 2 onto base Holes in bottom of log must seat over pins on base as shown in Figure 17 3 Place front log 3 onto grate as shown in Figure 18 4 Place left top log 4 as shown in Figure 19 Match square peg on top of rear log 1 with square hole on bottom of left top log 4 Match round peg on top of middle log 2 with round hole o...

Страница 17: ...d to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If you op erateheaterwithdoorsclosed heat buildup inside fireplace willcauseglasstoburst Make suretherearenoobstructions across openings of fireplace You must operate this heater withafireplacescreeni...

Страница 18: ...Pattern Pilot Burner Thermocouple Pilot Burner Thermocouple Inspecting Burners Check pilot flame pattern and burner flame patterns often PILOT FLAME PATTERN Figure 21 shows a correct pilot flame pattern Figure 22 shows an incorrect pilot flame pat tern Incorrect pilot flame is not touching ther mocouple This will cause the thermocouple to cool When thermocouple cools heater will shut down If pilot...

Страница 19: ...due to excessive lint from carpeting bedding material pet hair etc WARNING Failure to keep the primary air opening s of theburner s cleanmayresultin sooting and property damage Once every year a qualified agency or certified chimney sweep should examine and clean the venting system of fireplace ODS PILOT AND BURNER Use a vacuum cleaner or small soft bristled brush to clean Burner Orifice Holder an...

Страница 20: ...hile in PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When control knob is pressed in and turned to pilot there is not spark at ODS pilot When control knob is pressed in and turned to pilot there is spark at ODS pilot but no ignition REMEDY 1 Reconnect ignitor cable 2 Free igni...

Страница 21: ...al or propane LP gas company 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 19 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 19 or replace burner orifice 2 Replace damaged burner 3 Replace gas regulator POSSIBLE CAUSE 1 Control knob not fully pressed in 2 Control knob not pressed in long enough 3 Equipment shutoff val...

Страница 22: ...e burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see page 9 4 Clean burner see Cleaning and Maintenance page 19 or replace burner orifice 1 Turn heater off when us ing furniture polish wax carpet cleaners or similar products 1 This is normal with most heaters If noise is exces sive contact qualified ...

Страница 23: ...ks see Checking Gas Con nections page 14 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 19 1 Locate and correct all leaks see Checking Gas Con nections page 14 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Con nections page 14 ...

Страница 24: ...www fmiproducts com 125001 01B 24 Parts MODELS HDL18NA HDL18PA HDL24NA and HDL24PA 1 9 10 2 16 4 15 15 8 11 13 5 12 3 14 7 6 17e 17c 17a 17d 17b ...

Страница 25: ... 1 9 122568 01 Screw 12 x 1 25 Hex Head 4 10 122569 01 Washer 4 11 099056 26 Orifice 0 1070 1 099056 19 Orifice 0 0670 1 12 099387 08 Pilot Tube 1 13 098249 01 ODS Nut 2 14 M11084 38 Screw HWH AB 8 18 x 0 38 2 15 M11084 26 Screw HWH AB 10 16 x 0 38 7 16 098354 01 Control Knob 1 17 123189 01 18 Log Set 1 123189 02 24 Log Set 1 17a 123190 01 Rear Log 1 123190 06 Rear Log 1 17b 123190 02 Middle Log 1...

Страница 26: ...t 1 866 328 4537 for information You can also write to the address listed on the back page of this manual Technical Service You may have further questions about installation operation or troubleshooting If so contact FMI PRODUCTS LLC at 1 866 328 4537 When calling please have your model and serial numbers of your heater ready You can also visit our web site at www fmiproducts com Service Hints Whe...

Страница 27: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Страница 28: ...is product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs associated with warranty repairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded ...

Отзывы: