www.fmiproducts.com

118197-01D

6

Figure 7 - Minimum Clearances for Termination Cap

LOCATION OF TERMINATION CAP

Fixed

Closed

Openable Fixed

Closed

V

V

V

V

V

V

V

V

X

X

V

X

G

G

J

F

B

B

K

N

H

I

A

N

E

L

D

B

M

A

C

B

V

V

A

G

G

B

TERMINATION CAP

AIR SUPPLY INLET

GAS METER

RESTRICTED AREA
(TERMINATION PROHIBITED)

A  =  clearance above grade, veranda, porch, deck, or
    balcony [*12" (30.5 cm) minimum]
B  =  clearance to window or door that may be opened 
    [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
    if between 10,000 and 50,000, 12" (30 cm) in Canada 
    if between 10,000 and 100,000; 12" (30 cm) in US if 
    greater than 50,000, 36" (91 cm) in Canada if greater 
    than 100,000]
C  =  clearance to permanently closed window
    [minimum 12" (30.5 cm) recommended to prevent
    condensation on window]
D  =  vertical clearance to ventilated soffit located above the
    terminal within a horizontal distance of 24" (61 cm) from
    the center-line of the terminal [18" (45.7 cm) minimum]
E  =  clearance to unventilated soffit [12" (30.5 cm) minimum]
F  =  clearance to outside corner (see below)
G  =  clearance to inside corner (see below)
H  =  *not to be installed above a meter/regulator assembly
    within 36" (91.4 cm) horizontally from the center line
    of the regulator

I  =  clearance to service regulator vent outlet [*72" (182.9 cm)
    minimum]
J  =  clearance to non-mechanical air supply inlet to building
    or the combustion air inlet to any other fireplace
    [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
    if between 10,000 and 50,000, 12" (30 cm) in Canada 
    if between 10,000 and 100,000; 12" (30 cm) in US if 
    greater than 50,000, 36" (91 cm) in Canada if greater 
    than 100,000]
K  =  clearance to a mechanical air supply inlet [*In Canada, 
    6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
    10 ft. (3 m) horizontally]
L  =  † clearance above paved side-walk or a paved driveway
    located on public property [*84" (213.3 cm) minimum]
M  =  clearance under veranda, porch, deck
    [*12" (30.5 cm) minimum ‡]
N  =  clearance above a roof shall extend a minimum of
    24" (61 cm) above the highest point when it passes
    through the roof surface and any other obstruction within
    a horizontal distance of 18" (45.7 cm) 

†  vent shall not terminate directly above a side-walk or paved driveway which is located between two
 

single family dwellings and serves both dwellings*

‡  only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
*      as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. 

Note:

 Local codes or regulations may require different clearances

A = 6" (15.2 cm)

Inside Corner

V

B

E

V

B = 6" (15.2 cm)

C = Maximum depth of 48" (121.9 cm)

 

for recessed location

D = Minimum width for back wall of 

 

recessed location -

 

Combustible - 38" (965 mm)

 

Noncombustible - 24" (61 cm)

E =  Clearance from corner in 

 

recessed location-

 

Combustible - 6" (15.2 cm)

 

Noncombustible - 2" (5.1 cm)

Outside Corner

Recessed Location

G

H

G = 12" (30.5 cm) minimum clearance

Balcony with No Side Wall

V

J

Combustible & 

Noncombustible

H = 24" (61 cm)

J = 20" (50.8 cm)

Balcony with Perpendicular Side Wall

C

D

C

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Openable

Содержание DVC36

Страница 1: ...HUYLFH DJHQF RU WKH JDV VXSSOLHU 7KLV DSSOLDQFH PD EH LQVWDOOHG LQ DQ DIWHUPDUNHW SHU PDQHQWO ORFDWHG PDQXIDFWXUHG PRELOH KRPH ZKHUH QRW SURKLELWHG E ORFDO FRGHV IWHUPDUNHW RPSOHWLRQ RI VDOH QRW IRU SXUSRVH RI UHVDOH IURP WKH PDQXIDFWXUHU 6WDWH RI 0DVVDFKXVHWWV 7KH LQVWDOODWLRQ PXVW EH PDGH E D OLFHQVHG SOXPEHU RU JDV WWHU LQ WKH RPPRQZHDOWK RI 0DVVDFKXVHWWV 167 5 HDYH WKLV PDQXDO ZLWK WKH DSSOLDQ...

Страница 2: ... UHSDLU WKLV ÀUHSODFH DYH ÀUHSODFH LQVSHFWHG DQQX DOO E D TXDOLÀHG VHUYLFH SHUVRQ SAFETY INFORMATION TABLE OF CONTENTS Safety Information 2 Local Codes 3 3URGXFW GHQWL FDWLRQ 3 Product Features 3 Pre Installation Preparation 4 Location of Termination Cap 6 Venting Installation Instructions 7 Replacement Parts 16 Technical Service 17 Accessories 17 Illustrated Parts Breakdown and Parts List 18 Warr...

Страница 3: ...223 1 NFPA 54 YDLODEOH IURP PHULFDQ 1DWLRQDO 6WDQGDUGV QVWLWXWH QF URDGZD 1HZ RUN 1 1DWLRQDO LUH 3URWHFWLRQ VVRFLDWLRQ QF DWWHU PDUFK 3DUN 4XLQF 0 Figure 1 Direct Vent Fireplace Glass Door Assembly Switch Bracket for Optional Remote and Blower Upper Louver Panel Lower Louver Panel Flue Collar Nailing Flange PRODUCT FEATURES 7KHVH DUH D IHZ IDFWV WKDW FDQ KHOS RX XQGHUVWDQG DQG HQMR RXU GLUHFW YHQW...

Страница 4: ... PXVW EH PDLQWDLQHG I RXU ÀUHSODFH LV WR EH LQVWDOOHG GLUHFWO RQ FDUSHWLQJ YLQ O WLOH RU DQ FRPEXVWLEOH PDWH ULDO RWKHU WKDQ ZRRG LW PXVW EH LQVWDOOHG RQ D PHWDO RU ZRRG SDQHO H WHQGLQJ WKH IXOO ZLGWK DQG GHSWK RI WKH ÀUHSODFH 6HH LJXUH RXU ÀUHSODFH LV GHVLJQHG WR EH XVHG LQ HUR FOHDUDQFH LQVWDOODWLRQV DOO RU IUDPLQJ PDWHULDO FDQ EH SODFHG GLUHFWO DJDLQVW DQ H WHULRU VXU IDFH RQ WKH EDFN VLGHV RU ...

Страница 5: ... 2 163 4 811 2 131 2 Nailing Tabs 36 Models 42 Models 127 7KLV UHSODFH LV LQ tended for use as supplemental KHDW 8VH WKLV UHSODFH DORQJ ZLWK RXU SULPDU KHDWLQJ V VWHP R QRW LQVWDOO WKLV UHSODFH DV RXU SULPDU KHDW VRXUFH I RX KDYH D FHQWUDO KHDWLQJ V VWHP RX PD UXQ V VWHP V FLUFXODWLQJ EORZHU ZKLOH XVLQJ UHSODFH 7KLV ZLOO KHOS FLUFXODWH WKH KHDW WKURXJK RXW WKH KRXVH Q WKH HYHQW RI D SRZHU RXWDJH R...

Страница 6: ...10 000 and 50 000 12 30 cm in Canada if between 10 000 and 100 000 12 30 cm in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L clearance above paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under ver...

Страница 7: ...UHVWRSV ZKHQ SHQHWUDWLQJ FHLOLQJV RU DWWLF VSDFHV I XVLQJ D YHQWLQJ FRQÀJXUDWLRQ RI RQO KRUL RQWDO YHQWLQJ ZLWK QR YHUWLFDO UXQ D ULVH IRU HYHU RI UXQ WRZDUG WKH WHUPLQDWLRQ LV UHTXLUHG RU LQVWDOODWLRQ RI ÀUHSODFH DW HOHYDWLRQV RI IHHW RU JUHDWHU SD VSHFLDO DWWHQWLRQ WR YHQWLQJ UHTXLUHPHQW UHFRPPHQGDWLRQV WARNING Read all instruc WLRQV FRPSOHWHO DQG WKRURXJKO EHIRUH DWWHPSWLQJ LQVWDOODWLRQ DLOXUH ...

Страница 8: ...SHV 3XVK SLSH VHF WLRQV WRJHWKHU DQG WZLVW RQH VHFWLRQ FORFNZLVH DSSUR LPDWHO RQH TXDUWHU WXUQ XQWLO WKH VHFWLRQV DUH IXOO ORFNHG VHH LJXUH Note RUL RQWDO UXQV RI YHQW PXVW EH VXSSRUWHG HYHU WKUHH IHHW 8VH ZDOO VWUDSV IRU WKLV SXUSRVH 8VH D HOERZ WR FRQQHFW YHQWLQJ V VWHP WR ÀUHSODFH ÁXH FROODU 7KH HOERZ LV GHVLJQHG WR EH WZLVW ORFNHG RQWR WKH IOXH FROODU DV GHVFULEHG LQ VWHS IMPORTANT R QRW DWWHP...

Страница 9: ...OH DQG DWWDFK WR H WHULRU ZDOO ZLWK ZRRG VFUHZV SURYLGHG VHH LJXUH 7KH VLGLQJ VWDQGRII PXVW VLW ÁXVK DJDLQVW WKH H WHULRU IDVFLD PDWHULDO 7 RQQHFWLQJ 9HQW DS ZLWK RUL LQWDO 9HQW Pipe 6OLGH WKH ZDOO ÀUHVWRS RYHU WKH YHQW SLSH EHIRUH FRQQHFWLQJ KRUL RQWDO UXQ WR YHQW FDS VHH LJXUH DUHIXOO PRYH ÀUHSODFH ZLWK YHQW DVVHPEO DWWDFKHG WRZDUG ZDOO DQG LQVHUW YHQW SLSH LQWR KRUL RQWDO WHUPLQDWLRQ 7KH SLSH R...

Страница 10: ...DO WHUPLQDWLRQ FDS WR YHQW SLSH DS PXVW EH removable for vent inspection DQG PDLQWHQDQFH WARNING Never run vent GRZQZDUG DV WKLV PD FDXVH H FHVVLYH WHPSHUDWXUHV ZKLFK FRXOG FDXVH D UH 2SHUDWLRQ RI improperly installed and main WDLQHG YHQWLQJ V VWHP FRXOG UHVXOW LQ VHULRXV LQMXU SURSHUW GDPDJH RU ORVV RI OLIH 5281 225 167 7 21 5HFRPPHQGHG SSOLFDWLRQV QVWDOODWLRQ XVLQJ FDELQHW VXUURXQGV 7KURXJK WKH ...

Страница 11: ... 1 2 min None 30 max 54 1 2 min 1 ft 48 max 66 1 2 min 2 ft 60 max 78 1 2 min 3 ft 84 max 90 1 2 min 4 ft 20 max Ground Floor Corner Venting Not to Exceed H Limits 6125 7 50 1 7 21 167 7 21 5HFRPPHQGHG SSOLFDWLRQV QVWDOODWLRQV UHTXLULQJ D YHUWLFDO ULVH RQ EXLOGLQJ H WHULRU Q LQVWDOODWLRQ XVLQJ VQRUNHO WHUPLQDWLRQ WR DFKLHYH RQH IRRW DERYH JURXQG 6QRUNHO WHUPLQDWLRQV DUH DYDLODEOH IRU LQVWDOODWLRQV...

Страница 12: ... RQWDO 7HUPLQDWLRQ RQ JXUDWLRQ IRU 9HQWLQJ 8VLQJ 7ZR OERZV 45 Elbow 25 217 6 67 0 167 7 21 86 1 7 2 2 6 7KH IROORZLQJ FRQÀJXUDWLRQV VKRZ WKH PLQLPXP YHUWLFDO ULVH UHTXLUHPHQWV IRU D KRUL RQWDO V VWHP XVLQJ WZR HOERZV 9HQWLQJ ZLWK 7ZR OERZV 9HUWLFDO 9 RUL RQWDO 1 RUL RQWDO 2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max LJXUH RUL RQWDO 7HUPLQDWLRQ RQ JXUDWLRQ IRU 9HQWLQJ 8VLQJ 7Z...

Страница 13: ...KH DUHD DERYH WKH FHLOLQJ LV DQ LQVXODWHG FHLOLQJ RU DQ DWWLF VSDFH QDLO ÀUHVWRS IURP WKH WRS VLGH 7KLV SUHYHQWV ORRVH LQVXODWLRQ IURP IDOOLQJ LQWR WKH UHTXLUHG FOHDUDQFH VSDFH I WKH DUHD DERYH WKH FHLOLQJ LV D OLYLQJ VSDFH LQVWDOO ÀUHVWRS EHORZ WKH IUDPHG KROH 7KH ÀUHVWRS VKRXOG EH LQVWDOOHG ZLWK QR OHVV WKDQ WKUHH QDLOV SHU VLGH VHH LJXUH VVHPEOH WKH GHVLUHG OHQJWKV RI SLSH DQG HOERZV QHFHVVDU W...

Страница 14: ...ERYH WKH ÀUVW ÁRRU LQFOXGLQJ VWRUDJH VSDFHV DQG FORVHWV RX PXVW HQFORVH SLSH RX PD IUDPH DQG VKHHWURFN WKH HQFORVXUH ZLWK VWDQGDUG FRQVWUXFWLRQ PDWHULDO 0DNH VXUH DQG PHHW WKH PLQLPXP DOORZDEOH FOHDUDQFHV WR FRPEXVWLEOHV R QRW ÀOO DQ RI WKH UHTXLUHG DLU VSDFHV ZLWK LQVXODWLRQ VENTING INSTALLATION INSTRUCTIONS Continued 9HUWLFDO 7HUPLQDWLRQ RQ JXUDWLRQV LJXUHV WKURXJK VKRZ IRXU GLIIHUHQW FRQ ÀJXUDW...

Страница 15: ...in 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 40 max Figure 23 Vertical Venting RQ JXUDWLRQ 8VLQJ 7ZR OERZV Vertical Round High Wind Termination Shown 45 Elbow 9HUWLFDO 9HQWLQJ V 40 max Figure 24 Vertical Venting RQ JXUDWLRQ LWK 1R RUL RQWDO 5XQ Vertical Round High Wind Termination Shown Note Install restrictor into inner collar of UHSODFH DV shown 45 Elbow ...

Страница 16: ...w 18 Screws HHTK 58 High Wind Round Horizontal Termination Kit Includes Round Termination VENTING INSTALLATION INSTRUCTIONS Continued Wall Firestop 45 Elbow Number Description HHT 58 High Wind Round Horizontal Termination Kit Galvanized HTS 58 Horizontal Square Termination Galvanized HTKS 58 Horizontal Square Termination Kit Includes Square Termination Wall Firestop 45 Elbow VT 58 Vertical Round T...

Страница 17: ...FDOO 0 352 8 76 DW IRU UHIHUUDO LQIRUPDWLRQ KHQ FDOOLQJ KDYH UHDG PRGHO QXPEHU RI RXU ÀUHSODFH WKH UHSODFHPHQW SDUW QXPEHU TECHNICAL SERVICE RX PD KDYH IXUWKHU TXHVWLRQV DERXW LQVWDOODWLRQ RSHUDWLRQ RU WURXEOHVKRRWLQJ I VR FRQWDFW 0 352 8 76 V XVWRPHU 6HUYLFH HSDUW PHQW DW KHQ FDOOLQJ SOHDVH KDYH RXU PRGHO DQG VHULDO QXPEHUV RI RXU KHDWHU UHDG RX FDQ DOVR YLVLW 0 352 8 76 V ZHE VLWH DW ZZZ IPLSURG...

Страница 18: ...www fmiproducts com 118197 01D 18 ILLUSTRATED PARTS BREAKDOWN 02 6 9 9 1 9 9 6 7 10 17 18 13 2 12 19 8 1 4 11 9 14 3 16 5 15 ...

Страница 19: ...ht Refractory Brick Panel 1 111298 02 Right Refractory Brick Panel 1 111301 02 Right Refractory Brick Panel 1 110990 01 Right Refractory Brick Panel 1 111216 01 Right Refractory Brick Panel 1 111298 01 Right Refractory Brick Panel 1 111301 01 Right Refractory Brick Panel 1 12 9 9 9 9 6 5 37 21 47 1 Firebox Assembly 1 2 Face Weldment 1 3 108010 01 108328 01 Door Assembly 1 108328 02 Door Assembly V...

Страница 20: ... WKLV SURGXFW DQG RU 0 352 8 76 ZKR ZLOO SURYLGH RULJLQDO IDFWRU UHSODFHPHQW SDUWV DLOXUH WR XVH RULJLQDO IDFWRU UHSODFHPHQW SDUWV YRLGV WKLV ZDUUDQW 7UDYHO KDQGOLQJ WUDQVSRUWDWLRQ GLDJQRVWLF PDWHULDO ODERU DQG LQFLGHQWDO FRVWV DVVRFLDWHG ZLWK ZDUUDQW UHSDLUV XQOHVV H SUHVVO FRYHUHG E WKLV ZDUUDQW DUH QRW UHLPEXUVDEOH XQGHU WKLV ZDUUDQW DQG DUH WKH UHVSRQVLELOLW RI WKH RZQHU FOXGHG IURP WKLV ZDUUD...

Отзывы: