background image

www.fmiproducts.com

109034-01H

14

opTional gaS line inSTallaTion

Continued

  WARNING:  If  the  fireplace 

has been used for wood burn-

ing, firebox and chimney must 

be cleaned of soot, creosote and 

ashes  be  a  qualified  chimney 

cleaner.  Creosote  will  ignite  if 

heavily heated.

operaTion and MainTenance

Figure 23 - Glass Doors

Cleaning Glass

Clean  glass  with  any  commercial  glass 

cleaner or soap and water. Do not use any 

abrasive material to clean the glass. Do not 

clean glass with any cool water if glass is still 

hot from fire and smoke.
A gas line or gas log lighter may be installed 

for the purpose of installing a vented or vent-

free decorative gas appliance incorporating an 

automatic shutoff device and complying with 

the S

tandard for Decorative Gas Appliances 

for  Installation  in  Vented  Fireplaces, ANSI 

Z21.60

  or 

American  Gas Association  draft 

requirements for Gas Fired Log Lighters for 

Wood Burning Fireplaces, Draft NO. 4

 dated 

August, 1993.
If you wish to install an unvented (vent-free) 

gas log set, only unvented gas log sets which 

have been found to comply with the standard 

for unvented room heaters, ANSI Z21.11.2 are 

to be installed in this fireplace.

  WARNING:  When  using 

a  decorative  vented  gas  log, 

damper  must  be  removed  or 

permanently locked in fully open 

position and glass doors must 

be in fully open position.

GLASS DOORS

Glass doors are optional with this fireplace. 

When fireplace is in operation, doors must be 

fully opened or fully closed position only or a 

fire hazard may be created (see Figure 23).
A fireplace equipped with glass doors oper

-

ates much differently than a fireplace with an 

open front. A fireplace with glass doors has a 

limited amount of air for combustion. Exces

-

sive heat within fireplace can result if too large 

a fire is built or if combustion air gate is not 

completely open.
The following tips should be used to assure 

that  both  fireplace  and  glass  door  retain 

their beauty and function properly. Both the 

flue  damper  and  glass  doors  must  be  fully 

opened before starting a fire. This will provide 

sufficient  combustion  air  and  maintain  safe 

temperatures in firebox.

IMPORTANT:

  The  glass  must  be  allowed 

to warm slowly and evenly. Tempered glass 

will withstand a gradual temperature rise to 

550° F, which is more than a normal fire will 

generate. Such materials as pitch/wax laden 

logs,  very  dry  mill  end  lumber  and  large 

amounts  of  paper  or  cardboard  boxes  can 

create an excessively hot fire and should not 

be burned in this fireplace. Always keep fire 

back from doors and never allow flames to 

contact glass.

  WARNING:  Fireplaces 

equipped  with  glass  doors 

should  be  operated  only  with 

doors fully opened or doors fully 

closed. Doors, if left partly open, 

may draw gas and flame out of 

the  fireplace  opening  creating 

risks of both fire and smoke.

Doors Fully Closed

Doors Fully Opened

Fireplace Front

Fireplace Front

Содержание B36

Страница 1: ... free gas log heater approved to ANS Z21 11 2 standard A FMI PROD UCTS LLC hood must be installed when using a vent free log heater see Accessories page 18 This wood burning fireplace complies with UL127 CAN ULC S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before install...

Страница 2: ...tydamageor loss of life Refer to this manual for assistance or additional in formation Consult a qualified installer or local distributor IMPORTANT Check local codes before installing this fireplace Before beginning installation of this fireplace read these instructions through completely This FMI PRODUCTS LLC fireplace and its components are safe when installed according to this installation manu...

Страница 3: ... 125 0 TO BOTTOM OUTSIDE AIR LEFT SIDE ONLY TOP SPACERS 0 75 AIR SPACE BACK AND SIDES HEARTH EXTENSION 52 X 16 12 EACH SIDE NOT LESS THAN 14 TO PERPENDICULAR SIDEWALL 1 AIRSPACE TO COMBUSTIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE SQUARE CHASE TOP TERMINATION GAS LINE KNOCK OUT AIR KIT KNOCK OUT ROUND TOP TERMINATION ...

Страница 4: ...sure ment includes fireplace chimney sections and height of termination assembly at level of flue gas outlet see Figure 18 page 11 Framing 1 Frame opening for fireplace using dimen sions shown in Figures 1 and 2 2 If fireplace is to be installed directly on carpeting tile other than ceramic or any combustible material other than wood flooring fireplace must be installed upon a metal or wood panel ...

Страница 5: ... obtained from manufacturer or supplier of noncombustible material If hearth extension is to be covered use noncombustible mate rial such as tile slate brick concrete metal glass marble stone etc Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material see Figure 3 WARNING Hearthextension is to be installed o...

Страница 6: ...ting Fireplace 6 Ref 6 Min 33 3 Nom Note Drawing Not To Scale Safe Zone For Projection of Combustible Materials Combustible Material 12 Min 9 Min Fireplace Opening Top of Louvered Opening Fan Blower Kit assembly Fan or blower kit is optional with this fireplace for circulating models only Use of blowers or fans other than those manufactured by FMI PRODUCTS LLC voids warranty Fan is operated by pre...

Страница 7: ...nt Hood Required for Wall Installation Air Inlet Eyebrow Vented Crawl Space Check Local Codes Before Installing in a Vented Crawl Space Venting Installation Optional Outside air Kit Model AK4 AK4F Installation of outside air kit should be per formed during rough framing of fireplace due to the nature of it s location Outside combus tion air is accessed through a vented crawl space AK4F or through ...

Страница 8: ... be obstructed Never use blown insulation to fill chimney enclosure Continue to assemble chimney sections as outlined making sure that both inner and outer pipe sections are locked together When installing double wall snap lock chimney to gether it is important to assure joint between chimney sections is locked Check by pulling chimney upward after locking Chimney will not come apart if properly l...

Страница 9: ...0 60 3 4 1 1 33 66 1 1 36 71 1 1 38 1 4 75 2 41 1 4 80 1 4 1 1 1 45 86 3 4 2 46 3 4 89 1 2 1 1 1 51 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 4 111 1 2 1 1 1 61 3 4 115 1 2 2 1 64 3 4 120 3 4 2 1 68 1 4 127 1 2 70 130 2 1 1 74 1 4 137 1 2 1 2 1 76 3 4 141 1 2 1 2 1 79 3 4 146 3 4 4 OFFSET CHART 22 50 FT SYSTEM HEIGHT 2 Min Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop...

Страница 10: ...ting to prevent leakage through screw holes A roof coating must also be ap plied around perimeter of flashing to provide a proper seal Firestop Spacers 3600FS 8DM 1 Firestop spacers are required at each point where chimney penetrates a floor space Their purpose is to establish and maintain required clearance between chimney and combustible materials When pipe passes through a framed opening into a...

Страница 11: ...termination being used Flashing Cone Venting Installation Continued Attach Bracket Tabs to Outer Pipe 3 Places Secure with Screws RTL 8DM Level of Flue Gas Outlet Caulk Collar Flashing Underlap Shingles Bottom Only Figure 17 Termination Overlap Shingles Top and Sides Terminations with 16 slip pipe sections are available RTT 8DM and RTTL 8DM are approved for flashing installations When needed these...

Страница 12: ...ct contact with sides and top around fireplace face It is important that combustible materials do not overlap face itself Brick glass tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings such as louvered slots When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive 30E 8DM EFFECTIVE HEIGHT OF TERMIN...

Страница 13: ...s line and refractory knockout hole with refractory cement or commercial furnace cement Install gas appliance or cap off gas line if desired CAUTION Allgaspipingand connections must be tested for leaks after installation is com pleted After ensuring that gas valveison applysoapandwater solution to all connections and joints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN F...

Страница 14: ...Glass Doors Glass doors are optional with this fireplace When fireplace is in operation doors must be fully opened or fully closed position only or a fire hazard may be created see Figure 23 A fireplace equipped with glass doors oper ates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Exces sive heat within fireplace can...

Страница 15: ... Re placegratewithFMIPRODUCTS LLC model 107001 01 only This gratehasbeendesignedtokeep the operation of your fireplace safe and efficient For further operating guidelines instruc tions and warranty information please re fer to your homeowner s guide or contact your authorized dealer Damper Handle 1 2 3 1 2 3 Damper Weight To Close Damper To Open Damper Figure 25 Damper Rod Technical Service You ma...

Страница 16: ...www fmiproducts com 109034 01H 16 Parts Wood burning Fireplace MODELS V B36 V B36I V B36L V B36LI 11 27 30 23 22 24 10 14 25 4 17 3 2 1 18 5 20 28 12 7 15 9 16 13 8 26 6 29 19 21 ...

Страница 17: ...06969 01 Rear Brick Liner 1 13 106970 01 Right Side Brick Liner 1 14 106972 01 Bottom Brick Liner 1 15 106973 01 Front Bottom Brick Liner 1 16 21198 Blower Access Plate 1 17 20027 Refractory Retainer 2 18 Top Insulation 1 19 Insulation Retainer 1 20 20280 Top Standoff 4 21 20023 Chimney Starter Collar 1 22 20088 Door Stop 1 23 11418 Push On Nut 2 24 20090 Spring Clip 2 25 107001 01 Wood Burning Gr...

Страница 18: ...NTI DRAFT SHIELD Round Top Termination Only ADS 8DM 30 Offset and return 30E 8DM 30E HT Adjustable Hood Antique Brass Finish GA6053 Black Painted Finish GA6050 Required when installing a vent free gas log in this fireplace Storm Collar SC1 1 For RT 8DM and RTL 8DM SC2 1 For RTT 8DM and RTTL 8DM Bi Fold Glass Door BDB36 Black BDB36B Brushed Brass BDB36P Platinum Firestop Spacer 3600FS 8DM 1 Fan Kit...

Страница 19: ...erminations with Slip Section RTT 8DM RTTL 8DM RTT 8HT RLTT 8HT Outside Air Kit for Side Wall Installation AK4 Outside Air Kit for Floor Installation AK4F Square Chase Top Termination ET 8DM ET 8DM ET 8HT Square Top Termination with Slip Section ETL 8DM ETL 8DM ETL 8HT Face Extension FE3602 Accessories Continued ...

Страница 20: ...109034 01 Rev H 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Страница 21: ...à gaz avec système d évacuation de gaz homolo guée selon les normes ANSI Z21 60 Z21 84 ou une bû cheàgazsanssystèmed évacuationhomologuéeselon la norme ANSI Z21 11 2 Une hotte FMI PRODUCTS LLC doit être installée si l appareil est utilisé avec un appareil de chauffage à bûche sans système d évacuation voir Accessoires page 20 CefoyeràboisestconformeàlanormeUL127 CAN ULC S610 M87 en tant qu APPAREI...

Страница 22: ...qualifié ou votre distributeur local IMPORTANT consultezlescodes locaux avant d installer ce foyer Lisez entièrement ces instructions avant de procéder à l installation de ce foyer CefoyerFMIPRODUCTS LLCetsespièces sont sûrs lorsqu ils sont installés conformé mentauxconsignesdecemanuel Vouscréez un risque d incendie si vous n utilisez pas de pièces FMI PRODUCTS LLC qui ont été conçues et testées p...

Страница 23: ...SUPÉRIEURE CARRÉE POUR ENCHÂSSURE TERMINAISON À TÊTE RONDE 2 5 cm 1 po PROLONGEMENT D ÂTRE 132 1 X 40 6 CM 52 x 16 PO 30 5 CM 12 PO DE CHAQUE CÔTÉ ENTRETOISES SUPÉRIEURES 0 CM PO COUCHE D AIR ARRIÈRE ET CÔTÉS 19 MM 3 4 PO AIR EXTÉRIEUR CÔTÉ GAUCHE UNIQUEMENT 0 CM PO VERS LE BAS COUCHE D AIR ENTRE LES MATÉRIAUX COMBUSTIBLES 2 5 CM 1 PO AUCUN MATÉRIAU COMBUSTIBLE SUR LA FAÇADE PANNEAU DE MUR COMBUST...

Страница 24: ...La distance maximale entre les coudes est de 1 9 m 2 pi Dans le cas des systèmes avec deux coudes la hauteur minimale est de 6 7 m 22 pi La hauteur maximale de tous les systèmes est de 15 m 50 pi Ces mesures comprennent le foyer les sections de la cheminée ainsi que la hauteur de la terminaison au niveau de la sortie du conduit de fumée voir figure 18 page 11 58 6 cm 22 po 95 6 cm 37 6 po 97 2 cm ...

Страница 25: ... formule suivante donne 0 25 x 2 5 cm 1 0 po 7 6 mm 0 30 po 0 84 d épaisseur requise Le coefficient de conductivité thermique K des matériaux peut être obtenu du fabricant ou du fournisseur de ces matériaux Si le prolonge ment d âtre doit être recouvert utilisez un ma tériau non combustible comme des carreaux de céramique de l ardoise de la brique du béton du métal du verre du marbre de la pierre ...

Страница 26: ...m 3 8 cm 1 5 po max 23 cm 9 po min 15 2 cm 6 po min 30 5 cm 12 po min Prêt à monter de ventilateur et de souffleur Un prêt à monter de ventilateur ou de souffleur pour ce foyer est offert en option pour les modèles à circulation uniquement L utilisation de ventilateurs ou de souffleurs autres que ceux qui sont fabriqués par FMI PRODUCTS LLC annulent la garantie Le ventilateur fonctionne en appuyan...

Страница 27: ...t du prêt à monter de gaine d air extérieur ATTENTION Les conduits d entrée d air comburant ne doivent pas donner dans le grenier La bouche d aération ne peut pas être placée à plus de 91 5 cm 3 pieds en dessous de la terminaison de sortie de gaz du conduit de cheminée Conduit de cheminée Le système de cheminée de FMI PRO DUCTS LLC comprend des sections de conduit amovibles encastrables à double p...

Страница 28: ...ssurer que le joint entre chacune des sections est verrouillé Après avoir verrouillé une section tirez la vers le haut pour vérifier La cheminée ne se sépa rera pas si le joint est correctement verrouillé Il n est pas nécessaire d ajouter de vis pour garder réunie la cheminée exception voir figure 11 page 10 Installation du système de ventilation suite Figure 8 Accroissement linéaire ACCROISSEMENT...

Страница 29: ...port de plafond 12S 8DM Coude de retour Coude de décalage Coude de retour Coude de décalage 1 8 m 6 pi max 1 8 m 6 pi max 1 8 m 6 pi max 1 8 m 6 pi max 1 8 m 6 pi max 1 8 m 6 pi max Coude de retour Coude de décalage Coude de décalage Coude de retour A B C Coude de décalage Support de plafond de conduit 12S 8DM Coude de retour 5 cm 2 po min Attaches Attaches Attaches Attaches Détail A Coude de reto...

Страница 30: ... 4 po 1 1 70 5 cm 27 3 4 po 144 1 cm 56 3 4 po 1 76 2 cm 30 po 154 3 cm 60 3 4 po 1 1 83 8 cm 33 po 167 6 cm 66 po 1 1 91 4 cm 36 po 180 3 cm 71 po 1 1 97 2 cm 38 1 4 po 190 5 cm 75 po 2 104 8 cm 41 1 4 po 203 8 cm 80 1 4 po 1 1 1 114 3 cm 45 po 220 3 cm 86 3 4 po 2 118 7 cm 46 3 4 po 227 3 cm 89 1 2 po 1 1 1 129 5 cm 51 po 246 4 cm 97 po 1 1 135 3 cm 53 1 4 po 256 5 cm 101 po 2 1 142 9 cm 56 1 4 ...

Страница 31: ...us haut point où celle ci passe à travers la toiture Figure 14 Dimensions des ouvertures dans la toiture Entretoises de pare feu 3600FS 8DM 1 Des entretoises de pare feu sont nécessaires à chaque endroit où la cheminée traverse un plancher Elles servent à créer et à conserver le dégagement nécessaire entre la cheminée et les matériaux combustibles Lorsque le conduit passe à travers une ouverture e...

Страница 32: ... les modèles RT 8DM et RTL 8DM qui peuvent être utilisés pour les solins ou les enchâssures et les modèles ET 8DM ETO 8DM ETL 8DM et ETLO 8DM pour les terminaisons de type à enchâssure uniquement La figure 17 montre une termi naison RTL 8DM à tête ronde ATTENTION Ne calfeutrez paslesouverturesdessolinsde la toiture Suivez les directives d installation fournies avec la terminaison utilisée Installa...

Страница 33: ...otection décorative com muniquez avec le fabricant pour obtenir les spécifications 45 6 cm 18 po min typ 61 cm 24 po min 61 cm 24 po min Figure 18 Installation avec plusieurs enchâssures Figure 19 Règle de 3 m 10 pi Règle de trois mètres dix pieds Toutes les terminaisons de sortie de conduit de fumée doivent dépasser d au moins 91 cm 3 pi au dessus du point le plus élevé où le conduit traverse la ...

Страница 34: ...Enlevez la plaque couvercle de la cana lisation de gaz située sur l un des côtés du foyer et sortez l isolant du manchon du conduit de la canalisation de gaz Conservez l isolant pour plus tard Installation du système de ventilation suite 30E 8DM Hauteur minimale de 4 42 m 14 5 pi Hauteur minimale de 4 42 m 14 5 pi 30E 8DM Hauteur minimale de 6 7 m 22 pi avec deux coudes hauteur maximale de 15 m 50...

Страница 35: ...eil est utilisé avec un ensemble de bûches à gaz sans système d évacuation voir Accessoires page 20 AVERTISSEMENT n utilisez pasunensembledebûchessans système d évacuation dans ce foyer s il n y a pas de cheminée Figure 22 Installation de la canalisation de gaz Installation d une canalisation de gaz en option suite Si vous installez un appareil au gaz décoratif bûche à gaz avec système d évacuatio...

Страница 36: ...e d incendie peut exister voir figure 23 Un foyer doté de portes vitrées fonctionne différemment d un foyer ouvert Un foyer avec portes vitrées dispose d une quantité limitée d air comburant Il y a une chaleur excessive dans le foyer si le feu est trop important ou si la prise d air comburant n est pas entièrement ouverte Les conseils suivants doivent être suivis pour garantir que le foyer et les ...

Страница 37: ...cezlagrille qu avec le modèle 107001 01 de FMI PRODUCTS LLC Cette grille a été conçue pour que le foyerfonctionnedemanièresûre et efficace Pour d autres consignes sur le fonctionne ment des instructions et des renseigne ments sur la garantie consultez le guide du propriétaire ou un marchand autorisé Poignée du clapet 1 2 3 1 2 3 Poids du clapet Pour fermer le clapet Pour ouvrir le clapet Figure 25...

Страница 38: ...www fmiproducts com 109034 01H 18 Pièces Foyer à bois MODÈLES V B36 V B36I V B36L V B36LI 11 27 30 23 22 24 10 14 25 4 17 3 2 1 18 5 20 28 12 7 15 9 16 13 8 26 6 29 19 21 ...

Страница 39: ... 01 Revêtement en brique droit 1 14 106972 01 Revêtement en brique inférieur 1 15 106973 01 Revêtement en brique inférieur frontal 1 16 21198 Plaque d accès au souffleur 1 17 20027 Dispositif de retenue de matériau réfractaire 2 18 Supérieure isolante 1 19 Dispositif de retenue d isolation 1 20 20280 Douille entretoise supérieure 4 21 20023 Collier de bas de cheminée 1 22 20088 Butoir de porte 1 2...

Страница 40: ...n à tête ronde uniquement ADS 8DM Décalage de 30 et retour 30E 8DM 30E HT Hotte réglable Fini laiton antique GA6053 Fini peint noir GA6050 Nécessaire pour l installation de bûches à gaz sans système d évacuation de gaz dans ce foyer Mitre SC1 1 pour RT 8DM et RTL 8DM SC2 1 pour RTT 8DM et RTTL 8DM Porte vitrée pliable BDB36 Noire BDB36B Laiton brossé BDB36P Platine Entretoise de chambre de combust...

Страница 41: ...e RTT 8DM RTTL 8DM RTT 8HT RTTL 8HT Prêt à monter de gaine d air extérieur pour installation sur un mur latéral AK4 Prêt à monter de gaine d air extérieur pour installation au sol AK4F Terminaison supérieure carrée pour enchâssure ET 8DM ET 8DM ET 8HT Terminaison supérieure avec section coulissante ETL 8DM ETL 8DM ETL 8HT Prolongement de façade FE3602 Accessoires suite ...

Страница 42: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Страница 43: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Страница 44: ...109034 01 Rev H 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Отзывы: