First Setup Using the Web Tool
First Setup Using the Web Tool
Instruction
This instruction is applicable to an installation of
• a “new” MAS
• a MAS for retro
fi
t of a CAS.
Follow these steps to set up using the web tool:
Step
Action
Detailed
instruction in
chapter
Settings
with the Web Tool
1
Enter user name (con
fi
g) and password (default is ef56)
in the web tool login dialog box and click OK.
Change Password
2
If you want to select another language for the web tool
interface, click Setup — General con
fi
guration – General
settings and select language.
Change Display
Language
3
Click (Setup — General con
fi
guration —) Unit
information and set unit information.
Set Unit Information
4
Click (Setup — General con
fi
guration —)
RS-485/Modbus and activate/con
fi
gure communication
for applicable connected units: Pump memory, Operator
panel, Relay Module, Power analyzer, Higher level
controller (Flygt APP/FMC or PLC).
Con
fi
gure
Communication
(RS-485, Modbus)
5
If there is
• a pump memory in the system, continue with step 6.
•
no
pump memory in the system (for example for
retro
fi
t of a CAS), continue with step 7.
6
Click (Setup —) Pump Info — Pump memory and
perform
Copy all from pump memory to MAS
.
Result:
“Synchronization OK!” con
fi
rms when the
synchronization is performed. The base unit is now set
up with the selection of sensors in the actual pump and
the recommended factory alarm settings. See the Quick
overview.
Copy Data To/From
Pump Memory
(in
chapter
Operation
)
7
Click Setup and a selected channel in the main
menu if you want to activate a channel or make any
additional/manual settings.
Make a Manual
Setting of a
Monitoring Channel
8
If the pump is installed in an explosive or
fl
ammable
environment, make sure that the motor overheating
protection function (Temp stator ph 1-3) is setup to stop
the pump, that is, an A-alarm. The protection function
must also be set to manual reset (not automatic).
Make a Manual
Setting of a
Monitoring Channel
52
Содержание MAS 711
Страница 1: ...Installation and Operation MAS 711 895115 10...
Страница 2: ......
Страница 5: ...Overview 5...
Страница 6: ......
Страница 8: ......
Страница 14: ......
Страница 22: ......
Страница 98: ......
Страница 108: ......
Страница 142: ......
Страница 148: ......
Страница 150: ...www flygt com Installation and Operation MAS 711 895115 10 20071212 ITT Flygt AB Printed in Sweden...