Wiring, Large Pumps, SubCab 24–lead Sensor Cable
Wiring, Large Pumps, SubCab 24–lead Sensor Cable
NOTE!
The wires of the sensor cable shall be connected to the cabinet connection block.
The numbers of the cabinet connection block will differ from the numbers of the base
unit terminal block.
Wire
Connection
This table shows the connection of the wires for a SubCab 24-lead sensor cable:
Sensor/Component
Sensor cable, no.
Base unit terminal
block, no.
1
13
FLS — Leakage in stator housing
1)
2
14
3
8
Pt100 — Temperature measurement,
main bearing
4
4
5
1
Thermal switches — Temperature
guard stator windings
6
2
7
15
FLS — Leakage in junction box
1)
(2)
(14)
8
3
Pt100 — Temperature measurement,
stator winding ph 1
(4)
(4)
Pump memory:
• RS–485 B
2)
9
38
• RS-485 A
2)
10
37
• Supply, ground
11
36
• Supply, 12V +
12
35
13
5
Pt100 — Temperature measurement,
stator winding ph 2
14
7
15
6
Pt100 — Temperature measurement,
stator winding ph 3
16
7
17
9
Pt100 — Temperature measurement,
support bearing
18
10
19
17
CLS — Leakage in oil housing
20
16
21
18
VIS 10 — Vibration sensor
22
19
(Screen)
If applicable, attach
screen to ground
terminals in the
• pump top
and
• electrical cabinet.
35
Содержание MAS 711
Страница 1: ...Installation and Operation MAS 711 895115 10...
Страница 2: ......
Страница 5: ...Overview 5...
Страница 6: ......
Страница 8: ......
Страница 14: ......
Страница 22: ......
Страница 98: ......
Страница 108: ......
Страница 142: ......
Страница 148: ......
Страница 150: ...www flygt com Installation and Operation MAS 711 895115 10 20071212 ITT Flygt AB Printed in Sweden...