background image

Multi Variable Air Conditioners

Duct Type Indoor Unit 

Models:

F

MV-ND224PH/A-T

F

MV-ND280PH/A-T

Air Conditioners

Owner's Manual

Thank you for choosing Air Conditioners, please read this owner’s manual carefully before 

operation and retain it for future reference.

 

 

 

 

 

 

Содержание FMV-ND224PH/A-T

Страница 1: ...rs Duct Type Indoor Unit Models FMV ND224PH A T FMV ND280PH A T Air Conditioners Owner s Manual Thank you for choosing Air Conditioners please read this owner s manual carefully before operation and r...

Страница 2: ...ialists to guide the disassembly 6 All graphics in this manual is only for your reference For sales or production reasons these graphics are subject to change by manufacturer without prior notice User...

Страница 3: ...Testing 9 4 4 Installation of Air Duct 11 4 5 Installation of Wired Controller 13 4 6 External Static Pressure Settings 13 5 Wiring Work 14 5 1 Connection of Wire and Patch Board Terminal 14 5 2 Powe...

Страница 4: ...specified on the nameplate And also take care of the power safety Installation should be conducted by dealer or qualified personnel Please do not attempt to install the unit by yourself Improper handl...

Страница 5: ...k or injury may happen Do not expose the unit to the moist or corrosive circumstances Volatile liquid such as diluent or gas will damage the unit appearance Only use soft cloth with a little neutral d...

Страница 6: ...y Bulb Temp C Wet Bulb Temp C Dry Bulb Temp C Wet Bulb Temp C Rated Cooling 27 19 35 24 Rated Heating 20 15 7 6 Indoor Unit Working Temperature Range 16 C 32 C 2 3 Unit Functions Unit Functions Wired...

Страница 7: ...be used for connecting the refrigerant pipe 4 M10 Nut Nut with Washer M10X8 4 To be used together with the hanger bolt for installing the unit 5 M10 Nut M10X8 4 8 To be used together with the hanger...

Страница 8: ...y still occur Unit mm 560mm 1000mm Nut with Washer Nut Spring Washer 2500mm Fig 3 2 Notes Installation of the unit must be in accordance with National Electric Codes and local regulations Improper ins...

Страница 9: ...e L 1000 2 0 75 IEC 60227 5 1 If the wire diameter is enlarged to 2 1 mm2 the total communic ation line length can reach 1500 m 2 The cord shall be Circular cord the cores shall be twisted together 3...

Страница 10: ...hatch after lifting the unit For the convenience of maintenance the service port should be on one side of the electric box and below unit s lower level 1 Below are the outline dimension applicable to...

Страница 11: ...nut and washer from upper and lower sides of the hanger bracket The washer fixing plate will prevent the washer from falling 4 The usage of paper pattern Refer to paper pattern of installation for cei...

Страница 12: ...stallation and Drainage System Testing 4 3 1 Notice for Installation of Drain Pipe 1 The drainage pipe should be short and the gradient downwards should be at least 1 2 in order to drain condensation...

Страница 13: ...etween screw nut and hose smaller than 4mm metal clamp accessory drain hose accessory 3 Use sealing plate to make the pipe clamp and hose insulated as shown in Fig 4 3 3 metal clamp accessory hermal s...

Страница 14: ...ng install hanger bracket at intervals of 1000 1500mm 1000 1500mm Fig 4 3 9 4 3 3 Test of Drainage System 1 Please test drainage system after electric work is finished Inject approximately 1L purified...

Страница 15: ...ested to be more than 150mm away from the wall Add a filter to the air return opening Please consider noise damping and vibration damping for the design and construction of air duct Besides noise sour...

Страница 16: ...t the parameter value and press ENTER CANCEL button to finish setting 3 Press ENTER CANCEL button to return to last step until exists setting parameters The parameter setting list is as following Para...

Страница 17: ...according to related regulations and electrical standards Keep cable away from refrigerant pipings compressor and fan motor The communication wires should be separated from power cord and connection...

Страница 18: ...lamp 5 3 Connection of Communication Wire between Indoor Unit and Outdoor Unit or indoor unit 1 Detach the electric box lid 2 Let the Communication cable pass through the wiring through holes 3 Connec...

Страница 19: ...for Connection of Wired Controller and Indoor Units Network 1 Communication wire of indoor unit and outdoor unit or indoor unit is connected to D1 D2 2 Wired controller is connected to H1 H2 3 One in...

Страница 20: ...Multi Variable Air Conditioners Duct Type Indoor Unit 17 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 H1 H2 D1 D2 D1 D2 Fig 5 5...

Страница 21: ...vacuum cleaner to remove dust If the filters are dirty wash them with warm water and mild detergent and dry the filters in the shade 2 If the unit used in the environment with much dust please clean...

Страница 22: ...ck or fire so please contact an authorized service center for professional service The following checks prior to contact may save your time and money Phenomenon Troubleshooting The unit can t start Po...

Страница 23: ......

Страница 24: ......

Отзывы: