Accuracy is specified for 1 year after calibration, at 18 

°

C to 28 

°

C

(64 

°

F to 82 

°

F) with relative humidity to 90 %. AC conversions are ac-

coupled, average responding, and calibrated to the rms value of a sine
wave input.

Accuracy specifications are given as follows:

±

 ( [ % of reading] + [number of least significant digits] )

Temperature coefficient of 0.1 x (specified accuracy) / 

°

C for <18 

°

C

or >28 

°

C (< 64.4 

°

F or > 82.4 

°

F)

Function

T5-600

Range

T5-1000

Range

Reso-
lution

Accuracy

K

600 V rms

1000 V rms

1 V

±

 (1.5 % + 2 digits)

L

600 V

1000 V

1 V

±

 (1 % + 1 digit)

?

100.0 A

100.0 A

0.1 A

±

 (3 % + 3 digits)

e

1000 

1000 

±

 (1 % + 2 digits)

Input Protection

Function

T5-600

T5-1000

Input Impedance

(nominal)

K

600 V rms

1000 V rms

1 M

, <100 pF ac-coupled

L

600 V rms

1000 V rms

1 M

, <100 pF

e

600 V rms

1000 V rms

---

Function

Open Circuit Test

Voltage

Short Circuit

Current

e

1.65 V dc (nominal)

<0.6 mA

CAT III protects against transients in a 

fixed equipment installation such

as a distribution panel, and lighting systems in large buildings.

CAT IV protects against transients from a  

primary supply such as an

electricity meter or an overhead or underground utility service.

Limited Warranty & Limitation Of Liability

This Fluke product will be free from defects in material and
workmanship for two years from the date of purchase. This
warranty does not cover fuses, disposable batteries, or damage
from accident, neglect, misuse or abnormal conditions of operation
or handling. Resellers are not authorized to extend any other
warranty on Fluke’s behalf. To obtain service during the warranty
period, send the defective product to the nearest Fluke Authorized
Service Center with a description of the problem.
THIS WARRANTY IS YOUR ONLY REMEDY. NO OTHER
WARRANTIES, SUCH AS FITNESS FOR A PARTICULAR
PURPOSE, ARE EXPRESSED OR IMPLIED. FLUKE IS NOT
LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR
CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM
ANY CAUSE OR THEORY.
Since some states or countries do not allow the exclusion or
limitation of an implied warranty or of incidental or consequential
damages, this limitation of liability may not apply to you.

10/96

Содержание T5-1000

Страница 1: ...ersonnel Use caution when working above 30 V ac rms 42 V ac peak or 60 V dc When using the probes keep your fingers behind the finger guards on the probes Connect the common test lead before you connect the live test lead Disconnect the live test lead first The display will not display hazardous voltages in display hold The voltage indicator LED continues to operate Symbols B AC alternating curren...

Страница 2: ...display hazardous voltages in display hold The voltage indicator LED continues to operate To exit the display hold mode press and release HOLD again or turn the rotary switch to a new position Automatic Power Down The tester turns off automatically if you do not turn the rotary switch or press HOLD for approximately 45 minutes To resume operation turn the tester off then turn the tester on Low Bat...

Страница 3: ...voltage Category IV Pollution Degree 2 Maximum Voltage between Current Fork and Earth Ground T5 600 and T5 1000 1000 V rms Overvoltage Category III also 600 V rms Overvoltage Category IV Pollution Degree 2 This dual rating applies to the current fork only Temperature Operating 10 C to 50 C 14 F to 122 F Storage 30 C to 60 C 22 F to 140 F Altitude Operating 2000 m 6562 ft Storage 10 000 m 32808 ft ...

Страница 4: ...and lighting systems in large buildings CAT IV protects against transients from a primary supply such as an electricity meter or an overhead or underground utility service Limited Warranty Limitation Of Liability This Fluke product will be free from defects in material and workmanship for two years from the date of purchase This warranty does not cover fuses disposable batteries or damage from acc...

Отзывы: